20081753
16
GB
Technical description of the burner
Technical data
Tab. H
Control box
Mains voltage
AC 230 V -15% / +10%
Mains frequency
50 / 60 Hz ±6%
Power absorption
< 30 W
Safety class
I, with components in compliance with II and III, ac-
cording to DIN EN 60730-1
Load on
‘input’ terminals
Fuse on the control box (can be inspected)
6.3 AT
Undervoltage
–
Safety switch-off from operating position to mains
voltage
–
Restart when mains voltage picks up
< AC 186V
> AC 195V
Cable length
–
Main line AC 230 V
–
Control load (TL1-TL2)
–
External reset button (RS)
–
Load exit (DC 0/2...10V)
–
Fuel valve
–
Other lines
Max. 100 m (100 pF / m)
Max. 20 m (100 pF/m)
Max 20 m (100 pF/m)
Max. 10 m (100 pF/m)
Max. 3 m (100 pF/m)
Max. 3 m (100 pF/m)
Environmental
conditions
Storage
–
Climatic conditions
–
Mechanical conditions
–
Temperature range
–
Humidity
DIN EN 60721-3-1
Class 1K3
Class 1M2
-20 ... +60 °C
< 95% RH
Transport
–
Climatic conditions
–
Mechanical conditions
–
Temperature range
–
Humidity
DIN EN 60721-3-2
Class 2K2
Class 2M2
-30 ... +60 °C
< 95% RH
Operation
–
Climatic conditions
–
Mechanical conditions
–
Temperature range
–
Humidity
DIN EN 60721-3-3
Class 3K3
Class 3M3
-20 ... +60 °C
< 95% RH
WARNING
Condensation, the formation of ice and the entry
of water are prohibited!