20089633
10
GB
Technical description of the burner
4.8
Firing rates
The
MAXIMUM OUTPUT
is chosen from within the continuous
diagram area (Fig. 3).
The
MINIMUM OUTPUT
must not be lower than the minimum
limit of the diagram:
RS 1300/EV C01 FS1 = 2500 kW
RS 1600/EV C01 FS1 = 3065 kW
RS 2000/EV C01 FS1 = 4000 kW
4.9
Test boiler
The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 4).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the manufac-
turer.
The firing rates were set in relation to special test boilers, accord-
ing to EN 676 regulations.
In Fig. 4 you can see the diameter and length of the test combus-
tion chamber.
Example:
Output 13000 kW - diameter 120 cm - length 9 m
MODULATING RATIO
The modulating ratio, obtained in test boilers in accordance with
EN 676, is 1:5.
WARNING
The firing rate value (Fig. 3) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
shown on page 21.
Pressure in
combustion
h
ead
-
mba
r
Thermal power –
kW
Fig. 3
0
2
4
6
8
10
0
1000
3000
2000
7000
6000
5000
4000
8000
9000
12
10000 11000
12000 13000 14000
20000
14
16
18
20
22
24
26
28
30
32
34
15000 16000 17000 18000 19000
21000
20094546
RS 1300/EV
RS 1600/EV
RS 2000/EV
Fig. 4
Co
mb
usti
on chambe
r
leng
th
-
m
20099148
Thermal power
Summary of Contents for RS 1300/EV C01
Page 2: ...Translation of the original instructions ...
Page 40: ...20089633 38 GB Appendix Electrical panel layout ...
Page 41: ...39 20089633 GB Appendix Electrical panel layout ...
Page 43: ...41 20089633 GB Appendix Electrical panel layout ...
Page 44: ...20089633 42 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 45: ...43 20089633 GB Appendix Electrical panel layout 0 1 0 ...
Page 46: ...20089633 44 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1 ...
Page 47: ...45 20089633 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 4 ...
Page 48: ...20089633 46 GB Appendix Electrical panel layout 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 53: ......
Page 54: ......
Page 55: ......