Installation
21
20095042
GB
RLS 200/E (Fig. 14)
In order to extract the internal combustion head, proceed as fol-
lows:
➤
remove screw 1)(Fig. 14);
➤
pull the internal part 2) until the gas distributor level (detail 3);
➤
turn anti-clockwise (about 90°) the internal part 4) and then
extract completely the internal combustion head.
4.8
Combustion head setting
The setting of the combustion head depends exclusively on the
maximum delivery of the burner.
Turn screw 6)(Fig. 15) until the notch shown in diagram (Fig. 16) is
level with the front surface of flange 5)(Fig. 15).
Example for RLS 200/E:
maximum burner delivery = 7250 MBtu/hr.
If diagram (Fig. 16) is consulted it is clear that for this delivery, the
combustion head must be adjusted using notch 6, as shown in
Fig. 15.
In case of high altitude site, head setting must refer to the “correct-
ed capacity” according procedure described at page 9.