6
TECHNICAL DATA
(1)
Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2)
Sound pressure measured in manufacturer»s combustion laboratory, with burner operating on test boiler and at maximum rated output.
ACCESSORIES
(optional):
• OUTPUT MODULATION REGULATOR KIT
Two components should be ordered:
•
output regulator to install on the burner;
•
probe to install on the boiler.
• DEGASSING UNIT
It may occur that a certain amount of air is contained in the light oil sucked up by the pump. This air may originate from the light oil itself as a
consequence of depressurization or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return pipe; in single-pipe systems, the air remains in circulation causing pressure variations
in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner in single-pipe installations.
Degassing units are provided in two versions:
CODE
3010054
without filter
CODE
3010055
with filter
- Burner delivery
: max. 80 kg/h
- Light oil pressure
: max. 0.7 bar
- Ambient temperature
: max. 50 °C (without filter)
- Ambient temperature
: max. 40 °C (with filter)
- Light oil temperature
: max. 50 °C (without filter)
- Light oil temperature
: max. 40 °C (with filter)
- Attachment connectors
: 1/4 inch
For burner deliveries higher than 80 kg/h, install two parallel degassing units
MODEL
RL 42/M BLU
RL 85/M BLU
TYPE
950 T1
952 T1
OUTPUT
(1)
MAX.
kW
360 - 480
310 - 412
30,4 - 40,4
355 - 1000
306 - 862
30 - 85
Mcal/h
kg/h
MIN.
kW
200 - 360
172,4 - 310
14,9 - 30,4
178 - 355
154 - 306
15 - 30
Mcal/h
kg/h
FUEL
LIGHT OIL
- net calorific value
kWh/kg
Mcal/kg
11.86
10.2 (10.200 kcal/kg)
- density
kg/dm
3
0.82 - 0.85
- viscosity at 20 °C
mm
2
/s
max 6 (1,5 °E - 6 cSt)
OPERATION
• On-Off (min 1 stop each 24 hours). These burners are also fiitted for the
continuous operation, if they are equipped with the control box LANDIS
type LOK 16.250 A27 (interchangeable with the burner control box LAN-
DIS LAL 1.25).
• Progressive two-stage (modulating by Kit)
NOZZLE
number
1 (nozzle with return)
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATURE
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
Hz
230 - 400 with neutral +/-10%
50 - three-phase ~
ELECTRIC MOTOR
rpm
W
V
A
2800
1100
220/240 - 380/415
4.8 - 2.8
2800
2200
220/240 - 380/415
8,5 - 4,9
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 2 x 5 kV
1,9 A - 30 mA
PUMP
delivery (at 20 bar)
pressure range
fuel temperature
kg/h
bar
° C max
163
10 - 21
90
ELECTRICAL POWER CONSUMPTION
W max
1400
2600
ELECTRICAL PROTECTION
IP 44
IN CONFORMITY WITH EEC DIRECTIVES
89/336 - 73/23 - 98/37
NOISE LEVELS
(2)
dBA
75
78.5
APPROVAL
PARAMETER TO BE CHECKED
PROBE
POWER REGULATOR
Range
Type
Code
Type
Code
Temperature
- 100...+ 500 °C
PT 100
3010110
RWF40
3010212
Pressure
0...2,5 bar
0...16 bar
Probe with output
4...20 mA
3010213
3010214
GB