Par
Variable name
Description
Value range
Default
Min
Max
107
FLOW SWITCH
CONFIGURATION
Use
DAYS
button to select below mentioned functions
0
1
0. (used for service purposes only)
1
0: Open: flowing / Shut: not flowing
1: Shut: flowing / Open: not flowing
1.
0
0: Does not allow water flow when the unit pump is OFF (no external pump used)
1: Allows water flow when the unit pump is OFF (external pump used)
108
MASTER OUTPUT
CONFIGURATION
Use Up/Down buttons to select between 1 to 10:
1
16
4
1. Fan Coil: fan coils do not work when domestic hot water valve is activated
2. Fan Coil: fan coils are always working
3. Fan coils do not work when domestic hot water valve is activated, unless the mode
is Cool
4. Dehumidifier
5. All alarms
6. Alarms stop the outdoor unit
7. Alarms stop the entire system
9. Defrost
10. All defrost
11. Alarms stop the outdoor unit + defrost
12. Alarms stop the entire defrost
13. Not used
14. Not used
15. Not used
16. Not used
109
SLAVE OUTPUT
CONFIGURATION
Use
DAYS
button to select below mentioned functions
0
3
0
1
0. Three-way valve
1. Others
3
1
0. zone 1: Fan coils do not work when domestic hot water valve is activated
1. zone 1: Fan coils are always working
2. zone 1: Fan coils do not work when domestic hot water valve is activated, unless
the mode is Cool
3. zone 1: Dehumidifier
2
3
0. zone 2: Fan coils do not work when domestic hot water valve is activated
1. zone 2: Fan coils are always working
2. zone 2: Fan coils do not work when domestic hot water valve is activated, unless
the mode is Cool
3. zone 2: Dehumidifier
110
HUMIDITY LIMIT
This code defines the Humidity threshold limit to enable the output for the external
de-humidifier
20
100
100
111
ANTIFROST T°
This code defines the Temperature below which the water frost protection will be
activated
4 °C
10
4 °C
The parameters displayed in grey are not available.