Start-up, calibration and operation of the burner
6.7
Operation
Once the start-up cycle is completed, the servomotor command
moves on to the thermostat/pressure switch TR that controls the
pressure or the temperature in the boiler.
If the temperature or the pressure is low, the burner progres-
sively increases the output as far as the MAX value.
If the temperature or the pressure increases, the burner pro-
gressively reduces the output as far as the MIN value. The
sequence repeats endlessly.
The burner stops when the heat request is less than the heat
supplied by the burner at MIN output.
The thermostat/pressure switch TL opens, the control box
carries out the switching off phase.
The air damper closes completely to reduce heat losses to a
minimum.
6.8
Ignition failure
If the burner does not switch on, there is a lockout within 3s of the
electrical supply reaching the gas valve.
It may be that the gas does not arrive at the combustion head
within the safety time of 3s.
In this case increase gas ignition flow rate. The arrival of gas to
the pipe coupling is displayed on the pressure gauge, as shown
in Fig. 35 on page 38.
6.9
Burner flame goes out during operation
If the flame should go out during operation, the burner will lockout
within 1s.
6.10
Stopping of the burner
The burner can be stopped by:
intervening on the disconnecting switch of the electrical sup-
ply line, located on the boiler panel;
using the switch “
0-AUTO
6.11
Final checks (with burner operating)
Tab. O
WARNING
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row.
If the burner locks out for a third time, contact the
customer service.
DANGER
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
manual and in compliance with the standards and
regulations of current laws.
Open the thermostat/pressure switch TL
Open the thermostat/pressure switch TS
The burner must stop
Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
Turn the air pressure switch knob to the maximum end of
scale position
The burner must stop in lockout
Turn off the burner and cut off the power
Disconnect the minimum gas pressure switch connector
The burner must not start
Disconnect the connector of the ionisation probe
The burner must stop in lockout due to ignition failure
WARNING
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
Summary of Contents for RS 310/EV O2 BLU
Page 2: ...Translation of the original instructions...
Page 46: ...20175134 44 GB Appendix Electrical panel layout...
Page 49: ...47 20175134 GB Appendix Electrical panel layout...
Page 50: ...20175134 48 GB Appendix Electrical panel layout...
Page 51: ...49 20175134 GB Appendix Electrical panel layout 0...
Page 52: ...20175134 50 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0...
Page 53: ...51 20175134 GB Appendix Electrical panel layout 0 1 1 1 2...
Page 59: ......