20175134
22
GB
Installation
5.7
Access to head internal part
The burner leaves the factory set for opening to the left, therefore
maintaining the pin 1)(Fig. 15) in the housing.
To open the burner towards the left, proceed as follows:
A
disconnect the plug/socket 9)(Fig. 15) of the maximum gas
pressure switch;
B
remove the screws 2);
C
open the burner to a maximum of 100-150 mm by rotating
around the hinge and release the cables of the probe 5) and
electrode 11);
D
fully open the burner as in Fig. 15;
E
undo the screw 4) with pressure test point;
F
release the head by lifting it from its housing 3), then take out
the combustion head.
WARNING
To open the burner from the opposite side, before
removing the pin 1)(Fig. 15), make sure that the 4
screws 2) are tight. Then shift the pin 1) to the op-
posite side, only then is it possible to remove the
screws 2). Disconnect the socket 9 (Fig. 15) of the
maximum gas pressure switch, then proceed as
described above at point (
C
).
Fig. 15
20069489
Summary of Contents for RS 310/EV O2 BLU
Page 2: ...Translation of the original instructions...
Page 46: ...20175134 44 GB Appendix Electrical panel layout...
Page 49: ...47 20175134 GB Appendix Electrical panel layout...
Page 50: ...20175134 48 GB Appendix Electrical panel layout...
Page 51: ...49 20175134 GB Appendix Electrical panel layout 0...
Page 52: ...20175134 50 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0...
Page 53: ...51 20175134 GB Appendix Electrical panel layout 0 1 1 1 2...
Page 59: ......