background image

16

3  GENERAL REQUIREMENTS (UK)

This appliance must be installed by a competent person in ac-

cordance with the Gas Safety (Installation & Use) Regulations.

3.1  RELATED DOCUMENTS

The installation of this boiler must be in accordance with the 

relevant requirements of the Gas Safety (Installation & Use) 

Regulations, the local building regulations, the current I.E.E. 

wiring regulations, the bylaws of the local water authority, the 

Building Standards (Scotland) Regulation and Building Stand-

ards (Northern Ireland) Regulations.

It should be in accordance also with any relevant requirements 

of the local authority and the relevant recommendations of the 

following British Standard Codes of Practice.

ATTENTION

The use of PPE (Personal Protective Equipment) such as but 

not limited to gloves, mask, safety glasses, etc. is strongly 

recommended whenever carrying out the installation, repair, 

or maintenance of this appliance – please pay particular at-

tention to:

•  Sharp edges that may be encountered when:- handling or 

lifting the appliance, removing parts, etc. during installation 

and maintenance

•  Airborne particles that may be released and/or disturbed 

when cleaning or removing components during 

maintenance

•  Water treatment chemicals that could have been added to 

the system water may spill from the appliance and or com-

ponents during maintenance

Please refer to an appropriate Health and Safety document 

such as HSE L23 (UK) or S.I. 299 (Ireland), for more detailed 

advice on safe working practices and procedures. 

If the gas supply serves more than one appliance, it must be 

ensured that an adequate supply is maintained to each appli-

ance when they are in use at the same time.

NOTE

It is recognised that ‘pressure loss’ through the gas cock and 

gas valve may result in a pressure drop of approximately 2mbar 

between the gas meter and gas valve inlet test point; this will 

not impair the performance of the appliance, provided that a 

dynamic pressure of 18mbar is available at the appliance inlet.

3.4  FLUE SYSTEM

The terminal should be located where the dispersal of combustion 

products is not impeded and with due regard for the damage 

and discoloration that may occur to building products located 

nearby. The terminal must not be located in a place where it 

is likely to cause a nuisance (see Fig. 9). In cold and/or humid 

weather, water vapour will condense on leaving the terminal; 

the effect of such pluming must be considered.

If installed less than 2m above a pavement or platform to 

which people have access (including balconies or flat roofs) 

the terminal must be protected by a guard of durable material.  

The guard must be fitted centrally over the terminal. Refer to 

BS 5440 Part 1, when the terminal is 0.5 metres (or less) below 

plastic guttering or 1 metre (or less) below painted eaves.

3.5  AIR SUPPLY

The following notes are intended for general guidance only. 

This appliance is a room-sealed, fan-flued boiler, consequently 

it does not require a permanent air vent for combustion air sup-

ply. When installed in a cupboard or compartment, ventilation 

for cooling purposes is also not required.

3.6  WATER CIRCULATION

Detailed recommendations are given in BS 5449 Part 1 and 

BS 6798. The following notes are for general guidance only.

3.6.1  PIPEWORK

It is recommended that copper tubing to BS 2871 Part 1 is used 

in conjunction with soldered capillary joints. Where possible 

pipes should have a gradient to ensure air is carried naturally to 

air release points and that water flows naturally to drain cocks. 

Except where providing useful heat, pipes should be insulated 

to avoid heat loss and in particular to avoid the possibility of 

freezing. Particular attention should be paid to pipes passing 

through ventilated areas such as under floors, loft space and 

void areas.

3.6.2  AUTOMATIC BY-PASS

The appliance has a built-in automatic by-pass, consequently 

there is no requirement for an external by-pass, however the 

design of the system should be such that it prevents boiler 

‘cycling’.

3.6.3   DRAIN COCKS

These must be located in accessible positions to facilitate 

draining of the appliance and all water pipes connected to the 

appliance. The drain cocks must be manufactured in accord-

ance with BS 2879.

3.6.4  AIR RELEASE POINTS

These must be positioned at the highest points in the system 

where air is likely to be trapped. They should be used to expel 

trapped air and allow complete filling of the system.

3.2  LOCATION OF APPLIANCE

The appliance may be installed in any room or internal space, 

although particular attention is drawn to the requirements 

of the current I.E.E. wiring regulations, and in Scotland, the 

electrical provisions of the Building Regulations, with respect 

to the installation of the appliance in a room or internal space 

containing a bath or shower.

When an appliance is installed in a room or internal space 

containing a bath or shower, the appliance or any control per-

taining to it must not be within reach of a person using the bath 

or shower. The location chosen for the appliance must permit 

the provision of a safe and satisfactory flue and termination. 

The location must also permit an adequate air supply for com-

bustion purposes and an adequate space for servicing and air 

circulation around the appliance. Where the installation of the 

appliance will be in an unusual location special procedures may 

be necessary, BS 6798 gives detailed guidance on this aspect. 

A compartment used to enclose the appliance must be designed 

and constructed specifically for this purpose. An existing com

-

partment/cupboard may be utilised provided that it is modified 

to suit. Details of essential features of compartment/cupboard 

design including airing cupboard installations are given in BS 

6798. This appliance is not suitable for external installation.

3.3  GAS SUPPLY

The gas meter – as supplied by the gas supplier – must be 

checked to ensure that it is of adequate size to deal with the 

maximum rated input of all the appliances that it serves. Instal-

lation pipes must be fitted in accordance with BS 6891.

Pipe work from the meter to the appliance must be of adequate 

size. Pipes of a smaller size than the appliance gas inlet con-

nection must not be used. The installation must be tested for 

tightness in accordance with BS6891.

BS 5440

PART 1

FLUES

BS 5440

PART 2

FLUES & VENTILATION

BS 5449

PART 1

FORCED CIRCULATION HOT WATER SYSTEMS

BS 5546

INSTALLATION OF GAS HOT WATER SUPPLIES FOR  DOMESTIC PURPOSES

BS 6798

INSTALLATION OF BOILERS OF RATED INPUT NOT  EXCEEDING 60kW

BS 6891

LOW PRESSURE INSTALLATION PIPES

BS 7074

PART 1

APPLICATION, SELECTION, AND INSTALLTION OF EXPANSION VESSELS AND 

ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS

Summary of Contents for 47-364-52

Page 1: ...AINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK VISION PLUS High efficie...

Page 2: ...22 5 OPERATION 23 5 1 ACCESS TO THE PARAMETERS 23 5 2 CONTROL PANEL 23 5 3 SETTINGS MENU TREE STRUCTURE 24 5 4 STARTING THE BOILER 25 5 5 BOILER CONFIGURATION 26 5 6 FIRST COMMISSIONING 28 5 7 VENT CY...

Page 3: ...inated automatically 1 6a DIMENSIONS VISION PLUS 25C 30C HEIGHT 715 mm WIDTH 405 mm DEPTH 248mm Dear Customer Your Vok ra VISION PLUS boiler has been designed to meet and exceed the very latest standa...

Page 4: ...indicator Indicates the presence of a flame in the event of a flame lockout the icon looks like Reset It comes on when there are alarms that require a manual reset by the user Enter It comes on when...

Page 5: ...ns and the segments come on for 1sec and in sequence the firmware revision is displayed for 3sec Then the interface displays the status active at that moment If necessary the interface automatically g...

Page 6: ...and the burner is lit the icon appears on the display Heating REQUEST the radiator icon blinks Bar 2 3 2a SUMMER MODE Set the boiler to the SUMMER status by pressing key 1 until the domestic hot water...

Page 7: ...On the 4 digits a message scrolls containing the error code and its description DAY 2 3 8a RESET FUNCTION The RESET icon comes on when there is an alarm that requires a manual reset by the user for e...

Page 8: ...ngineer 2 6a INFO MENU Pressing key 3 on the display screen displays a list of informa tion regarding the operation of the boiler listed by parameter name and value Passing from the display of one par...

Page 9: ...DOWN THE SYSTEM FOR SHORT PERIODS The system and boiler can be shut down in the event of temporary absences weekends short breaks etc setting the boiler status to OFF 3a HOW TO While the electrical s...

Page 10: ...secontactyournearestVok raoffice 4 2a WHAT IF I HAVE FREQUENTLY TO TOP UP THE SYSTEM If the system regularly requires topping up it may be indicative of a leak Please contact your installer and ask hi...

Page 11: ...mer services VISION PLUS boiler complies with basic requirements of the following Directives Regulation EU 2016 426 Yield directive Article 7 2 and Annex III of directive 92 42 EEC Electromagnetic com...

Page 12: ...r DHW flow switch Top AAV High limit thermostat Flow temperature sensor Safety valve DHWFilter Automatic by pass Return temperature sensor Water trans ducer Fig 5 2 DESIGN PRINCIPLES AND OPERATING SEQ...

Page 13: ...25C VISION PLUS 30C Capacity 8 litres Maximum system volume 74 litres Pre charge pressure 1 bar Dimensions VISION PLUS 25C VISION PLUS 30C Height mm 715 Width mm 405 Depth mm 248 Dry weight kg 27 29 C...

Page 14: ...ed 24 kW Seasonal space heating energy efficiency s 93 For boiler space heaters and boiler combination heaters useful heat output For boiler space heaters and boiler combination heaters useful efficie...

Page 15: ...of 600 mm T Below an opening or window on a pitched roof 2000 mm V From a vertical terminal to an adjacent opening window air brick etc call Vokera technical for advice W From a vertical terminal to a...

Page 16: ...PIPEWORK It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capillary joints Where possible pipes should have a gradient to ensure air is carried naturally to...

Page 17: ...ed socket with a fused 3 pin plug both complying with BS 1363 is acceptable NOTE Note Vokera Ltd cannot guarantee the performance or reliability of the appliance if when it is supplied via an invertor...

Page 18: ...4E AIR RELEASE POINTS These must be positioned at the highest points in the system where air is likely to be trapped They should be used to expel trapped air and allow complete filling of the system...

Page 19: ...20132062 2000mm extension 2000mm 20131979 telescopic extension 372 519mm 522 plume management kit 1370mm 20135587 100mm flue brackets 5 N A Fig 12 Using the template A provided with the kit mark and d...

Page 20: ...ONLY Using the template provided mark and drill a 125mm hole for the passage of the flue pipe The hole should be drilled LEVEL to ensure any condense fluid that forms is allowed to drain back to the a...

Page 21: ...are located in the groove of the vertical flue connector Both screws C should now be tightened NOTE If more convenient the vertical flue connector can be attachedtotheverticalflueterminal extensionbe...

Page 22: ...trical supply Connect the fly lead to a fused plug or fused isolator in the following way brown wire to LIVE supply blue wire to NEUTRAL supply green yellow to EARTH connection Insertthesupplied3 AMPf...

Page 23: ...d it has the back cancel function A B Access to the domestic hot water comfort functions see para graph 5 8 9 Domestic hot water comfort function C It is normally used to raise the heating water tempe...

Page 24: ...P4 05 PUMP CONTROL TYPE NOT USED P4 08 OT CASCADE CONTROL NOT AVAILABLE ON THIS MODEL P4 09 SCREED FUNCTION 0 1 INSTALLER 0 P4 10 ANTI CYCLE FUNCTION 0 20min INSTALLER 3min P4 11 RESET CH TIMERS 0 1 I...

Page 25: ...ITY P8 01 BUS 485 CONFIG 0 1 2 SERVICE 0 P8 03 OT CONFIG 0 1 SERVICE 1 5 4 STARTING THE BOILER Ensure that steps 6 1 through to 6 6 have been completed be fore supplying the gas and electrical supply...

Page 26: ...oard for calculating the ignition delivery temperature of the burner IGNITION TEMPERATURE HEATING SETPOINT P4 04 The factory setting for this parameter is 3 C it can be changed within the 2 10 C range...

Page 27: ...eet of the BE16 accessory board for more information about the use of this parameter P4 25 When P4 12 1 this parameter allows you to set the hydraulic configuration of heating zone 1 The factory setti...

Page 28: ...ntil the icon for the desired function is displayed 5 8 1 WINTER MODE Set the boiler to the WINTER status by pressing key 1 until both the domestic hot water icon and the heating icon are displayed Th...

Page 29: ...in the preset range in steps of 0 5 C The level bars beside the heating icon show the setpoint value set with respect to the operating range four bars on max setpoint one bar on min setpoint 5 8 7 SAF...

Page 30: ...t the P4 menu and then P4 09 with the keys confirming the selection with Note SCREED HEATING is not available if the boiler is a status other than OFF To activate the function set the parameter to 1 t...

Page 31: ...e Drain the boiler and system from the lowest points Open the drain valve full bore to remove any installation debris from the boiler prior to lighting Refill the boiler and heating system as describe...

Page 32: ...mperature can be adjusted between 37 C 60 C via the buttons A B Fig 1 6 11 SETTING THE SYSTEM DESIGN PRESSURE The design pressure should be a minimum of 0 5 bar and a maximum of 1 5 bar The actual rea...

Page 33: ...m pump base and lift pump assembly clear of the hydraulic manifold The pump assembly can now be removed from the appliance Replace carefully in the reverse order 7 7 SAFETY VALVE FIG 32 Carry out comp...

Page 34: ...front cover Disconnect the electrode leads and ancillary wiring from their respective connectors Re move the retaining screws V for electrode Remove the spark ignition electrode W Remove the flame sen...

Page 35: ...fully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 Ensure all seals are in good condition taking care to ensure they are replaced correctly Replace in the reverse order ensurin...

Page 36: ...component removal procedure as described in 7 4 Disconnect the electrical plug from the actuator H2 Replace in the reverse order 7 21 4 DHW THERMISTOR FIG 33 Carry out component removal procedure as d...

Page 37: ...er Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15 minutes The speed of the fan and therefore the output of the boiler is determined...

Page 38: ...own on the display IMPORTANT The combustion analysis function is active for a maximum time of 15 minutes the burner shuts down if an outlet temperature of 95 C is reached It will ignite again when the...

Page 39: ...isconnection and re connection of any electrical wiring or component these checks must be repeated 8 7 FAULT FINDING Before attempting any fault finding the electrical checks as detailed in 8 6 must b...

Page 40: ...14 15 16 17 18 19 20 21 22 23 24 25 26 Giri ven latore r p m Portata termica kW Curva portata termica giri ven latore Caldaia Vision PLUS 25C Qm Qn RANGE RATED HTG curve VISION PLUS 25C heat output kW...

Page 41: ...0 15 20 CORREZIONE CURVA CLIMATICA CLIMATE CURVE CORRECTION EXTERNAL TEMPERATURE C DELIVERY TEMPERATURE C NIGHT COMPENSATION PARAMETER P4 20 If a ROOM THERMOSTAT is connected to a programming timer fr...

Page 42: ...his latter is replaced The total hours can be verified in the following way access the INFO menus as indicated in the paragraph 8 15 INFO menu at I0 15 to display the value of the flue gases probe met...

Page 43: ...n P4 12 1 I0 14 ZONE 1 OUTLET Zone 1 ow sensor value when P4 13 1 I0 15 EXHAUST PROBE HOURS Number of hours the heat exchanger has been operating in condensing mode I0 16 MAIN ZONE SET Main zone deliv...

Page 44: ...following figure Using the arrows select the day or the pre selected group of days 1 2 3 4 5 6 7 programming of the individual days 1 5 programming from Monday to Friday 6 7 programming from Saturday...

Page 45: ...er must always be supplied with a permanent 230V electrical supply The room thermostat connection is low voltage 24 Vdc Do not connect any controls or auxiliary equipment to the low voltage terminal s...

Page 46: ...brown blue CN3 1 2 NOTE L N E connection is advisable 7 1 CN9 D H W T D H W F S red red violet violet t 3 CN4 1 brown heat black D H W blue Heat 3 D H W 1 N 2 3W TSC2 S E N F 3 yellow green blue brown...

Page 47: ...he boiler to propane gas G31 use the specific accessory kits For disassembly refer to the instructions below remove the power supply to the boiler and close the gas tap remove the casing as indicated...

Page 48: ...section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES I Is s C CO O 3 35 50 0p pp pm m a an nd d C CO O C CO O2 2 r ra at ti...

Page 49: ...urers recommendations at least annually This must be carried out by a competent Gas Safe registered engineer The service details should be recorded on the Benchmark Service and Interim Boiler Work Rec...

Page 50: ...no what is the maximum central heating output selected kW Dynamic gas inlet pressure mbar C Central heating return temperature C System correctly balanced rebalanced Yes COMBINATION BOILERS ONLY Is th...

Page 51: ...er name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas r...

Page 52: ...er name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas r...

Page 53: ...structions must be provided e g Benchmark Service Record If this condition is not met the period of warranty will extend to only 12 months from date of installation By registering your appliance you w...

Page 54: ...from a Trading Standards Authority or a Citizen Advice Bureaux Your Personal Details Vok ra takes care of your personal details in order to protect your privacy Below we detail how we use any data you...

Page 55: ...Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the right to change specification without prior notice Consumers statutory rights are not affected Company Reg...

Reviews: