COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjust-
ment and testing must be carried out observing the instruction manual of the boiler, including verifica-
tion of the CO and CO

2

 concentration in the flue gases, their temperatures and the average

temperature of the water in the boiler.
To suit the required appliance output, fit the nozzle then adjust the pump pressure, the setting of the
combustion head and the air damper opening in accordance with the following schedule.

FUEL LIGHT OIL 

FUEL KEROSENE 

 

NOZZLES RECOMMENDED:

  Monarch  type R - PLP; Delavan  type B - W

Steinen  type S - SS ; Danfoss  type S - B

Angle 60°:

in most cases. 
Particularly suitable to avoid flame-detachment during ignition.

45°:

for narrow and long combustion-chamber.

 

PRESSURE:

8 bar: 

the pump leaves the factory set at this value, which is suitable only for kerosene.

10 bar: 

maximum pressure for kerosene.

FOR LIGHT OIL INCREASE PRESSURE

12 bar: 

in most cases.

14 bar: 

improves flame retention; it is therefore suitable for ignitions at low temperatures.

1

2

3

4

Nozzle

Pump pressure

Burner output

Comb. head 

adjustment

Air damper

adjustment

GPH

Angle

bar

kg/h ± 4%

Set-point

Set-point

2.00

60°

12

8.6

1

3

2.25

60°

12

9.7

1.5

3.2

2.50

60°

12

10.7

2

3.5

3.00

60°

12

12.9

2.5

4.3

3.50

60°

12

15.0

3.5

5.5

4.00

60° / 45°

12

17.2

5

6.5

4.00

60° / 45°

13

17.9

6

7

1

2

3

4

Nozzle

Pump pressure

Burner output

Comb. head 

adjustment

Air damper

adjustment

GPH

Angle

bar

kg/h ± 4%

Set-point

Set-point

2.75

60°

8

8.1

0.5

2.2

3.00

60°

8

8.9

1

2.4

3.50

60°

8

10.3

1.5

3.0

4.00

60°

8

11.8

2.5

3.2

4.50

60°

8

13.3

3

4.0

5.00

60°

8

14.8

3.5

6.0

5.50

60° / 45°

8

16.2

5

6.5

6.00

60° / 45°

8

17.7

6

7.0

1

2

Summary of Contents for G20KI

Page 1: ...Installation use and maintenance instructions 2902403 6 05 2011 Light oil kerosene burner One stage operation CODE MODEL TYPE 3747455 G20KI 474T52...

Page 2: ...y start up use and mainte nance of the burner DELIVERY OF THE SYSTEM AND THE INSTRUC TION MANUAL When the system is delivered it is important that The instruction manual is supplied to the user by the...

Page 3: ...0 kW 1 Return line 2 Suction line 3 Gauge connection 4 Pump pressure regulator 5 Vacuum gauge connection 6 Screws fixing air damper 7 Hydraulic jack with air damper 8 Lock out lamp and reset button 7...

Page 4: ...lating gasket Screws and nuts for flange Maintenance assembly Cable gland Screw with two nuts for flange Pressure in the combustion chamber mbar Fuel output kg h Thermal power kW D5683 0 0 4 8 10 12 1...

Page 5: ...g 5 Remove the burner out of the boiler after loosing the fixing nut to the flange Hook the burner to the flange 1 by removing the combustion head 6 after loosing the fixing screws 7 Remove the diffus...

Page 6: ...r the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before repeating the operation A metal bowl filter with replaceable micronic filter must be fitted in the...

Page 7: ...rds the arrow The photoresistance is fitted directly into the control box underneath the ignition trans former on a plug in support TESTING Check the shut down of the burner by opening the thermostats...

Page 8: ...nt during ignition 45 for narrow and long combustion chamber PRESSURE 8 bar the pump leaves the factory set at this value which is suitable only for kerosene 10 bar maximum pressure for kerosene FOR L...

Page 9: ...ustion head with the burner running operate on the rod 1 with a 6 mm spanner 2 as follows TURN TO THE RIGHT SIGN In order to increase the volume of air entering the combustion chamber and thus diminis...

Page 10: ...l these conditions may require a different air damper setting It is important to take account of the fact that the air output of the fan differs according to whether the burner has its metal cover fit...

Page 11: ...ne set point further ahead than indicated in the instructions Example the instructions require to set the combustion head on set point 2 5 Instead the setting is made on set point 3 5 5 FAN AIR DAMPER...

Page 12: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com...

Reviews: