20010950
12
GB
Technical description of the burner
4.12 Control box for the air/fuel ratio (LMV52...)
Warning notes
All activities (mounting, installation and service work, etc.)
must be performed by qualified staff.
Before making any wiring changes in the connection area of
the LMV52..., completely isolate the plant from mains sup-
ply (all-polar disconnection). Ensure that the plant cannot
be inadvertently switched on again and that it is indeed
dead. If not observed, there is a risk of electric shock haz-
ard.
Protection against electrical shock hazard on the LMV52...
and on all connected electrical components must be
ensured through appropriate mounting.
Each time work has been carried out (mounting, installation
and service work, etc.), check to ensure that wiring is in an
orderly state, that the parameters have been correctly set
and make the safety checks.
Fall or shock can adversely affect the safety functions.
Such units must not be put into operation even if they do not
exhibit any damage.
In programming mode, the position check of actuators and
VSD (checking electronic fuel / air ratio control) is different
from the check during automatic operation.
Like in automatic operation, the actuators are still jointly
driven to their required positions. If an actuator does not
reach the required position, corrections are made until that
position is reached.
However, in contrast to automatic operation, there are no
time limits to these corrective actions.
The other actuators maintain their positions until all actua-
tors have reached the positions currently required.
This is essential for setting fuel /air ratio control. This means
that during the time the fuel / air ratio curves are pro-
grammed, the person making the plant settings must contin-
uously monitor the quality of the combustion process (e.g.
by means of a flue gas analyzer).
Also, if combustion levels are poor, or in the event of dan-
gerous situations, the commissioning engineer must take
appropriate action (e.g. switching off manually).
To ensure the safety and reliability of the LMV52... system, the
following points must also be observed:
– Condensation and ingress of humidity must be avoided.
Should such conditions occur, make sure that the unit will be
completely dry before switching on again!
– Static charges must be avoided since they can damage the
unit’s electronic components when touched.
Mechanical design
The LMV52... is a microprocessor-based burner management
system with matching system components for the control and su-
pervision of forced draft burners of medium to large capacity.
The following components are integrated in the basic unit of the
LMV52...:
• Burner control with gas valve proving system
• Electronic fuel / air ratio control with a maximum of 6 actuators
• Optional PID temperature / pressure controller (load control-
ler)
• Optional VSD moduleMechanical design
Installation notes
• Ensure that the electrical wiring inside the boiler is in compli-
ance with national and local safety regulations.
• Do not mix up live and neutral conductors.
• Make certain that strain relief of the connected cables is in
compliance with the relevant standards (e.g. as per DIN EN
60730 and DIN EN 60 335).
• Ensure that spliced wires cannot get into contact with neigh-
boring terminals. Use adequate ferrules.
• Always run high-voltage ignition cables separately while ob-
serving the greatest possible distance to the unit and to other
cables
• The burner manufacturer must protect unused AC 230 V ter-
minals with dummy plugs (refer to sections Suppliers of other
accessory items).
• When wiring the unit, ensure that AC 230 V mains voltage ca-
bles are run strictly separate from extra low-voltage cables to
warrant protection against electrical shock hazard.
WARNING
To avoid injury to persons, damage to prop-
erty or the environment, the following warn-
ing notes must be observed!
The LMV52... is a safety device!
Do not open, interfere with or modify the
unit.
Riello S.p.A. will not assume responsibility
for any damage resulting from unauthorized
interference!
Risk of explosion!
Incorrect configuration can lead to excessive
fuel supply which might cause an explosion!
Operators must be aware that incorrect set-
tings made on the AZL5… display and operat-
ing unit and incorrect settings of the fuel and /
or air actuator positions can lead to danger-
ous burner operating conditions.
D9301
Fig. 7
Summary of Contents for RLS 800/EV MX
Page 2: ......
Page 38: ......
Page 75: ...37 20010950 Appendix Annexe 0 0 0 0 0 0 0 00 0 0 00 1 2 2 2 3 2 4 2 2 2 2 2 2 2 2 2 2 3 2 ...
Page 76: ...20010950 38 Appendix Annexe ...
Page 78: ...20010950 40 Appendix Annexe ...
Page 79: ...41 20010950 Appendix Annexe 0 1 1 1 ...
Page 80: ...20010950 42 Appendix Annexe 0 ...
Page 81: ...43 20010950 Appendix Annexe 0 0 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2 ...
Page 82: ...20010950 44 Appendix Annexe 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 85: ...47 20010950 Appendix Annexe ৼ 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3 ...