11. Safety devices
Type of
protection
Protection form
Model
ROSH18AXFWJ
ROSH24AXFWJ
Circuit protection
Current fuse (Filter PCB)
250 V, 5 A × 2
Current fuse (Main PCB)
250 V, 3.15 A × 2
Fan motor
protection
Thermal protection
Activate
302
+27
-18
°F (150
+15
-10
°C)
Fan motor stop
Reset
248
+27
-18
°F (120
+15
-10
°C)
Fan motor restart
Compressor
protection
Terminal protection
program
(Compressor temp.)
Activate
226 °F (108 °C)
Compressor stop
Reset
176 °F (80 °C)
Compressor restart
Thermal protection
program
(Discharge temp.)
(COOL or DRY mode)
Activate
230 °F (110 °C)
Compressor stop
Reset
After 7 minutes
Compressor restart
High pressure
protection
Pressure switch
Activate
4.2±0.1 MPa
Compressor stop
Reset
3.2±0.15 MPa
Compressor restart
DESIGN & TECHNICAL MANUAL
- 46 -
OUTDOOR UNIT
ROSH18-24AXFWJ