Maintenance
Voltage on the QRI cell
Minimum value for correct operation: 3.5V DC (value on AZL dis-
play at about 50%).
If the value is lower, it could be due to:
–
cell not positioned correctly
–
low voltage (lower than 187V)
–
bad regulation of the burner
In order to measure, use a voltmeter with a 10V DC scale con-
nected as in the diagram (Fig. 35).
Gas leaks
Make sure that there are no gas leaks on the pipe between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical As-
sistance Service in order to carry out the necessary adjustments.
Tab. N
7.2.4
Electrical panel
In the event of maintenance/replacement of components in the
lower part of the electrical panel, access is possible via the front
of the panel itself, following the directions below:
unscrew the screws 2) of the control panel 1);
extract the control panel 1) and turn it 90°, hooking it with the
brackets 3) in the profile of the electrical panel as shown in
Fig. 36;
after performing the operation, install the control panel 1) in
the electrical panel with the appropriate screws 2), arranging
the cables present.
7.2.5
Positioning the rpm sensor
To adjust, proceed as follows:
loosen the screws 3) and rest the sensor against the plate of
the disc 2);
referring to the scale 4) draw back the rpm sensor by about
a notch so that there is a distance of about 2 mm from the
disc plate 2).
Having correctly positioned the RPM sensor 1), tighten the
screws 3) with a torque of approximately 5±0.5 Nm.
Rpm sensor
2
Disc
3
Screw
4
Scale
EN 676
Air excess
CO
Max. output.
1.2
Max. output.
1.3
GAS
Theoretical
max CO
2
0 % O
2
CO
2
% Calibration
mg/kWh
= 1.2
= 1.3
G 20
11.7
9.7
9
100
G 25
11.5
9.5
8.8
100
G 30
14.0
11.6
10.7
100
G 31
13.7
11.4
10.5
100
DANGER
Turn off the burner's power supply using the main
system switch.
WARNING
Failure to install the control panel 1) in the seat of
the electrical panel, results in the machine's loss
of “IP” protection.
0...10 V
Ri > 10 M
:
X10-02 / 6
X10-02 / 4
X10-02 / 2
LMV...
+
D9174
Fig. 35
WARNING
In the event the rpm sensor is malfunctioning or
needs replacing, check/reset its position inside
the fan motor cover.
1
2
1
3
Fig. 36
20094732
Fig. 37
20087860
Summary of Contents for RS 1300/EV C01
Page 2: ...Translation of the original instructions ...
Page 40: ...20089633 38 GB Appendix Electrical panel layout ...
Page 41: ...39 20089633 GB Appendix Electrical panel layout ...
Page 43: ...41 20089633 GB Appendix Electrical panel layout ...
Page 44: ...20089633 42 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 45: ...43 20089633 GB Appendix Electrical panel layout 0 1 0 ...
Page 46: ...20089633 44 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1 ...
Page 47: ...45 20089633 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 4 ...
Page 48: ...20089633 46 GB Appendix Electrical panel layout 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 53: ......
Page 54: ......
Page 55: ......