COIL pressure drop (Riello 7000.1000/S -1500/S models only)
6 Technical specifications
7 Pressure drops
0
1
2
3
4
5
PERDIT
A
DI CARICO (mbar)
PORTATA (m
3
/h)
650
600
550
500
450
400
350
300
250
200
150
100
50
0
STOR 1000 M
STOR 1500 M
Riello 7000.1500/S
Riello 7000.1000/S
FLOW RATE (m3/h)
PRES
SURE DROP (mb
ar)
DESCRIPTION
Riello
7000.
1000/S
Riello
7000.
1500/S
Riello
7000.
2000/F
Riello
7000.
3000/F
Riello
7000.
5000/F
Storage tank type
non vitrified
Tank layout
Vertical
Heat exchanger layout
Vertical
Vertical
-
-
-
External diameter with insulation
990
1200
1300
1450
1800
mm
Height with insulation
2190
2165
2480
2720
2870
mm
Insulation thickness
100
mm
Flange diameter (external/internal)
-
-
290/220
290/220
290/220
mm
Probe well diameter
8
mm
Coil water capacity
14,6
21,6
-
-
-
l
Coil heat exchange surface area
2,6
3,8
-
-
-
m2
Power absorbed by coil (*)
68
99
-
-
-
kW
Heating hot water production (*)
1700
2400
-
-
-
l/h
Necessary capacity heat - exchanger (*)
2,9
4,2
-
-
-
m3/h
Maximum working pressure of storage tank
3
bar
Maximum working temperature of storage tank
99
°C
Maximum working pressure of coil
6
6
-
-
-
bar
Maximum working temperature of coil
99
°C
Net weight with insulation
225
285
345
415
570
kg
Useful volume
920
1410
2010
2959
5055
I
Dispersion
203
249
305
344
646
W
4,872
5,976
7,32
8,256
15,504
kWh/24h
Insulation type
Soft PU shells
(*) According to DIN 4708, to get domestic hot water with
Δ
T 20°C (80°/60°C) on the heat-exchanger, please observe the values showed in the datasheet