Installation
5.12.2 Gas train
Type-approved in accordance with EN 676 and supplied sepa-
rately from the burner.
To select the correct model of the gas train, refer to the “burner-
gas train combination” manual supplied.
5.12.3 Gas train installation
The gas train can enter the burner from the right or left side, de-
pending on which is the most convenient, see Fig. 27.
The gas train must be connected to the gas attachment
1)(Fig. 27), with the flange 2), the gasket 3) and the screws 4)
supplied with the burner.
See the accompanying instructions for the adjustment of the gas
train.
5.12.4 Gas pressure
indicates the pressure drop of the combustion head and the gas
butterfly valve depending on the operating output of the burner.
Tab. J
The values shown in refer to:
–
Natural gas G 20 NCV 9.45 kWh/Sm
3
(8.2 Mcal/Sm
3
)
–
Natural gas G 25 NCV 8.13 kWh/Sm
3
(7.0 Mcal/Sm
3
)
Column 1
Load loss at combustion head.
Gas pressure measured at the test point 1)(Fig. 28), with:
•
combustion chamber at 0 mbar;
•
burner working at maximum output;
Column 2
Pressure loss at gas butterfly valve 2)(Fig. 28) with maximum
opening: 90°.
DANGER
Disconnect the electrical power using the main
system switch.
Check that there are no gas leaks.
Beware of train movements: danger of crushing of
limbs.
Make sure that the gas train is properly installed
by checking for any fuel leaks.
The operator must use appropriate tools for instal-
lation.
WARNING
The gas solenoids must be as close as possible to
the burner, to ensure that the gas reaches the
combustion head within the safety time of 3s.
Ensure that the maximum pressure to the burner
is within the calibration range of the pressure reg-
ulator.
kW
1
p (mbar)
2
p (mbar)
G 20
G 25
G 20
G 25
RS 120
/EV
600
4.4
6.6
0.3
0.4
760
9.2
13.7
0.4
0.6
955
14.0
20.9
0.6
0.9
1170
18.7
27.9
0.8
1.2
1300
22.5
33.6
1.2
1.8
R
S
16
0/EV
930
5.6
8.4
0.0
0.0
1100
7.5
11.2
0.0
0.0
1300
9.7
14.5
0.8
1.2
1600
13.0
19.4
3.0
4.5
1860
17.7
26.4
3.8
5.7
RS 2
00/EV
1383
9.0
13.4
3.1
4.7
1500
10.7
16.0
3.7
5.5
1800
14.7
21.9
5.3
7.9
2100
20.3
30.3
7.2
10.7
2400
28.0
41.8
9.4
14.0
Fig. 27
D722
Summary of Contents for RS 120/EV BLU
Page 2: ...Translation of the original instructions ...
Page 43: ...41 20085953 GB Appendix Electrical panel layout ...
Page 45: ...43 20085953 GB Appendix Electrical panel layout ...
Page 46: ...20085953 44 GB Appendix Electrical panel layout ...
Page 47: ...45 20085953 GB Appendix Electrical panel layout ...
Page 54: ......
Page 55: ......