16
Func.
Name
Description
Range of
Setting
Unit Default
F_191
Feedback Limit
Level
Set the physical volume according to the specification
of transmitter(refer to F_151, F_152)
-800.0~
800.0
0.1
8.0
F_192
Feedback Limit
Detection Setting
0: Detection when “PV” > F_191
1: Detection when “PV” < F_191
0,1
─
0
F_193
Feedback Limit
Detection Time
When the feedback signal exceeds the setting value
of F_191 and maintaining a duration, drive is
detection. Drive will close the detection when the
feedback signal is without the range of feedback limit.
0~2550 1 sec
300
F_194
Feedback Limit
Range Setting
0~20.0
0.1
unit
1.0
F_195
(Feedback Limit)
Condition Selection
0: Enable during operation
1: Enable full time
0,1
─
1
F_208
Filter Setting of
Keypad pot knob
Filter the input signal when the frequency command
is controlled by keypad pot knob. (F_002=6).
0~255
─
10
F_209
Keypad pot knob
Bias
Analog input “keypad pot knob” bias ratio adjustment. 0.00~1.00 0.01
0.00
F_211 Drive Duty selection 0: Heavy duty(150% OL1)1: Normal duty(120% OL1)
0,1
─
0
F_212
Parameter Display
Selection of
Parameter Lock
1: Paramerter cannot be changed after F_213 is
ocked, but it can display the setting value.
2: Paramerter cannot be changed after F_213 is
locked, but it cannot display the setting value.
0~1
─
0
F_213
Parameter Lock
Password Setting
Setting the password of parameter lock.
0~9999
1
0
F_214
Parameter Lock
Decoding Setting
Decording the password of parameter lock.
0~9999
1
─
F_215
Current Oscillation
Gain (HPF)
The setting gain of the current oscillation (16=1)
0~255
─
0
F_220
Cut frequency of
Current Oscillation
When the setting value is too high, it will make the
output current to high in light duty.
0~2000
─
400
F_221
Current Oscillation
Gain (LPF)
When the setting value is too high, it will make the
output current to high in light duty.
0~255
─
128
F_222
Upper frequency of
Current Oscillation
prevention
The function of current oscillation enable when the
output frequency is within the range of F_222 and
F_223.
0~255
Hz
25
F_223
lower frequency of
Current Oscillation
prevention
0~255
Hz
14
F_224
Default Setting
0: Disable
─
─
0
CLF: Clear fault records
dEF60: Default value of drive for 60Hz.(heavy duty)
dEF50: Default value of drive for 50Hz.(heavy duty)
SAv: Save the setting value.
rES: Restore the setting value.
rd_EE: Read the parameters from drive to Keypad
Wr_EE: Write the parameters from keypad to drive
dEFC3: Default value of constant pressure PID
control for 50Hz
dEFC4: Default value of constant pressure PID
control for 60Hz
dEFC1~dEFC6: Customize default value
PdEF60: Default value of drive for 60Hz(normal duty)
PdEF50: Default value of drive for 50Hz(normal duty)
The color as means the functions can be set during operation.
Note:
1. Default value of 50Hz.
2. Default value of 60Hz.
3. Specification of 200V series.
4. Specification of 400V series.
5. 0.5 ~ 5HP: 5sec / 7.5 ~ 30HP: 15sec / 40HP above: 30sec
6. Heavy duty: When F_081 exceeds 4, the drive must be de-rating or selecting higher capacity.
Normal duty: When F_081 exceeds 2, the drive must be de-rating or selecting higher capacity.
7.
+
: Represents a contact (N.O)
-
: Represents b contact (N.C)