background image

3312

14

GB

FAULTS / SOLUTIONS

Here below you can find some causes and the possible solutions for some problems that could cause a fail-
ure to start or a bad working of the burner. A fault usually makes the lock-out lamp light which is situated
inside the reset button of the control box (11, fig. 1, page 1). When lock-out lamp lights the burner will attempt
to light only after pushing the reset button. After this if the burner functions correctly, the lock-out can be
attributed to a temporary fault. However, if lockout continues, you must determine the cause of the problem
and take the action illustrated in the tables below .

START-UP PROBLEMS

FAULTS

POSSIBLE CAUSES

SOLUTION

The burner does not
start when the limit
thermostat closes.

Lack of electrical supply.

Check for voltage at L1-N terminals in
7-pin plug.

Check the conditions of the fuses.

Check that safety thermostat is not
lock out.

Gas is not supplied.

Check gate opening.

Make sure that valves have changed
over to open position and that there
are no short circuits.

The gas pressure switch does not
close the contact.

Adjust it.

The connections in the control box
are wrongly inserted.

Check and connect completely all the
plugs.

The air pressure switch has
changed over to the operational po-
sition.

Replace the pressure switch.

Burner runs normally
in the pre-purge and
ignition cycle and
locks out after
3 seconds ca.

The phase-neutral connection is in-
verted

Swap them over.

The wiring to the earth is lacking or
ineffective.

Make earth connection efficient.

Ionisation probe has a ground fault or
is not in contact with flame, or there is
a break in its wiring to control box, or
there is a ground fault due to its insu-
lation being defective.

Check right position and, if necessary,
adjust as indicated in the manual.

Restore electrical connection.

Replace faulty lead.

Burner starts with an
ignition delay.

Ignition electrode is wrongly posi-
tioned.

Adjust them according to the instruc-
tions in the manual.

Air output is too high.

Set the air output according to the 
instructions of this manual.

Valve brake not open enough with
insufficient gas allowed through.

Set correctly.

The burner does not
switch into the
2

nd

stage.

The air damper open is jammed.

Check that it is working properly.

Check the precise electrical connection.

The 2

nd

 stage gas valve does not en-

ergise.

Valve broken: replace it.

Check the air damper opener works 
properly.

Summary of Contents for 3758704

Page 1: ...so y mantenimiento Installation use and maintenance instructions Forced draught gas burner Quemador de gas de aire soplado CODE C DIGO MODEL MODELO TYPE TIPO 3758704 FS5D 587M 3758705 FS5D 587M GB E T...

Page 2: ......

Page 3: ...ixing screws of the cover If necessary replace them with the fixing screws 7 fig 1 supplied as equipment TYPE 587M Thermal power 12 23 58 kW 10 000 20 000 50 000 kcal h Natural gas Family 2 Pci 8 12 k...

Page 4: ...parately to the appropriate socket on the control box The information is read after the software program in the kit is booted RESET KIT The use of a connection available as an accessory is provided fo...

Page 5: ...given in EN 676 please consult the manufacturers INSTALLATION S7392 HINGE A O Separate the combustion head assembly from the burner body by removing nut 1 and removing group A O Fix the head assembly...

Page 6: ...ure mbar 4 1 2 3 5 6 10 000 20 000 30 000 40 000 50 000 kcal h 10 30 20 40 50 kW Output D5058 60 0 GAS TRAIN ACCORDING TO EN 676 MULTIBLOC CONNECTIONS USE TRAIN BURNER MBZRDLE 405 B01 Rp 1 2 Rp 1 2 Na...

Page 7: ...o it the 7 pin plug and the earth wire TB undo the screw A and pull out the control box in the direction of the arrow For the installation of the control box it is neces sary to tighten up the screw A...

Page 8: ...e used only for initial settings to improve air pressure switch operation or improve combustion it may be necessary to reduce this setting set point toward position 0 230V 50Hz KEY TO LAY OUT B5 2nd s...

Page 9: ...on the fixed damper 3 after loosening the screws 4 Once the ideal setting has been reached securely tighten the screws 4 The damper leaves the factory set at pos 6 Take the burner to 1st stage workin...

Page 10: ...stments have been made Begin with the switch at the lowest setting With the burner function at the required power turn the knob slowly in a clockwise direction until burner lockout Then turn the knob...

Page 11: ...air pressure switch has already been moved to the work position before the required heat the control box remains in standby status a lockout fol lows if the air pressure switch remains switched for t...

Page 12: ...f 3 repetitions within one second Air pressure switch broken before or after the burner starts up Within 120 seconds within 15 seconds ts TL M I V1 SO LED P M t4i t2 t1 t3 V2 t2 ts TL M I P M t1 t3 LE...

Page 13: ...nnect the diagnostic software kit as described on page 2 ADDITIONAL PROGRAMMABLE CONTROL BOX FUNCTIONS POST PURGING FUNCTION t6 Post purging is a function that keeps air purging on even after the burn...

Page 14: ...of the burner avoiding the excessive consumption of fuel and consequent pollution THE BASIC OPERATIONS ARE Checking that there are no obstructions or kinks in the supply or return oil pipes in the ai...

Page 15: ...button SIGNAL PROBABLE CAUSE 2 pulses The flame does not stabilise at the end of the safety time faulty ionisation probe faulty gas valve neutral phase inverted faulty ignition transformer poor burner...

Page 16: ...ctions in the control box are wrongly inserted Check and connect completely all the plugs The air pressure switch has changed over to the operational po sition Replace the pressure switch Burner runs...

Page 17: ...ocking out The gas pressure in the mains is very near the value the gas pres sure switch is adjusted to Conse quently the sudden falling off in pressure at the opening of the valve causes the pressure...

Page 18: ...heat dissipation grilles or the ventilation openings in rooms where the control box is installed be plugged with rags paper or anything else No attempt must be made to repair the control box by non a...

Page 19: ...era necesario sustit yalos con aquellos entregados con la m quina 7 fig 1 TIPO 587M Potencia t rmica 12 23 58 kW 10 000 20 000 50 000 kcal h Gas natural Familia 2 Pci 8 12 kWh m3 7 000 10 340 kcal m3...

Page 20: ...rol el kit suministrado por separado La lectura de los datos se produce despu s de iniciar el programa de software incluido en el kit KIT DESBLOQUEO Est prevista la utilizaci n de una conexi n disponi...

Page 21: ...s m s peque as que aquellas indicadas en la norma EN 676 consulte al fabricante MONTAJE S7392 BISAGRA A O Separe el cabezal de combusti n del resto del quemador quitando la tuerca 1 y extraiga el grup...

Page 22: ...ompa an Presi n gas mbar 4 1 2 3 5 6 10 000 20 000 30 000 40 000 50 000 kcal h 10 30 20 40 50 kW Rendimiento D5058 60 0 RAMPA DE GAS SEG N EN 676 MULTIBLOC UNIONES EMPLEO RAMPA QUEMADOR MBZRDLE 405 B0...

Page 23: ...y el cable a tierra TB desenroscar el tornillo A y tirar de la caja de control en el sentido de la flecha Para instalar la caja de control es necesario enroscar el tornillo A con un par de torsi n de...

Page 24: ...mplear para una primera regulaci n Para garantizar un funcionamiento correcto del pres stato de aire podr a ser necesario disminuir la abertura del cabezal de combus ti n marca hacia la pos 0 230V 50H...

Page 25: ...dal de aire de la 2a llama con el registro fijo 3 tras haber aflojado los tornillos 4 Una vez alcanzada la regulaci n ideal enrosque com pletamente los tornillos 4 El registro sale de f brica regulado...

Page 26: ...e regulado a inicio escala Con el quemador fun cionando a la potencia requerida girar el bot n esf rico en el sentido de las agujas del reloj hasta el bloqueo del quemador Girara despu s el bot n esf...

Page 27: ...onmutado en posici n de trabajo antes de la solicitud de calor la caja de control permanece en estado de espera se produce un bloqueo si el pres stato aire sigue conmu tado durante T2a t4i Tiempo de e...

Page 28: ...iones antes de 1 segundo Pres stato de aire averiado antes o despu s de encender el quemador Antes de 120 segundos antes de 15 segundos ts TL M I V1 SO LED P M t4i t2 t1 t3 V2 t2 ts TL M I P M t1 t3 L...

Page 29: ...E LA CAJA DE CONTROL FUNCI N DE POSTVENTILACI N t6 La postventilaci n es una funci n que mantiene la ventilaci n del aire incluso despu s de apagado el quema dor El apagado del quemador se produce con...

Page 30: ...o la emisi n de agentes contaminantes LAS OPERACIONES B SICAS QUE SE DEBEN REALIZAR SON LAS SIGUIENTES Controlar que no existan oclusiones ni estrangulamientos en los tubos de alimentaci n y de retorn...

Page 31: ...ROBABLE 2 destellos No se detecta ninguna se al estable de llama en el tiempo de seguridad aver a en la sonda de ionizaci n aver a en la v lvula del gas inversi n fase neutro aver a en el transformado...

Page 32: ...cto Proceder a su regulaci n Las conexiones de la caja de con trol electr nica no est n correcta mente introducidas Compruebe y conecte a fondo todas las tomas El pres stato de aire est en posi ci n d...

Page 33: ...tinuamente sin que in tervenga el bloqueo La presi n del gas en la red est demasiado pr xima al valor con el cual est regulado el pres stato gas La ca da de presi n repentina al abrirse la v lvula pro...

Page 34: ...eles u otros objetos las rejillas de aspiraci n o de di sipaci n as como la abertura de ventilaci n del local en donde est instalada la caja de control Est prohibido cualquier intento de reparaci n de...

Page 35: ......

Page 36: ...RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com Subject to modifications Con la posibilidad de modificaci nes 3312...

Reviews: