34
COMMISSIONING AND MAINTENANCE
for first commissioning, do the following to activate the device:
—
follow the instructions given in the manual of the indoor
unit that you are installing
9
Keep the leak finder on and close to the unit so that it sig-
nals any refrigerant leak.
9
Use an electronic leak finder properly calibrated for the sys-
tem refrigerant.
0
It is forbidden to use leak finders with halogen lamps.
Checks during and after the first commissioning
After starting the device, check that:
—
the current consumed by the compressor is less than the
maximum permitted
—
the device is operating under the recommended operating
conditions
—
the unit is able to stop and start up again
9
Should any of the above-listed controls have problems: turn
the device off and call the Technical Service immediately.
9
Do not touch the device pipes to prevent potential burns.
9
Take anti-static precautions in case of weather conditions
where humidity is less than 40%.
9
Avoid using mobile phones.
Additional refrigerant charge
The units are supplied with a sufficient amount of refrigerant gas
for a pre-set length of the connection pipes.
An additional refrigerant charge is needed if such length is ex-
ceeded.
The pre-set values are detailed in the following table:
Model
250
P
355
P
370
P
475
P
485
P
Maximum length with
standard charge
20
30
30
40
40
m
Additional charge
20
20
20
20
20
g/m
9
The device must be earthed before performing the addi-
tional charge.
9
The R32 refrigerant gas is slightly inflammable and odour-
less. Carefully read the safety data sheet available from the
dealer and see table "Minimum floor area"
p. 9.
To perform the additional charge:
A
High pressure
B
Low pressure
1
Pressure gauge unit
2
Electronic scale
3
3-way valve service connection
A
B
1
R32
3
2
—
connect the refrigerant cylinder to the pressure gauge unit
—
connect the charging tube to the service connection on the
3-way shut-off valve
—
remove the air from the charging tube
—
charge the refrigerant with an electronic scale
—
disconnect the charging tube from the service valve
—
refit the three-way valve closing plug
9
Carefully check for absence of leakages from the closing
point of the plug.
9
Do not force beyond the stop point to prevent damaging the
shaft and causing leakage as a consequence.
9
Use equipment suitable for the system refrigerant.
9
Use only the system refrigerant.
9
Any gas leaks indoors can generate toxic gases if they come
into contact with naked flames or high temperature bodies,
in case of leaks, please air the rooms thoroughly.
9
Take anti-static precautions in case of weather conditions
where humidity is less than 40%.
9
Avoid using mobile phones.
3.2.1
Refrigerant label