RHEEM THERMAL AIR SOURCE HEAT PUMP INSTALLATION, MAINTENANCE & SERVICE MANUAL
RHEEM HOT WATER SYSTEM (ASEAN REGION)
10 |
P a g e
SECTION 3: OPERATION
•
The Heat Pump has an internal thermostat located in the return water pipe which maintains
storage tank water temperature at the nominated set point. The normal operating range
for entering water is between 55
°
C and 57
°
C.
•
As water usage occurs, mains water will enter the storage tank, lowering the overall stored
water temperature, which in turn, activates the Heat Pump. The Heat Pump will run until
the water temperature (at the sensing point) reaches set point.
3.1 Thermostat Model (Carel PJEZ Controller)
To check set point, push and hold the “Set” button for 1 second, current set point will be
displayed, push the “up” or “down” arrows to adjust the value. Press “set” to confirm the
value.
a)
Adjusting the differential
or Hysteresis “All parameters” screen must be accessed.
b)
Press and hold “Set” for approx
. 5 seconds, PS will be displayed.
c)
Press “Set” then “Arrow up” till the password value “22” is displayed “PS” will be
displayed
d)
Press “Arrow up” unit parameter “rd” is displayed.
e)
Press “Set” Value will be displayed.
f)
Press “Arrow up” or “Down” to set the desired value.
g)
Press “Set”
h)
Press and hold “Set” for
approx. 5 seconds, until temperature is displayed to save
values.
3.2 Rheem IQ
TM
Model (Intelligent Controller)
Refer to
“
Rheem IQ
Owner’s Guide and Installation
Instructions
”
Manual and/or the
provided Operations and Maintenance Manual for the respective project.
The manufacturer’s detailed full Instructions on the operation of the
controller will be supplied
with the unit and reference may also be made to these instructions.