16 

Func. 

Name 

Description 

Range of 

Setting 

Unit  Default 

F_191 

Feedback Limit 

Level 

Set the physical volume according to the specification 
of transmitter(refer to F_151, F_152) 

-800.0~ 

800.0 

0.1 

8.0 

F_192 

Feedback Limit 

Detection Setting 

0: Detection when “PV” > F_191 
1: Detection when “PV” < F_191 

0,1 

─ 

F_193 

Feedback Limit 

Detection Time 

When the feedback signal exceeds the setting value 
of F_191 and maintaining a duration, drive is 
detection. Drive will close the detection when the 
feedback signal is without the range of feedback limit. 

0~2550  1 sec 

300 

F_194 

Feedback Limit 

Range Setting 

0~20.0 

0.1 

unit 

1.0 

F_195 

(Feedback Limit) 

Condition Selection 

0: Enable during operation   
1: Enable full time 

0,1 

─ 

F_208 

Filter Setting of 

Keypad pot knob 

Filter the input signal when the frequency command 
is controlled by keypad pot knob. (F_002=6). 

0~255 

─ 

10 

F_209 

Keypad pot knob 

Bias 

Analog input “keypad pot knob” bias ratio adjustment. 0.00~1.00  0.01 

0.00 

F_211  Drive Duty selection 0: Heavy duty(150% OL1)1: Normal duty(120% OL1) 

0,1 

─ 

F_212 

Parameter Display 

Selection of 

Parameter Lock   

1: Paramerter cannot be changed after F_213 is 
ocked, but it can display the setting value. 
2: Paramerter cannot be changed after F_213 is 
locked, but it cannot display the setting value. 

0~1 

─ 

F_213 

Parameter Lock 

Password Setting 

Setting the password of parameter lock. 

0~9999 

F_214 

Parameter Lock 

Decoding Setting 

Decording the password of parameter lock. 

0~9999 

─ 

F_215 

Current Oscillation   

Gain (HPF) 

The setting gain of the current oscillation (16=1) 

0~255 

─ 

F_220 

Cut frequency of 

Current Oscillation   

When the setting value is too high, it will make the 
output current to high in light duty. 

0~2000 

─ 

400 

F_221 

Current Oscillation   

Gain (LPF) 

When the setting value is too high, it will make the 
output current to high in light duty. 

0~255 

─ 

128 

F_222 

Upper frequency of 

Current Oscillation 

prevention     

The function of current oscillation enable when the 
output frequency is within the range of F_222 and 
F_223. 

0~255 

Hz 

25 

F_223 

lower frequency of 
Current Oscillation 

prevention 

0~255 

Hz 

14 

F_224 

Default Setting 

0: Disable 

─ 

─ 

CLF: Clear fault records 
dEF60: Default value of drive for 60Hz.(heavy duty) 
dEF50: Default value of drive for 50Hz.(heavy duty) 
SAv: Save the setting value. 
rES: Restore the setting value. 
rd_EE: Read the parameters from drive to Keypad 
Wr_EE: Write the parameters from keypad to drive 
dEFC3: Default value of constant pressure PID 

control for 50Hz 

dEFC4: Default value of constant pressure PID 

control for 60Hz 

dEFC1~dEFC6: Customize default value 
PdEF60: Default value of drive for 60Hz(normal duty) 
PdEF50: Default value of drive for 50Hz(normal duty) 

The color as                      means the functions can be set during operation. 

Note: 
1. Default value of 50Hz. 
2. Default value of 60Hz. 
3. Specification of 200V series. 
4. Specification of 400V series. 
5. 0.5 ~ 5HP: 5sec / 7.5 ~ 30HP: 15sec / 40HP above: 30sec 
6. Heavy duty: When F_081 exceeds 4, the drive must be de-rating or selecting higher capacity. 

Normal duty: When F_081 exceeds 2, the drive must be de-rating or selecting higher capacity. 

7.

: Represents a contact (N.O) 

: Represents b contact (N.C) 

Summary of Contents for RM6 Series

Page 1: ...source input terminals Single phase sinusoidal power source input terminals R S T L1 L2 L3 Three phase sinusoidal power source input terminals N DC power source input terminals External DC power source terminal Only 2007 2015 4007 4020 models have the terminal Motor U V W T1 T2 T3 Drive outputs to motor terminals Output three phase variable frequency and voltage to motor Power and Braking P N Dyna...

Page 2: ...ption Jumper P PR P1 1 DC Reactor DCL option RM6 IM R L1 S L2 W T3 V T2 U T1 Induction Motor T L3 R L1 S L2 T L3 N Jumper P P1 1 DC Reactor DCL option Model RM6 2007 RM6 2015 Model RM6 4007 RM6 4025 Model RM6 2020 RM6 2040 Model RM6 4030 RM6 4060 RM6 IM R L1 S L2 W T3 V T2 U T1 Induction Motor T L3 R L1 S L2 T L3 N Jumper P P1 1 DC Reactor DCL option Three Phase 50 60Hz AC Power Input 2 Braking Re...

Page 3: ... R L1 S L2 W T3 V T2 U T1 Induction Motor T L3 R L1 S L2 T L3 Three Phase 50 60Hz AC Power Input Model RM6 2050 RM6 2075 Model RM6 4075 1 N Jumper P P1 1 DC reactor DCL option 1 RM6 100HP above drives AC reactor ACL is the standard accessory RM6 175HP above drives DC reactor DCL is the standard accessory Please remove the jumper between P1 and P terminal when connecting the external DC reactor DCL...

Page 4: ...tal input control signal terminals FWD REV and X1 X6 Vin Analog input terminal Input range DC 0 10V Iin Analog input terminal Input signal selection JP4 I position current signal JP4 V position voltage signal Input range DC 4 20mA 2 10V or DC 0 20mA 0 10V The function is set by F_126 Output terminals FM AM Analog output terminals Voltage meter with 10V full scale spec meter impedance 10kΩ above Ma...

Page 5: ...ded Wire P P P P VR 1KΩ 1 4W Forward Reverse Multi function Input Terminal 1 Multi function Output Terminal Relay Type AC 250V 0 5A COSθ 0 3 Multi function Output Terminal Open collector DC 48V 50mA 2 M GND Analog Output Terminal DC 0 10V 1 COM GND Analog input signal default DC 4 20mA Analog input control default DC 0 10V JP4 Communication Control Terminal P DX DX GND P24 JP5 ON 1 DSW3 Multi func...

Page 6: ...udes fault messages and three modes The switching methods are shown as below figure Monitor mode Function setting mode Parameter setting mode Fault message FUN DATA PROG FUN DATA STOP RESET PROG PROG KEYPAD Hz V A KEYPAD Hz V A KEYPAD Hz V A KEYPAD Hz V A When the keypad is idle for three minutes at function setting mode or parameter setting mode drive will switch back to the main display The oper...

Page 7: ...ture FUN DATA FUN DATA Func Name Description Range of Setting Unit Default F_000 Drive Information 0 Software version 1 Drive model number 2 Drive running hours 3 Drive supply power time 4 Software checksum code 5 Reserved F_001 Start Command Selection Start command Rotation direction command 0 11 3 0 FWD or REV terminal FWD or REV terminal 1 FWD terminal REV terminal 2 Keypad RUN key FWD REV term...

Page 8: ...mand Multi speed level 1 command 0 00 400 00 0 01 Hz 50 00 Note1 OFF OFF OFF OFF 60 00 Note2 F_010 Preset Speed 1 OFF OFF OFF ON 10 00 F_011 Preset Speed 2 OFF OFF ON OFF 20 00 F_012 Preset Speed 3 OFF OFF ON ON 30 00 F_013 Preset Speed 4 OFF ON OFF OFF 0 00 F_014 Preset Speed 5 OFF ON OFF ON 0 00 F_015 Preset Speed 6 OFF ON ON OFF 0 00 F_016 Preset Speed 7 OFF ON ON ON 0 00 F_196 Preset Speed 8 O...

Page 9: ... of V F pattern 0 0 399 9 0 1Hz 0 0 F_037 V F Voltage 1 Voltage at the first point of V F pattern 0 0 255 0 0 1V 0 0 0 0 510 0 F_038 V F Frequency 2 Frequency at the second point of V F pattern 0 0 399 9 0 1Hz 0 0 F_039 V F Voltage 2 Voltage at the second point of V F pattern 0 0 255 0 0 1V 0 0 0 0 510 0 F_040 Vin Gain Analog input Vin gain ratio adjustment 0 00 2 00 0 01 1 00 F_041 Vin Bias Analo...

Page 10: ...nction Input Terminal X4 0 Selection of primary or secondary frequency command ON secondary frequency command 2 F_056 Multi function Input Terminal X5 0 Stop command with 3 wire start stop circuit N O contact a 7 F_057 Multi function Input Terminal X6 0 Stop command with 3 wire start stop circuit N C contact b 6 F_058 Multi function Output Terminal Y1 0 Disable 1 Operation command detection 2 Cons...

Page 11: ...rrent level of DC braking 0 150 of drive rated current 1 50 F_076 Time of DC Braking after Stop Set the time for DC braking after drive stopped 0 0 20 0 0 1sec 0 5 F_077 Time of DC Braking before Start Set the time for DC braking before drive started 0 0 20 0 0 1sec 0 0 F_078 Operation Selection at Instantaneous Power Failure 0 Drive cannot be restarted 1 Drive can be restarted 2 Ramp to stop 3 Dr...

Page 12: ...onitor mode of external indicator 3 0 Disable 0 10 2 F_102 V F Pattern Selection 0 Linear 1 Energy saving mode auto adjust V F pattern according to the load condition 2 Square curve 3 1 7th power curve 4 1 5th power curve 0 4 0 F_103 Subtracted Frequency of Ramp to Stop by Power Failure When the power failure drive will substract the setting value from the current frequency before ramp to stop F_0...

Page 13: ...he terminal is activated with the duration 1 5 sec 6 Edge trigger 1 6 1 F_121 UP DOWN Frequency Adjustment Adjust UP DOWN frequency by KP 603 keypad 0 00 400 00 0 01 Hz 0 00 F_122 Secondary Frequency Command Selection 0 Frequency command by analog signal via terminal 1 Frequency command by keypad 2 Frequency command by UP DOWN terminal 3 Frequency command by communication 0 3 0 F_123 Analog Input ...

Page 14: ...PID control and command by SV condition 0 PV value 1 SV PV value 0 1 1 F_150 PID Control Command 0 By F_002 1 Analong frequency command controls SV 2 Keypad conrols SV 3 Communication interface controls SV 0 3 2 F_151 Upper Limit of Transmitter Set the value in accordance with the maximum specification of transmitter 800 0 800 0 0 1unit 10 0 F_152 Lower Limit of Transmitter Set the value in accord...

Page 15: ...ion F_178 drive starts 0 250 1sec 0 F_179 Off Delay Time After the PV value exceeds the Off range and lasts a duration F_179 drive stops 0 250 1sec 0 F_180 On Off Accel Decel Time Selection 0 Primary accel decel time 1 Secondary accel decel time 0 1 1 F_181 Off Holding Time Hold the Off condition with the duration 0 240 1sec 0 F_182 Air conditioning mode 0 Disable 1 Enable 0 1 0 F_183 Air Conditio...

Page 16: ...urrent Oscillation Gain HPF The setting gain of the current oscillation 16 1 0 255 0 F_220 Cut frequency of Current Oscillation When the setting value is too high it will make the output current to high in light duty 0 2000 400 F_221 Current Oscillation Gain LPF When the setting value is too high it will make the output current to high in light duty 0 255 128 F_222 Upper frequency of Current Oscil...

Page 17: ...se open PAdF KEYPAD Hz V A Keypad interruption during copy LE1 KEYPAD Hz V A Under voltage during operation OH KEYPAD Hz V A Drive overheating OC KEYPAD Hz V A Drive over current OL KEYPAD Hz V A Motor overload GF KEYPAD Hz V A Grounding fault OL1 KEYPAD Hz V A Drive overload OE KEYPAD Hz V A Over voltage ntCF KEYPAD Hz V A NTC thermistor sensor fault no Fb KEYPAD Hz V A PID feedback signal error ...

Page 18: ...to stop Wr_F KEYPAD Hz V A Different software version inter copy db KEYPAD Hz V A Over voltage at stop PUF1 KEYPAD Hz V A First time you enter wrong LOC KEYPAD Hz V A Parameter locking PUF2 KEYPAD Hz V A Second time you enter wrong ULOC KEYPAD Hz V A Parameter Password Unlock PUF3 KEYPAD Hz V A Third time you enter wrong dtF KEYPAD Hz V A Direction command error Ht KEYPAD Hz V A Drive overheat PrE...

Reviews: