Operating Instructions and Parts Manual

5

   The foot valve MUST be at least 18” from the 

bottom of the well or sand or sediment WILL be drawn into the system.

 MISE EN GARDE

   Le clapet de pied DOIT au moins être 

à 45,7 cm (18 po) du fond du puits, sinon du sable ou des sédiments 

POURRAIENT être aspirés dans le système

4.   After proper depth is reached, install a well seal or pitless 

adapter to support pipe and prevent surface water and other 

contaminants from entering well.

INSTALLATION (CONT'D)

5.   Slope the horizontal pipe upward toward the pump to eliminate 

trapping air. Sloping the pipe will also aid in priming the pump.

DRIVEN WELL (FIGURE 12 ON PAGE 11)

1.   Drive the point several feet below the water table.

NOTE:

 

A packer type foot valve can be installed in the well (Figure 

2, Illustration B). This type of foot valve allows the well to be filled 

with water when priming and makes the inlet pipe much easier to 

test for leaks. Follow the manufacturer’s instructions when installing 

the packer type foot valve.

As an alternative, an in-line check valve can be used with a driven 

well (Figure 2, Illustration C). The pipe between the check valve and 

the water level will always be under a vacuum.
Leaking joints or couplings will allow air to leak into the pipe and 

cause abnormal pump operation. Make sure to use pipe joint 

compound on all male pipe threads.

DRIVE POINT

TO PUMP

PACKER TYPE 

FOOT VALVE

Figure 2

Figure 2
Illustration B

Illustration B

Figure 2
Illustration C

DRIVE POINT

TO PUMP

IN-LINE 

CHECK VALVE

DUG WELL, CISTERN, LAKE AND SPRING INSTALLATION 
(FIGURE 12 ON PAGE 11)

1.   Install a foot valve on inlet pipe and lower into water.

   The foot valve MUST be at least 18” from the 

bottom of the well or sand or sediment WILL be drawn into the system.

 MISE EN GARDE

   Le clapet de pied DOIT au moins être 

à 45,7 cm (18 po) du fond du puits, sinon du sable ou des sédiments 

POURRAIENT être aspirés dans le système

NOTE:

 

When a lake is used as a water supply, make sure the 

inlet pipe is deep enough to be submerged at all times. Slope the 

horizontal piping upward toward the pump to prevent trapping 

air. The pipe must be removed during winter months or protected 

against freezing.Protect the pipe from damage from swimmers and 

boats.

   Install a screen around the inlet pipe to prevent 

the entrapment of swimmers, wildlife and debris.

 MISE EN GARDE

   Installer un écran autour du tuyau 

d'entrée pour éviter de piéger des nageurs, des animaux et des débris.

SHALLOW WELL PUMP WITH CONVENTIONAL STORAGE 
TANK

1.   Install air volume control on tank.
2.   Connect the copper tube from the air volume control to the 

uppermost 1/8” NPT opening on the side of pump. Be sure 

the connections are tight. Leaking can cause the pump not to 

prime (Figure 3).

3.   Install a valve and an isolator hose between the tank and the 

house plumbing to aid in pump removal for servicing and for 

reducing the noise transmitted to the house through the piping.

4.   Provide a faucet at the lowest point in the system to drain the 

system for service or storage.

SHALLOW WELL PUMP WITH PRECHARGED STORAGE 
TANK

1.   Shut off the power to the pump.
2.   Open the faucet nearest the tank and allow all water to drain 

from the tank.

3.   Measure the tank precharge at the valve stem using a tire 

pressure gauge.

4.   If necessary, precharge with an air pump to 28 - 30 psi on 

1/2HP and 3/4HP pumps.

5.   Slope the horizontal pipes upward toward the pump to prevent 

trapping air. If the horizontal distance exceeds 25 feet, see 

Chart 2 on page 4 for the recommended pipe size.

Figure 3 - Horizontal Tank

PRIME PLUG

AIR VOLUME 

CONTROL TUBING

SUCTION

AIR VOLUME

PUMP

TANK

Summary of Contents for RSWS Series

Page 1: ...del HP PSI Discharge Head Lift Distance 0 ft 5 ft 10 ft 15 ft 20 ft 25 ft RSWS75 3 4 30 779 750 721 691 662 633 40 644 615 586 557 528 499 50 510 481 451 422 393 364 RSWS50 1 2 30 711 674 638 601 565 529 40 543 506 470 433 397 361 50 375 338 302 265 229 193 Intended for Indoor Use Only Please read and save these instructions Read carefully before attempting to assemble install operate or maintain ...

Page 2: ...ESCRIPTION Shallow well jet pumps are single stage residential water pumps designed for pumping potable water in applications where the water is located less than 25 feet vertically from the pump A pressure switch is a standard feature The shallow well pump must be mounted to either a pre charged conventional type or free standing pressure tank Intended for indoor use only Installation of this pum...

Page 3: ...cal circuit checked by a licensed or certified electrician to make sure the circuit is properly grounded 12 The circuit voltage and frequency of electrical current must correspond with the specifications of the motor 13 Do NOT attempt repairs to the electric motor All repairs to the motor must be completed by a licensed electrician Do NOT touch an operating motor Modern motors are designed to oper...

Page 4: ...lling the pump Sand will damage the pumping parts and seal The draw down level of the well should not exceed the maximum rated depth for the pump The capacity of the pump will be reduced and a loss of prime may occur PIPING Inlet piping may be copper steel or rigid PVC plastic Flexible pipe is prohibited on suction pipe inlet pipe MISE EN GARDE Un tuyau flexible est interdit sur le tuyau d aspirat...

Page 5: ... well or sand or sediment WILL be drawn into the system MISE EN GARDE Le clapet de pied DOIT au moins être à 45 7 cm 18 po du fond du puits sinon du sable ou des sédiments POURRAIENT être aspirés dans le système NOTE When a lake is used as a water supply make sure the inlet pipe is deep enough to be submerged at all times Slope the horizontal piping upward toward the pump to prevent trapping air T...

Page 6: ...ire directly to the metal well casing or use a ground electrode furnished by the power company There is only one proper ground terminal on the unit The terminal s is located under the pressure switch cover is painted green and is identified as GRD The ground connection must be made at this terminal Figure 5 The ground conductor must not be smaller than the circuit conductors supplying the motor Di...

Page 7: ...tank with the correct air to water ratio for the system to operate If the air volume control is good the pump will shut off at the desired cut off and will be adjusted correctly WATERLOGGED TANKS PRECHARGED If a precharged tank becomes waterlogged the bladder is normally leaking or broken 1 Test the tank by depressing the air valve The air valve will expel water if the bladder is broken 2 If broke...

Page 8: ...ard washer 2 Carefully slip seal plate over shaft Do not disturb seal position in seal plate The seal plate must be orientated during assembly so the two screw holes are on a horizontal line across the motor shaft Figure 10 This placement should be done to ensure proper draining and priming 3 Place rotating shaft seal member in position on impeller and press into place Take care not to press again...

Page 9: ...th new parts in reverse order 14 Wipe down the seal plate to remove any debris or loose rust 15 Push the ceramic seat of the shaft seal into the seal plate using the cardboard ring provided to keep the ceramic face clean You can use a little water or dish soap to lubricate the seal pocket to make assembly easier 16 Slide the square cut gasket over the flange on the seal plate make sure not to let ...

Page 10: ...alve may be clogged or stuck closed 8 Pump not fully primed 9 Water level below maximum lift specification 10 Undersized piping 11 Gaseous well 12 Distorted venturi 13 Incorrect jet for application 14 Undersized pump 15 Pump cavitates sounds like pumping gravel 16 Low supply voltage 1 Lower suction pipe further into wall 2 Open faucet to allow air to vent while priming pump 3 Repair or replace to ...

Page 11: ... or concrete to prevent cave in D DRIVEN WELL Pipe with a pointed screen is driven into the ground below the water table The depth is usually less than 50 feet Available diameters are 1 through 2 E DRILLED WELL A hole bored into the earth with machinery and lined with pipe Depths range from a few feet to over 1000 feet Common well diameters are 2 3 4 and 6 for domestic water wells F CISTERN An und...

Page 12: ...IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE AND ANY RIGHTS OR REMEDIES AGAINST ANY PERSON OR ENTITY UNDER THE UNIFORM COMMERCIAL CODE OR OTHERWISE WITH RESPECT TO THE SALE OF THE PRODUCT THE REMEDIES AND OBLIGATIONS STATED IN THIS WARRANTY ARE THE SOLE AND EXCLUSIVE REMEDIES OF AND OBLIGATIONS TO THE OWNER FOR ANY AND ALL MATTERS ARISING WITH RESPECT TO OR IN ANY WAY ...

Reviews: