20145860
8
GB
Technical description of the burner
4.3
Technical data
Tab. B
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure on the socket 5) (Fig. 4) with zero pressure in the combustion chamber and at maximum burner output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
power is measured with the “Free Field” method, as per EN 15036, and according to an “Accuracy: Category 3” measuring accuracy, as set out in
EN ISO 3746.
4.4
Electrical data
Tab. C
4.5
Burner categories - Countries of destination
Tab. D
Model
RS 1000/M BLU
RS 1200/M BLU
Type
1133 T
1134 T
Output
(1)
Output
(1)
min - max
kW
1100/4000 - 10100
1500/5500 - 11100
Fuels
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
Gas pressure at max. output
(2)
-
Gas: G20/G25
mbar
67.1/101.2
97.2/145
Operation
–
Intermittent (min. 1 stop in 24 hours)
–
Progressive two-stage or modulating by kit (see accessories).
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 50
Combustion air temperature
°C max
60
Noise levels
(3)
Sound pressure
Sound power
dB(A)
85
99
89.3
99.7
Weight
Kg
460
500
Model
RS 1000/M BLU
RS 1200/M BLU
Electrical supply
3N ~ 400V +/-10% 50 Hz
Fan motor IE3
rpm
Hz
V
kW
A
2950
50
400/690
22
39,4/22,7
2930
50
400/690
25
44/25,4
Ignition transformer
V1 - V2
I1 - I2
230 V - 2 x 5 kV
1,9 A - 35 mA
Absorbed electrical power
kW max
25
28
Protection level
IP 54
Destination country
Gas category
SE - FI - AT - GR - DK - ES - GB - IT - IE - PT - IS - CH - NO
I
2H
DE
I
2ELL
NL
I
2 L -
I
2E -
I
2
(43.46 ÷ 45.3 MJ/m3 (0°C))
FR
I
2Er
BE
I
2E(R)B
LU - PL
I
2E
Summary of Contents for RS 1000/M BLU
Page 2: ...Translation of the original instructions ...
Page 45: ...43 20145860 GB Appendix Electrical panel layout ...
Page 46: ...20145860 44 GB Appendix Electrical panel layout 0 0 1 0 0 0 0 0 2 2 2 0 0 0 ...
Page 47: ...45 20145860 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 52: ...20145860 50 GB Appendix Electrical panel layout 0 12 3 4 5 4 5 6 7 8 9 8 9 0 0 0 0 ...