6
TECHNICAL DATA
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m s.l.m.
(2) Pressure at test point 16)(A)p.8, with zero pressure in the combustion chambre, with open gas ring 2)(B)p.12 an maximum burner output
(2) Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
ACCESSORIES
(optional):
•
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valve, pressure governor and filter):
see page 18.
MODEL
RS 55 BLU
RS 65 BLU
RS 85 BLU
TYP
832 T1
833 T1
834 T1
OUTPUT
(1)
2nd stage
kW
407 - 640
350 - 550
616 - 814
530 - 700
790 - 1000
680 - 860
Mcal/h
min. 1st stage
kW
204
176
308
265
400
344
Mcal/h
FUEL
NATURAL GAS: G20 - G21 - G22 - G23 - G25
G20
G25
G20
G25
G20
G25
- net calorific value
kWh/Nm
3
Mcal/Nm
3
10
8.6
8.6
7.4
10
8.6
8.6
7.4
10
8.6
8.6
7.4
- absolute density
kg/Nm
3
0.71
0.78
0.71
0.78
0.71
0.78
- max. delivery
Nm
3
/h
64
74.5
81.4
94.5
100
116
- pressure at max. delivery
mbar
7.1
9.2
11
14.3
12.6
16.4
OPERATION
• On-Off (1 stop min each 24 hours).
• Two-stage (high and low flame) and single stage (all - nothing)
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATUR
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
Hz
230 - 400 with neutral +/-10%
50 - three-phaes ~
ELECTRIC MOTOR
rpm
W
V
A
2800
1100
220/240 - 380/415
4.8 - 2.8
2800
1500
220/240 - 380/415
5.9 - 3.4
2800
2200
220/240 - 380/415
8.8 - 5.1
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
ELECTRICAL POWER CONSUMPTION
W max
1400
1800
2600
ELECTRICAL PROTECTION
IP 44
IN CONFORMITY WITH EEC DIRECTIVES
90/396 - 89/336 - 73/23 - 98/37
NOISE LEVELS
(2)
dBA
75
77
78.5
APPROVAL
CE
0085AS0431
0085AS0431
0085AS0431
COUNTRY
CATEGORY
SE - FI - AT - GR - DK -ES - GB - IT - IE - PT - IS - CH - NO
DE
NL
FR
BE
LU
I
2H
I
2ELL
I
2L
I
2Er
I
2E(R)B
I
2E
Important:
The installer is responsible for the addition of any safety device not forseen in the present manual.
GB
Summary of Contents for RS BLU Series