5) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
Setting value
Setting description
Factory setting
44
00
A
♦
01
B
02
C
03
D
6) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number
Setting value
Setting description
Factory setting
46
00
Operation/Stop mode
♦
01
(Setting prohibited)
02
Forced stop mode
7) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is pos-
sible by setting function setting 30 and 31 too.
Function number
Setting value
Setting description
Factory setting
48
00
Both
♦
01
Wired remote controller
DESIGN & TECHNICAL MANUAL
- 26 -
WALL MOUNTED
RIWH18-24AVFJ