Multiple outdoor unit installation
•
When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only.
When there are obstacles at the front only.
12 (300)
10 (250)
or more
or more
60 (1,500)
or more
10 (250) or more
When there are obstacles at the front and
rear.
20 (500)
or more
60 (1,500)
or more
10 (250) or more
•
When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
60 (1,500) or more
20 (500) or more
10 (250)
or more
10 (250)
or more
Max. 11
(300)
60 (1,500)
or more
- 35 -