Technical specifications
Performance combined with AMW P
Model
AMW 70 P
Cooling performance [A35 / A27]
(1)
Capacity at rated air flow
kW
7,00
Absorbed power at rated air flow
kW
2,17
EER
kW/kW
3,23
Capacity at maximum air flow
kW
7,50
Absorbed power at maximum air flow
kW
2,50
Capacity at minimum air flow
kW
2,20
Absorbed power at minimum air flow
kW
0,70
Cooling energy data
(2)
SEER
kW/kW
7,10
Energy class
A++
Annual energy cons.
kWh/annum
345
Heating performance [A7 / A20]
(3)
Capacity at rated air flow
kW
8,00
Absorbed power at rated air flow
kW
2,16
COP
kW/kW
3,71
Capacity at maximum air flow
kW
8,50
Absorbed power at maximum air flow
kW
2,90
Capacity at minimum air flow
kW
0,70
Absorbed power at minimum air flow
kW
2,40
Enery data for Average climatic profile
(4)
Pdesign at -10 °C
kW
5,60
SCOP
kW/kW
4,00
Energy class
A+
Annual energy cons.
kWh/annum
1959
Energy data for Warm climatic profile
(4)
Pdesign at +2 °C
kW
5,20
SCOP
kW/kW
5,40
Energy class
A+++
Annual energy cons.
kWh/annum
1357
(1)
Outdoor air: 35 °C D.b., Indoor air: 27 °C D.b. / 19 ° W.b.
(2)
In compliance with 626/2011 regulation
(3)
Outdoor air: 7 °C D.b. / 6 °C W.b., Indoor air: 20 °C D.b.
(4)
In compliance with EU 206/2012 regulation