20068131
44
GB
Start-up, calibration and operation of the burner
6.9.3
Parameter list
Parameter
No. ele-
ments
Unit of
measure
Modifica-
tion
Value range
Degree of
accuracy
Default
setting
Acces mode
No. Description
Min.
Max.
000 INTERNAL PARAMETERS
050
Start backup/restore process via RDI21... / PC TOOL
(set the parameter to 1)
Index 0 = create backup
Index 1 = perform restore
Negative values indicate errors
2
-
Modification
-99
2
1
0; 0
Service mode
055
Burner identification number created from the backup
on RDI21...
1
-
Reading only
0
99999999
1
0
Service mode
056 ASN number created by the backup on RDI21...
8
-
Reading only
0
127
1
0
Service mode
057 Software Version created by the backup on RDI21...
1
-
Reading only
0x100
0xFFF9
1
0
Service mode
100 GENERAL PARAMETERS
102 Control box identification date
1
-
Reading only
0
255
1
Info mode
103 Control box identification number
1
-
Reading only
0
65535
1
Info mode
104 Identification number of the group of parameters set
1
-
Reading only
0
255
1
30
Info mode
105 Version of the group of parameters set
1
-
Reading only
0
0xFFFF
1
V 01.08
Info mode
107 Software version
1
-
Reading only
0
0xFFF9
1
V 03.30
Info mode
108 Software variation
1
-
Reading only
0
225
1
1
Info mode
111
ASN number to verify the ASN number created by the
backup on RDI 21…
8
-
Reading only
0
127
1
0
Service mode
113 Burner identification
1
-
Modification
0
99999999
1
Not defined
Info Mode with
password
Service Mode
121
Manual setting of output
Not defined = automatic operation
1
%
Modification /
zero setting
0%
100%
0.1%
Not defined
Info mode
123
Minimum output step position
Index 0: BACS output
Index 1: output of the external load regulator,
analogue.
Index 2: output of the external load regulator contacts.
3
%
Modification
0%
100%
0.1%
0% ; 1%;
0%
Service mode
124
Beginning flame loss test (TÜV test) (define the
parameter at 1) (switch of flame loss fuel valves) A
negative value indicates an error (see code 150)
1
-
Modification
-6
1
1
0
Service mode
125
Frequency of main power supply
0 = 50 Hz
1 = 60 Hz
1
-
Modification
0
1
1
0
Service mode
126 Brightness of display
1
%
Modification
0%
100%
1%
75%
Service mode
128
Fuel meter: Led pulse valence
(led pulses / volumetric flow units)
1
-
Modification
0
400
0.01
0
Service mode
130
Eliminate visualisation error chronology
To eliminate the visualisation, set the parameter to 1,
then to 2
Answer 0: process successful
Answer -1: time-out of 1_2 - sequence
1
-
Modification
-5
2
1
0
Service mode
133
Default output for TÜV test:
TÜV test not valid when output is activated
2,000 ..... 10,000 = low flame or first / second / third
stage
1
%
Modification /
zero setting
20%
100%
0.1%
Not defined
Service mode
141
Remote management of control box
0 = off
1 = Modbus
2 = reserved
1
-
Modification
0
2
1
0
Service mode
142
Standby time before a new attempt in event of com-
munication fault
Values set:
0 = not active
1 = .... 7200 s
1
s
Modification
0s
7200s
1s
120s
Service mode
143 Reserved
1
-
Modification
1
8
1
1
Info mode
144 Reserved
1
s
Modification
10s
60s
1s
30s
Service mode
145
Peripheral address for Modbus
Values set:
1 ... 247
1
-
Modification
1
247
1
1
Service mode
Summary of Contents for RS 34/E MZ
Page 2: ...Translation of the original instructions ...
Page 65: ...63 20068131 GB Appendix Electrical panel layout RS 34 E MZ ...
Page 66: ...20068131 64 GB Appendix Electrical panel layout RS 44 E MZ ...
Page 67: ...65 20068131 GB Appendix Electrical panel layout RS 44 E MZ 3Ph ...
Page 68: ...20068131 66 GB Appendix Electrical panel layout RS 34 44 E MZ ...
Page 69: ...67 20068131 GB Appendix Electrical panel layout RS 44 E MZ 3Ph ...
Page 70: ...20068131 68 GB Appendix Electrical panel layout ...
Page 71: ...69 20068131 GB Appendix Electrical panel layout ...
Page 72: ...20068131 70 GB Appendix Electrical panel layout ...
Page 73: ...71 20068131 GB Appendix Electrical panel layout ...
Page 75: ......