- (01 - 29) -
EXTERNAL INPUT & OUTPUT
11.
EXTERNAL INPUT
11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation
Initial setting after power is ON
Starting mode other than initial setting
Operation mode
Auto changeover
Mode at previous operation
Set temperature
76 °F (24 °C)
Temperature at previous operation
Air
fl
ow mode
AUTO
Mode at previous operation
Air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Circuit diagram example
Indoor unit
control PC board
Connected unit
Ex.) Switch
Connector
1
3
Signal
Field supply
*: Make the distance from the PC board to the connected unit within 33 ft. (10 m).
33 ft. (10 m)*
Contact capacity : DC 24 V or more, 10 mA or mor
Use non-polar relays and switches.
When function setting is in "Operation/Stop" mode
●
Operation
Stop
ON
OFF
Input signal
Indoor unit
When function setting is in "Forced stop" mode
●
Remote controller
ON
ON
ON
Input signal
ON
OFF
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control
operation invalidity
Parts (Optional)
Model name
Wire (External input)
Connector
INPUT
OUTPUT
REMARKS
CN102
Control input
—
See external
input/output settings for
details.
CN103
—
Operation status output
CN6
—
Fresh air control output
CN10
—
Auxiliary heater output
Summary of Contents for RIDH09AVFJ
Page 2: ...1 INDOOR UNIT DUCT TYPE RIDH09AVFJ RIDH12AVFJ RIDH18AVFJ...
Page 12: ...01 09 5 WIRING DIAGRAMS MODELS RIDH09AVFJ RIDH12AVFJ RIDH18AVFJ...
Page 48: ...2 OUTDOOR UNIT SINGLE TYPE ROSH09AFCJ ROSH12AFCJ ROSH18AFCJ...
Page 53: ...02 04 4 WIRING DIAGRAMS MODEL ROSH09AFCJ ROSH12AFCJ...
Page 54: ...02 05 MODEL R O S H 1 8 A F C J...
Page 62: ...02 13 SOUND LEVEL CHECK POINT 8 2 39 3 8in 1m Airflow Microphone Microphone...