background image

Operating Instructions and Parts Manual

7

MAINTENANCE

  Disconnect power and release all pressure from 

the system before attempting to install, service, relocate or perform any 

maintenance. Lock the power disconnect in the open (OFF) position. Tag 

out the power disconnect to prevent unexpected application of power.

  Débrancher de la source d’alimentation puis 

dissiper toute la pression du système avant d’essayer d’installer, 

de réparer, de déplacer ou de procéder à l’entretien. Verrouiller 

le sectionneur de courant en position ouverte (OFF). Étiqueter le 

sectionneur de courant pour éviter toute mise sous tension imprévue.

   Protect the pump from freezing during winter 

conditions.

 MISE EN GARDE

   Protéger la pompe du gel pendant l'hiver.

DRAINING THE PUMP

Drain openings are provided on all models.
To drain the pump:
1.   Remove drain fitting and prime plug to vent the system (see 

Figure 7).

2.   Drain all piping to a point below the freeze line.

DRAINING THE TANK

Conventional tanks can be drained by opening an outlet at the 

lowest point in the system. Remove plug or the air volume control 

to vent the tank.
Precharged tanks force virtually all the water from the tank when 

system pressure is released. No draining is necessary.

RESTARTING PUMP

If the pump has been serviced, drained or has not been used for 

some time, be sure there is water in the pump housing (volute) and 

the piping to the well. There must be water in the pump housing 

(volute) at all times when the pump is running to avoid internal 

damage of seal members.

WATERLOGGED TANKS: CONVENTIONAL

When a tank system has an inadequate ratio of air and water, the 

pump will start and stop often and eradically.
1.   Disconnect the power to the pump.
2.   Open the lowest faucet in the system to release all pressurized 

water in the system.

3.   Prime the pump (Priming the Shallow Well Pump on page 6).
4.   Reconnect the power to the pump.

NOTE:

 

As the pump refills the tank with water, the air volume 

control supplies the tank with the correct air to water ratio for the 

system to operate. If the air volume control is good, the pump will 

shut off at the desired cut-off and will be adjusted correctly.

WATERLOGGED TANKS: PRECHARGED

If a precharged tank becomes waterlogged, the bladder is normally 

leaking or broken.
1.   Test the tank by depressing the air valve. The air valve will expel 

water if the bladder is broken.

2.   If broken, replace the tank.

NOTE:

 

Once a bladder is leaking or broken, the bladder cannot be 

repaired. The tank must be replaced.

Figure 6- Vertical Tank

AIR VOLUME

AIR VOLUME

HOSE COUPLING

OUTLET

LUBRICATION

The bearings used in the pumps are lifetime lubricated at the 

factory and require no additional lubrication.

PRECHARGED TANK

Some air is lost through the bladder in any tank. To prevent tank 

failure, check the tank precharge on a yearly basis.
1.   Disconnect power to the pump, so water does not refill the 

precharged tank.

2.   Open a faucet nearest to the tank and allow all water to drain 

from the tank, then close.

3.   Measure the tank precharge at the valve stem using a tire 

gauge.

4.   If necessary, adjust the precharge with an air pump 28 - 30 psi 

on 1/2 HP and 3/4 HP pumps.

5. Reconnect power to the pump.

DISCHARGE

NOZZLE CLEAN 

OUT

PRIME PLUG

28-30 PSI 1/2 HP 

3/4 HP

DRAIN FITTING

Figure 7 - Precharged Storage Tank

KITS SECTION

REMOVING OLD SHAFT SEAL 

Disconnect power and release all 

pressure from the system before attempting to install, service, relocate or 

perform any maintenance.

1.   Disconnect power to the pump.

2.   Open a faucet nearest to the tank and allow all water to drain 

form the tank, then close.

3.   Remove the four cap screws holding the pump housing (volute) 

to the motor (Figure 8).

4.   Separate the pump housing (volute) from the motor to expose 

the diffuser and the seal plate.

5.   Remove the two cap screws and diffuser from the seal plate to 

expose the impeller.

6.   Remove the rear cover on the end of the motor opposite the 

impeller.

7.   Secure a 7/16" wrench across wrech flats of shaft to keep the 

shaft from rotating and remove the impeller by hand (standard 

right hand thread). Be sure to hold onto the seal plate when 

removing the impeller from the shaft.

Summary of Contents for RSWS Series

Page 1: ...del HP PSI Discharge Head Lift Distance 0 ft 5 ft 10 ft 15 ft 20 ft 25 ft RSWS75 3 4 30 779 750 721 691 662 633 40 644 615 586 557 528 499 50 510 481 451 422 393 364 RSWS50 1 2 30 711 674 638 601 565 529 40 543 506 470 433 397 361 50 375 338 302 265 229 193 Intended for Indoor Use Only Please read and save these instructions Read carefully before attempting to assemble install operate or maintain ...

Page 2: ...ESCRIPTION Shallow well jet pumps are single stage residential water pumps designed for pumping potable water in applications where the water is located less than 25 feet vertically from the pump A pressure switch is a standard feature The shallow well pump must be mounted to either a pre charged conventional type or free standing pressure tank Intended for indoor use only Installation of this pum...

Page 3: ...cal circuit checked by a licensed or certified electrician to make sure the circuit is properly grounded 12 The circuit voltage and frequency of electrical current must correspond with the specifications of the motor 13 Do NOT attempt repairs to the electric motor All repairs to the motor must be completed by a licensed electrician Do NOT touch an operating motor Modern motors are designed to oper...

Page 4: ...lling the pump Sand will damage the pumping parts and seal The draw down level of the well should not exceed the maximum rated depth for the pump The capacity of the pump will be reduced and a loss of prime may occur PIPING Inlet piping may be copper steel or rigid PVC plastic Flexible pipe is prohibited on suction pipe inlet pipe MISE EN GARDE Un tuyau flexible est interdit sur le tuyau d aspirat...

Page 5: ... well or sand or sediment WILL be drawn into the system MISE EN GARDE Le clapet de pied DOIT au moins être à 45 7 cm 18 po du fond du puits sinon du sable ou des sédiments POURRAIENT être aspirés dans le système NOTE When a lake is used as a water supply make sure the inlet pipe is deep enough to be submerged at all times Slope the horizontal piping upward toward the pump to prevent trapping air T...

Page 6: ...ire directly to the metal well casing or use a ground electrode furnished by the power company There is only one proper ground terminal on the unit The terminal s is located under the pressure switch cover is painted green and is identified as GRD The ground connection must be made at this terminal Figure 5 The ground conductor must not be smaller than the circuit conductors supplying the motor Di...

Page 7: ...tank with the correct air to water ratio for the system to operate If the air volume control is good the pump will shut off at the desired cut off and will be adjusted correctly WATERLOGGED TANKS PRECHARGED If a precharged tank becomes waterlogged the bladder is normally leaking or broken 1 Test the tank by depressing the air valve The air valve will expel water if the bladder is broken 2 If broke...

Page 8: ...ard washer 2 Carefully slip seal plate over shaft Do not disturb seal position in seal plate The seal plate must be orientated during assembly so the two screw holes are on a horizontal line across the motor shaft Figure 10 This placement should be done to ensure proper draining and priming 3 Place rotating shaft seal member in position on impeller and press into place Take care not to press again...

Page 9: ...th new parts in reverse order 14 Wipe down the seal plate to remove any debris or loose rust 15 Push the ceramic seat of the shaft seal into the seal plate using the cardboard ring provided to keep the ceramic face clean You can use a little water or dish soap to lubricate the seal pocket to make assembly easier 16 Slide the square cut gasket over the flange on the seal plate make sure not to let ...

Page 10: ...alve may be clogged or stuck closed 8 Pump not fully primed 9 Water level below maximum lift specification 10 Undersized piping 11 Gaseous well 12 Distorted venturi 13 Incorrect jet for application 14 Undersized pump 15 Pump cavitates sounds like pumping gravel 16 Low supply voltage 1 Lower suction pipe further into wall 2 Open faucet to allow air to vent while priming pump 3 Repair or replace to ...

Page 11: ... or concrete to prevent cave in D DRIVEN WELL Pipe with a pointed screen is driven into the ground below the water table The depth is usually less than 50 feet Available diameters are 1 through 2 E DRILLED WELL A hole bored into the earth with machinery and lined with pipe Depths range from a few feet to over 1000 feet Common well diameters are 2 3 4 and 6 for domestic water wells F CISTERN An und...

Page 12: ...IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE AND ANY RIGHTS OR REMEDIES AGAINST ANY PERSON OR ENTITY UNDER THE UNIFORM COMMERCIAL CODE OR OTHERWISE WITH RESPECT TO THE SALE OF THE PRODUCT THE REMEDIES AND OBLIGATIONS STATED IN THIS WARRANTY ARE THE SOLE AND EXCLUSIVE REMEDIES OF AND OBLIGATIONS TO THE OWNER FOR ANY AND ALL MATTERS ARISING WITH RESPECT TO OR IN ANY WAY ...

Reviews: