3312
12
GB
CONTINUOUS PURGING FUNCTION,
(only for applications in which this is provided for)
Continuous purging is an operation that maintains the air purging regardless of whether there is a request for
the burner to turn on or not. From the moment it is set, the motor keeps running whether the limit thermostat
(
TL
) has not been switched (burner off), or when the burner is blocked.
When the limit thermostat (
TL
) is switched the motor is stopped for the standby time of four seconds (standby
position = t2 + t1), the subsequent check of the air pressure switch and beginning of a new burner operation cy-
cle.
The function can be set from the reset button when the limit thermostat (
TL
) is not switched (burner off), by
following the procedure in the post-purging function paragraph pressing the button
7 times = continuous
purging
.
To reset
this function, press and hold the button for at least 5 seconds at least, till the LED indicator changes to
red then release it without carrying out any operation, then wait for 20 seconds for the burner to start again.
The control box's factory settings are as follows:
0 minutes = no continuous post-purging
.
FUNCTION SETTING PROCEDURE USING RESET BUTTON
MAINTENANCE
Before cleaning or performing checks, switch off the burner’s power supply with the system’s master
switch and close the gas shutoff valve.
The burner requires periodic maintenance carried out by a qualified and authorised technician in conformity
with legislation and local standards.
Periodic maintenance is essential for the reliability of the burner, avoiding the excessive consumption of fuel
and consequent pollution.
THE BASIC OPERATIONS ARE:
Checking that there are no obstructions or kinks in the supply or return oil pipes, in the air intake regions
and the combustion product discharge tubes.
Checking that the burner and gas train electrical connections are correct.
Checking that the gas train is suitable for the burner's power, the type of gas used and the mains gas
pressure.
Checking the proper positioning of the combustion head and its fixing to the boiler.
Checking the proper positioning of the air damper and the air damper opening motor.
Checking the proper positioning of the ionisation probe and electrode.
Checking the adjustment of the air pressure switch and the gas pressure switch.
Leave the burner working without interruption for 10 min., checking the right settings at 1
st
and 2
nd
stage of
all the components stated in this manual.
Then carry out the analysis of the scale combustion by checking:
Percentage of CO
2
(%);
CO Content (ppm);
NOx content (ppm);
Ionisation current (µA);
Flue gases temperature at the flue.
Control box function
Action with the reset button
Possible
Reset button use
status
Reset
1 - 2 seconds
After control box lockout
Visual diagnostic of the causes of the
block
3 seconds
After control box lockout
Post-purging
5 seconds then press
once = 1 minute
W i t h l i m i t t h e r m o s t a t (
T L
) n o t
switched (burner off)
Continuous purging (only for applica-
tions provided for)
5 seconds then press
7 times = continuous purging
W i t h l i m i t t h e r m o s t a t (
T L
) n o t
switched (burner off)
Resetting
set functions
5 seconds
W i t h l i m i t t h e r m o s t a t (
T L
) n o t
switched (burner off)
Resetting operating parameters
5 seconds
With limit thermostat (
TL
) switched
during pre-purging