Par
Variable name
Description
Value range
Default
Min
Max
133
SHW CARREXT
Defines if domestic hot water is managed by the system control or by an external
control.
1
3
3
1. Managed by system control
2. Managed by system control with Solar
3. Managed by external control
If domestic hot water tank is not installed set code to 3 and set code 106.0 = 0
134
SHW MAX HP T°
If domestic hot water temperature is equal to or higher than this value, domestic hot
water priority is 0
40 °C
80 °C
55 °C
135
SHW DELTA MED T°
If domestic hot water temperature is equal to code 134 - this code, domestic hot water
priority is 0.5
1 °C
15 °C
5 °C
136
SHW DELTA ALARM T°
If domestic hot water temperature is equal or lower to code 134 - code 135 - this code,
domestic hot water priority is 1
1 °C
15 °C
5 °C
137
ROOM DELTA MED T°
In heat mode: if room temperature is room setpoint - this code, room priority is 0.5
In cool mode: if room temperature is room se this code, room priority is 0.5
0,5 °C
5 °C
1 °C
138
ROOM DELTA MIN T°
In heat mode: if room temperature is room setpoint - code 137 - this code, room
priority is 1
In cool mode: if room temperature is room se code 137 + this code, room
priority is 1
0,5 °C
5 °C
1 °C
139
BOILER WAIT TIME
Time delay after which the boiler will be activated if domestic hot water priority does
not decrease due to heat pump operation.
0
180
15
If 0 is selected, boiler does not turn on to support the domestic hot water production.
140
LEGIONELLA FREQ
Define how often (days) the disinfection cycle starts.
0
7
0
If 0 is selected, Disinfection is not performed.
141
LEGIONELLA START TIME
Start time of the Disinfection cycle (hours)
0
24
3
142
LEGIONELLA TEMP
T° to be reached in the Disinfection cycle
60
90
75 °C
143
LEGIONELLA DURATION
Disinfection dwell time (minutes). T° has to be equal to or higer than code 142 for this
time period
5
180
30
144
LEGIONELLA TIME OVER
If Disinfection cycle is not completed within this time (hours), the antilegionalla cycle
is considered failed
2
12
4
The parameters displayed in grey are not available.