Rheem RTHW105 Installation Maintenance And Service Manual Download Page 4

 
 
 

RHEEM THERMAL AIR SOURCE HEAT PUMP INSTALLATION, MAINTENANCE & SERVICE MANUAL 

 

 
RHEEM HOT WATER SYSTEM (ASEAN REGION)                                                                     

4 | 

P a g e

 

SECTION 1: INSTALLATION 

 

For validity of warranty, installation must be carried out by registered trade person. 

 

1.1 Installation Guidelines 

 

Heating efficiency and output increases with the rise in entering air temperature, as 

such full advantage should be taken for direct sunlight, typically with evaporator coil 

facing north-west or facing a heat source like boiler room, etc. 

 

Locating the unit close to other system equipment like the pump, tank, etc. will minimize 

friction and heat losses. 

 

Free  circulation  of  air  across  the  coil,  requires  no  obstructions  on  the  intake  or  fan 

discharge  of  Heat  Pumps.  Do  not  position the unit  with  any  intake  side closer than 

1,000mm to adjacent wall, fences, hedges, etc. Ensure that walls, eaves, etc. do not 

obstruct the release of discharge air such that this may recirculate in the incoming air 

stream of the unit. 

 

Service access is required at both ends of the heater. Allow a minimum 850 mm service 

access at the compressor end if possible for units up to 80 kW. For units 100 kW and 

above 1000 mm access at the compressor end is required. 

 

Where multiple heat pumps are to be installed, follow the required minimum clearance 

indicated in the heat pump catalogue. 

 

The Heat Pump requires a concrete slab. Rubber mounts shall be installed between 

the unit and slab. 

 

Local  building  authorities  should  be  consulted  for  regulations  concerning  minimum 

installation distance from pool or other amenities. 

 

Units to be used in areas having highly corrosive atmosphere, must be specified at time 

of ordering. 

 

Consideration should be given to the operating noise, wherever possible the exhaust 

should be directed away from the occupied areas. 

 

To ensure proper drainage of the Heat Pump, make sure that the unit is located at a 

slightly tilted angle with the drain on the downhill side of the unit. This can be done by 

making the concrete slab slightly higher at one end or lifting one end of the unit by 

rubber mounts. 

Summary of Contents for RTHW105

Page 1: ...y read and instructions followed for efficient and trouble free operation of the Rheem Thermal Hot Water Heat Pump Rheem Manufacturing Company Singapore Pte Ltd 8 Pandan Crescent 02 02 Singapore 128464 Tel 68721161 Fax 68721151 Email rheem rheemasia com Website www rheemasia com REV OCTOBER 2019 ...

Page 2: ...uidelines 4 1 2 Plumbing 5 1 3 Electrical 7 1 4 Control Design 7 SECTION 2 COMMISSIONING 9 SECTION 3 OPERATION 10 3 1 Thermostat Model Carel PJEZ Controller 10 3 2 Rheem IQTM Model Intelligent Controller 10 3 3 De Icing 11 SECTION 4 MAINTENANCE 11 SECTION 5 TROUBLESHOOTING 12 5 1 Thermostat Model 12 5 2 Rheem IQTM Model 13 SECTION 6 INSTALLATION SCHEMATIC DRAWING 14 SECTION 7 WARRANTY 14 The End ...

Page 3: ...ient operating conditions water flow water temperature and also due to the wide diversity of commercial and industrial applications selection of the unit should be done in conjunction with an experienced heat pump dealer or the manufacturer In hot water application vessels and reticulation containing the heated water should all be suitably insulated to obtain the optimum performance from the syste...

Page 4: ...e in the incoming air stream of the unit Service access is required at both ends of the heater Allow a minimum 850 mm service access at the compressor end if possible for units up to 80 kW For units 100 kW and above 1000 mm access at the compressor end is required Where multiple heat pumps are to be installed follow the required minimum clearance indicated in the heat pump catalogue The Heat Pump ...

Page 5: ...ons for optimum flow rate Assistance will be provided in relation to optimum plumbing design and pump selection Water connections on the unit are clearly marked as water inlet and water outlet The water lines should be as short as conditions will permit The size of these lines is not necessarily the same as unit connections Breakable unions should be installed on both inlet and outlet pipes to fac...

Page 6: ...y This heat pump should only be connected to a water supply which complies with these guidelines for the Rheem Thermal warranty to apply 1 2 2 Change of Water Supply The changing or alternating from one water supply to another e g a rain water supply bore water supply desalinated water supply public reticulated water supply or water bought in from another supply then water chemistry should be test...

Page 7: ...t to AS3000 latest edition wiring standards Refer to the internal electrical wiring diagram supplied with the units before proceeding with electrical work Cable and fuse sizing must be correct relative to unit specified Volts Hz Phase An isolating switch must be fitted adjacent to the unit up to 80 kW units above 100 kW have a factory installed isolation switch To install the unit remove the elect...

Page 8: ... the desired set point normally with a 2 K split and stop running when the EWT is a set point The heat pump will likewise not run without water flow so there is a very direct link between the heat pump hot water recirculating pump and thermostat controller The thermostat sensor can be located in the hot water tank with control wiring back to the water recirculating pump The operation of the recirc...

Page 9: ...have unrestricted supply of fresh air to the coil and exhaust air removed from closed in areas c The unit should stand on a firm base with fall to take condensate or rain water away from the compressor compartment and to the unit s drainage at the plumbing end d Noise should be directed away from living areas e Water connected correctly as indicated f Condensate drain runs to waste g Unit is wired...

Page 10: ...will be displayed push the up or down arrows to adjust the value Press set to confirm the value a Adjusting the differential or Hysteresis All parameters screen must be accessed b Press and hold Set for approx 5 seconds PS will be displayed c Press Set then Arrow up till the password value 22 is displayed PS will be displayed d Press Arrow up unit parameter rd is displayed e Press Set Value will b...

Page 11: ...Leak test refrigerant system once every 6 months c Check pressure switches de ice control and solenoid valves d Check thermostat or Rheem IQTM controller e Check fan motor support and fan blades f Check condensate drain for blockages g Check water inlet and outlet connections for any leaks h Check current draw with and without load i Check operating voltage at compressor terminal with load without...

Page 12: ... the ejected air temperature is colder than incoming air If so this means the unit is extracting heat from the air and transferring this to water Check that the evaporator and internal pipes sweating This is evidence of heat removal from the air suggesting that the heater is working Check inlet louvres outlet grill and condenser coil has satisfactory airflow and is not clogged Check that thermosta...

Page 13: ...frigerant charge and HP LP operation Possible condenser water flow failure Check condenser pump water entering temperature and flow rate Motor windings faulty Contact manufacturer for replacement 5 1 4 Compressor Motor Hums But Will Not Start Possible Cause Possible Solution Low voltage Provide adequate voltage Wrong motor connections Check with name plate or wiring diagram Tight or seized compres...

Page 14: ...___________________________ SECTION 7 WARRANTY Rheem Manufacturing Company Singapore Pte Ltd undertakes to provide twelve 12 months warranty for Rheem Thermal Heat Pumps only against manufacturing defects during the Defects and Liabilities Period DLP effective upon delivery date subject to be confirmed by your local Rheem distributor In keeping with its policy of continuous progress and product de...