![Rhosonics SDM Series Manual Download Page 42](http://html1.mh-extra.com/html/rhosonics/sdm-series/sdm-series_manual_1452886042.webp)
SDM – Slurry Density Meter
42
www.rhosonics.com
CONFIGURATION
Setting Low and High value
Open Map Signal condition (Online
Device Setup
Detailed setup
Signal condition)
Set value for PV LRV (i.e. SGx1000 = 800)
Set value for PV URV (i.e. SGx1000 = 1800)
Low and High value 4-20 mA output
Setting Analog output condition
Open Map Signal condition (Online
Device Setup
Detailed setup
Output
condition
Analog output)
Set mode for PV Alrm typ (choose from Hi, Lo, Hold last value or None)
Set Loop current mode to Enabled
Use D/A trim to fine-tune the 4 mA and 20 mA value digitally. After this trim a power down and
power up must be done.
Analog output condition