P
RELIMINARY CONTENT CHECK
After opening the package, first check the content:
metal chutes, warranty card, user manual, safety manual, inspection certificate, serial connection cable, 4 x battery fuses (to be
inserted in the “SWBATT” fuse holders), door key.
P
OSITIONING THE
UPS
When positioning the equipment, the following points should be taken into account:
The wheels are intended for accurate positioning, therefore for small movements only.
The plastic parts and the door are not suitable for pushing or gripping the UPS.
Sufficient space should be left in front of the equipment, for it to be switched on and off and in order to allow carrying
out maintenance operations on it (
≥
1,5 metres).
The rear part of the UPS should be placed at least at 30 cm from the wall, to allow the air blown by the ventilation fans
to outflow correctly.
No objects should be placed on its upper surface.
Once the equipment has been positioned, secure it with the apposite brake rod (see
"Front views of the UPS "
).
In earthquake-prone zones or in mobile systems it is possible to use the brackets securing the UPS to the pallet to anchor the
machine to the ground (see figure below). In normal conditions the brackets are not necessary.
O
PERATIONS TO ACCESS THE TERMINALS OF THE
UPS
To carry out the following operations, the UPS must be disconnected from the mains power supply,
switched off, and with all the equipment switches and fuse holders open.
Follow the instructions provided below to open the UPS:
Open the door using, if necessary, the key provided
Remove the terminal cover in correspondence with the switches (see
"Front views of the UPS"
)
Once the installation operations inside the equipment have been completed, replace the terminal cover and close the door.