Start-up, calibration and operation of the burner
6.8
Adjustment pressure switches
6.8.1
Air pressure switch - CO check
Adjust the air pressure switch after having performed all other
burner adjustments with the air pressure switch set to the start of
the scale (Fig. 33).
With the burner working at MIN output, insert a combustion ana-
lyser in the stack, slowly close the suction inlet of the fan (for ex-
ample, with a piece of cardboard) until the CO value does not
exceed 100 ppm.
Slowly turn the appropriate knob clockwise until the burner goes
into lockout.
Check the indication of the arrow pointing upwards on the gradu-
ated scale (Fig. 33).
Turn the knob clockwise again, until the value shown on the grad-
uated scale corresponds with the arrow pointing downwards
(Fig. 33), and so recovering the hysteresis of the pressure switch
(shown by the white mark on a blue background, between the two
arrows).
Now check the correct start-up of the burner.
If the burner locks out again, turn the knob anti-clockwise a little
bit more.
6.8.2
Max. gas pressure switch
Adjust the maximum gas pressure switch after having performed
all the other burner adjustments with the pressure switch set at
the end of the scale (Fig. 34).
With the burner operating at maximum output, decrease adjust-
ment pressure by slowly turning the relative knob anti-clockwise
until the burner locks out.
Then turn the knob clockwise by 2 mbar and repeat burner start-
ing to ensure it is uniform.
If the burner locks out again, turn the knob anti-clockwise again
by 1 mbar.
6.8.3
Min. gas pressure switch
Adjust the minimum gas pressure switch after having performed
all the other burner adjustments with the pressure switch set at
the start of the scale (Fig. 35).
With the burner operating at maximum output, increase adjust-
ment pressure by slowly turning the relative knob clockwise until
the burner locks out.
Then turn the knob anti-clockwise by 2 mbar and repeat burner
starting to ensure it is uniform.
If the burner locks out again, turn the knob anti-clockwise again
by 1 mbar.
6.8.4
Pressure switch PVP kit
Adjust the pressure switch for the valve leak detection control de-
vice (PVP kit) (Fig. 36), if present, according to the instructions
supplied with the kit itself.
Fig. 33
D3854
Fig. 34
D3856
Fig. 35
D3855
Fig. 36
D3855
Summary of Contents for RLS 800/EV MX
Page 2: ......
Page 38: ......
Page 75: ...37 20010950 Appendix Annexe 0 0 0 0 0 0 0 00 0 0 00 1 2 2 2 3 2 4 2 2 2 2 2 2 2 2 2 2 3 2 ...
Page 76: ...20010950 38 Appendix Annexe ...
Page 78: ...20010950 40 Appendix Annexe ...
Page 79: ...41 20010950 Appendix Annexe 0 1 1 1 ...
Page 80: ...20010950 42 Appendix Annexe 0 ...
Page 81: ...43 20010950 Appendix Annexe 0 0 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2 ...
Page 82: ...20010950 44 Appendix Annexe 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 85: ...47 20010950 Appendix Annexe ৼ 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3 ...