Control Termianl 

 

Type 

Symbol 

Function 

Description 

Control c

ircui

t ter

mi

nal

 

Control 

power

 

P24 

Power terminal;   

Control device usage 

Output DC+24V; Maximum supplied current is 50mA. 

P12/12V 

Output DC+12V; Maximum supplied current is 20mA. 

GND 

(COM) 

Common of analog input 

control terminals 

Common terminal for control power (P12/12V,P24) and 
analog input terminal (Vin, Iin).   

Input termi

nal

s

 

FWD 

Forward command 

terminal 

Connect the FWD and COM terminals for forward 
operation. (F_001=0,1,2) 

REV 

Reverse command 

terminal 

Connect the REV and COM terminals for reverse operation. 
(F_001=0,1,2) 

X1 

Multi-function input 

terminal 1 

The function is set by F_052. 

Default setting: Multi-speed level 1 command 

X2 

Multi-function input 

terminal 2 

The function is set by F_053. 

Default setting: Multi-speed level 2 command 

X3 

Multi-function input 

terminal 3 

The function is set by F_054. 

Default setting: Jog command 

X4 

Multi-function input 

terminal 4 

The function is set by F_055. 

Default setting: Secondary accel/decel time command 

X5 

Multi-function input 

terminal 5 

The function is set by F_056. 

Default setting: External fault command (thr) 

X6 

Multi-function input 

terminal 6 

The function is set by F_057. 

Default setting: Reset command 

COM 

(GND) 

Common of digital input 

control terminals 

Common of digital input control signal terminals. (FWD, 
REV and X1 ~ X6) 

Vin 

Analog input terminal    Input range: DC 0~10V

 

Iin 

Analog input terminal 

Input signal selection 
JP4: I position (current signal) 
JP4: V position (voltage signal) 

Input range: DC 4~20mA (2~10V) or   

DC 0~20mA (0~10V) 

The function is set by F_126. 

O

utput te

rmin

al

s

 

FM+ 
AM+ 

Analog output terminals 

Voltage meter with 10V full scale spec. 

(meter impedance: 10kΩ above) 

Maximum output current: 1mA 

M- 

(GND) 

Common of   

analog output terminals 

Common of analog output terminals. 

Ta1 

Multi-function 

output terminals 

(relay type) 

N.O (contact a); The function is set by F_060 . 

Default setting: Error detection 

Capacity: AC250V, 0.5A 

Max, cosθ=0.3 

Tb1 

N.C (contact b); The function is set by F_060   

Capacity: AC250V, 0.5A 

Max, cosθ=0.3 

Tc1 

Common terminal for Ta1, Tb1. 

Ta2 

N.O (contact a); The function is set by F_131 

Default setting: Operation detection 

Capacity: AC250V, 0.5A 

Max, cosθ=0.3 

Tb2 

N.C (contact b); The function is set by F_131   

Capacity: AC250V, 0.5A 

Max, cosθ=0.3 

Tc2 

Common terminal for Ta2. 

Y1 

Multi-function output 

terminals 

(open collector type) 

The function is set by F_058, F_059. 

Capacity: DC48V, 50mA Max 

Y2 

CME 

Common terminal of Y1, Y2. 

Ex

ternal

 

Comm

uni

c

ati

on

 

T

ermi

nal

 

DX+ 

Signal transmission 

te) 

Connect the RM6 series drive by transmission cable, 
when the drive is controlled by RS-485 communication 
interface. 

Communication protocol: Modbus 

DX- 

Signal transmission 

terminal(-) 

GND 

Grounding terminal of 

signal transmission 

Grounding terminal of shielding wire. 

Summary of Contents for RM6 Series

Page 1: ...source input terminals Single phase sinusoidal power source input terminals R S T L1 L2 L3 Three phase sinusoidal power source input terminals N DC power source input terminals External DC power source terminal Only 2007 2015 4007 4020 models have the terminal Motor U V W T1 T2 T3 Drive outputs to motor terminals Output three phase variable frequency and voltage to motor Power and Braking P N Dyna...

Page 2: ...ption Jumper P PR P1 1 DC Reactor DCL option RM6 IM R L1 S L2 W T3 V T2 U T1 Induction Motor T L3 R L1 S L2 T L3 N Jumper P P1 1 DC Reactor DCL option Model RM6 2007 RM6 2015 Model RM6 4007 RM6 4025 Model RM6 2020 RM6 2040 Model RM6 4030 RM6 4060 RM6 IM R L1 S L2 W T3 V T2 U T1 Induction Motor T L3 R L1 S L2 T L3 N Jumper P P1 1 DC Reactor DCL option Three Phase 50 60Hz AC Power Input 2 Braking Re...

Page 3: ... R L1 S L2 W T3 V T2 U T1 Induction Motor T L3 R L1 S L2 T L3 Three Phase 50 60Hz AC Power Input Model RM6 2050 RM6 2075 Model RM6 4075 1 N Jumper P P1 1 DC reactor DCL option 1 RM6 100HP above drives AC reactor ACL is the standard accessory RM6 175HP above drives DC reactor DCL is the standard accessory Please remove the jumper between P1 and P terminal when connecting the external DC reactor DCL...

Page 4: ...tal input control signal terminals FWD REV and X1 X6 Vin Analog input terminal Input range DC 0 10V Iin Analog input terminal Input signal selection JP4 I position current signal JP4 V position voltage signal Input range DC 4 20mA 2 10V or DC 0 20mA 0 10V The function is set by F_126 Output terminals FM AM Analog output terminals Voltage meter with 10V full scale spec meter impedance 10kΩ above Ma...

Page 5: ...ded Wire P P P P VR 1KΩ 1 4W Forward Reverse Multi function Input Terminal 1 Multi function Output Terminal Relay Type AC 250V 0 5A COSθ 0 3 Multi function Output Terminal Open collector DC 48V 50mA 2 M GND Analog Output Terminal DC 0 10V 1 COM GND Analog input signal default DC 4 20mA Analog input control default DC 0 10V JP4 Communication Control Terminal P DX DX GND P24 JP5 ON 1 DSW3 Multi func...

Page 6: ...udes fault messages and three modes The switching methods are shown as below figure Monitor mode Function setting mode Parameter setting mode Fault message FUN DATA PROG FUN DATA STOP RESET PROG PROG KEYPAD Hz V A KEYPAD Hz V A KEYPAD Hz V A KEYPAD Hz V A When the keypad is idle for three minutes at function setting mode or parameter setting mode drive will switch back to the main display The oper...

Page 7: ...ture FUN DATA FUN DATA Func Name Description Range of Setting Unit Default F_000 Drive Information 0 Software version 1 Drive model number 2 Drive running hours 3 Drive supply power time 4 Software checksum code 5 Reserved F_001 Start Command Selection Start command Rotation direction command 0 11 3 0 FWD or REV terminal FWD or REV terminal 1 FWD terminal REV terminal 2 Keypad RUN key FWD REV term...

Page 8: ...mand Multi speed level 1 command 0 00 400 00 0 01 Hz 50 00 Note1 OFF OFF OFF OFF 60 00 Note2 F_010 Preset Speed 1 OFF OFF OFF ON 10 00 F_011 Preset Speed 2 OFF OFF ON OFF 20 00 F_012 Preset Speed 3 OFF OFF ON ON 30 00 F_013 Preset Speed 4 OFF ON OFF OFF 0 00 F_014 Preset Speed 5 OFF ON OFF ON 0 00 F_015 Preset Speed 6 OFF ON ON OFF 0 00 F_016 Preset Speed 7 OFF ON ON ON 0 00 F_196 Preset Speed 8 O...

Page 9: ... of V F pattern 0 0 399 9 0 1Hz 0 0 F_037 V F Voltage 1 Voltage at the first point of V F pattern 0 0 255 0 0 1V 0 0 0 0 510 0 F_038 V F Frequency 2 Frequency at the second point of V F pattern 0 0 399 9 0 1Hz 0 0 F_039 V F Voltage 2 Voltage at the second point of V F pattern 0 0 255 0 0 1V 0 0 0 0 510 0 F_040 Vin Gain Analog input Vin gain ratio adjustment 0 00 2 00 0 01 1 00 F_041 Vin Bias Analo...

Page 10: ...nction Input Terminal X4 0 Selection of primary or secondary frequency command ON secondary frequency command 2 F_056 Multi function Input Terminal X5 0 Stop command with 3 wire start stop circuit N O contact a 7 F_057 Multi function Input Terminal X6 0 Stop command with 3 wire start stop circuit N C contact b 6 F_058 Multi function Output Terminal Y1 0 Disable 1 Operation command detection 2 Cons...

Page 11: ...rrent level of DC braking 0 150 of drive rated current 1 50 F_076 Time of DC Braking after Stop Set the time for DC braking after drive stopped 0 0 20 0 0 1sec 0 5 F_077 Time of DC Braking before Start Set the time for DC braking before drive started 0 0 20 0 0 1sec 0 0 F_078 Operation Selection at Instantaneous Power Failure 0 Drive cannot be restarted 1 Drive can be restarted 2 Ramp to stop 3 Dr...

Page 12: ...onitor mode of external indicator 3 0 Disable 0 10 2 F_102 V F Pattern Selection 0 Linear 1 Energy saving mode auto adjust V F pattern according to the load condition 2 Square curve 3 1 7th power curve 4 1 5th power curve 0 4 0 F_103 Subtracted Frequency of Ramp to Stop by Power Failure When the power failure drive will substract the setting value from the current frequency before ramp to stop F_0...

Page 13: ...he terminal is activated with the duration 1 5 sec 6 Edge trigger 1 6 1 F_121 UP DOWN Frequency Adjustment Adjust UP DOWN frequency by KP 603 keypad 0 00 400 00 0 01 Hz 0 00 F_122 Secondary Frequency Command Selection 0 Frequency command by analog signal via terminal 1 Frequency command by keypad 2 Frequency command by UP DOWN terminal 3 Frequency command by communication 0 3 0 F_123 Analog Input ...

Page 14: ...PID control and command by SV condition 0 PV value 1 SV PV value 0 1 1 F_150 PID Control Command 0 By F_002 1 Analong frequency command controls SV 2 Keypad conrols SV 3 Communication interface controls SV 0 3 2 F_151 Upper Limit of Transmitter Set the value in accordance with the maximum specification of transmitter 800 0 800 0 0 1unit 10 0 F_152 Lower Limit of Transmitter Set the value in accord...

Page 15: ...ion F_178 drive starts 0 250 1sec 0 F_179 Off Delay Time After the PV value exceeds the Off range and lasts a duration F_179 drive stops 0 250 1sec 0 F_180 On Off Accel Decel Time Selection 0 Primary accel decel time 1 Secondary accel decel time 0 1 1 F_181 Off Holding Time Hold the Off condition with the duration 0 240 1sec 0 F_182 Air conditioning mode 0 Disable 1 Enable 0 1 0 F_183 Air Conditio...

Page 16: ...urrent Oscillation Gain HPF The setting gain of the current oscillation 16 1 0 255 0 F_220 Cut frequency of Current Oscillation When the setting value is too high it will make the output current to high in light duty 0 2000 400 F_221 Current Oscillation Gain LPF When the setting value is too high it will make the output current to high in light duty 0 255 128 F_222 Upper frequency of Current Oscil...

Page 17: ...se open PAdF KEYPAD Hz V A Keypad interruption during copy LE1 KEYPAD Hz V A Under voltage during operation OH KEYPAD Hz V A Drive overheating OC KEYPAD Hz V A Drive over current OL KEYPAD Hz V A Motor overload GF KEYPAD Hz V A Grounding fault OL1 KEYPAD Hz V A Drive overload OE KEYPAD Hz V A Over voltage ntCF KEYPAD Hz V A NTC thermistor sensor fault no Fb KEYPAD Hz V A PID feedback signal error ...

Page 18: ...to stop Wr_F KEYPAD Hz V A Different software version inter copy db KEYPAD Hz V A Over voltage at stop PUF1 KEYPAD Hz V A First time you enter wrong LOC KEYPAD Hz V A Parameter locking PUF2 KEYPAD Hz V A Second time you enter wrong ULOC KEYPAD Hz V A Parameter Password Unlock PUF3 KEYPAD Hz V A Third time you enter wrong dtF KEYPAD Hz V A Direction command error Ht KEYPAD Hz V A Drive overheat PrE...

Reviews: