20049577
6
GB
Technical description of the burner
3.1
Technical data
Tab. A
(1)
Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394” wc - Altitude 329 ft.
(2)
Pressure at test point 5) (Fig. 5), with zero pressure in the combustion chamber, and maximum burner output
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated
output.
3.2
Electrical data
Tab. B
3.3
Burner models designation
Tab. C
3
Technical description of the burner
Model
RS 1200/E BIOGAS/GPL C01 FS2
Output
(1)
max.
kW
MBtu/hr
5500 - 12000
18766 - 40944
min.
kW
MBtu/hr
1500
5118
Fuel
- max. delivery
- pressure at max. delivery
(2)
SCFH
“ wc
Natural gas
29973
17.9
Operation
Low - high or modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °C)
Combustion air temperature
°F max
140 (60 °C)
Noise levels
(3)
dBA
99
Fan motor
IE2
Control circuit power supply
V/Ph/Hz
120/1/60
Main power supply (+/- 10%)
V/Ph/Hz
575/3/60
Fan motor
rpm
V
HP
A
3520
575/795
34
30.8
Ignition transformer
V1 - V2
I1 - I2
120 V - 1 x 8 kV
1.6 A - 20 mA
Electrical power consumption
A max
33
Electrical control circuit consumption
W max
Total electrical consumption
kW
26
Electrical protection
NEMA 1
Model
Code
Voltage
Flame safeguard
RS 1200/E C01
20048377
575/3/60
Burner mounted
Summary of Contents for RS 1200/E BIOGAS/GPL C01 FS2