28
Furnaces for use on LP gas, the LP
gas supply pressure must be set
between 11.0
(
and 14.0
(
W.C. by
means of the tank or branch supply
regulators. The furnace manifold
pressure should be set at 10
(
W.C. at
the gas control valve. For elevations
up to 8,000 feet, rating plate input
ratings apply. For high altitudes
(elevations 8,000 and over) and for
any necessary major changes in the
gas flow rate the orifice spud must be
changed.
To change orifice spuds:
1. Shut off the manual main gas valve
and remove the gas manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
4. Turn the gas supply back on and
check for proper operation and
manifold pressure.
Check of input is important to prevent
over firing of the furnace beyond its
design-rated input. NEVER SET
INPUT ABOVE THAT SHOWN ON
THE RATING PLATE.
To check furnace input:
1. Make certain that all other gas
appliances are shut off, with the
exception of pilot burners.
2. Start the furnace
3. Time the meter to measure the time
required to burn one cubic foot of
gas.
4. Use Table 4 to determine input rate.
RATING PLATE
ELEVATION
INPUT
BTU/HR
0 TO 7,999 FT.
8,000 FT. AND ABOVE
NATURAL GAS
HEATING VALUE @ 1,000 BTU/FT
3
, SPECIFIC GRAVITY 0.62
MANIFOLD PRESSURE @ 3.5
(
W.C.
45,000
43
45
50,000
42
43
67,500
43
45
75,000
42
43
100,000
42
43
125,000
42
43
150,000
42
43
L.P. GAS
HEATING VALUE @ 2,475 BTU/FT
3
, SPECIFIC GRAVITY 1.52/
MANIFOLD PRESSURE @ 10
(
W.C.
45,000
54
55
50,000
54
55
67,500
54
55
75,000
54
55
100,000
54
55
125,000
54
55
150,000
54
55
ORIFICE SIZING CHART
RATING PLATE
ELEVATION
INPUT
BTU/HR
0 TO 1,999 FT.
2,000 FT. TO 4,500 FT.
NATURAL GAS
HEATING VALUE @ 1,000 BTU/FT
3
, SPECIFIC GRAVITY 0.62
MANIFOLD PRESSURE @ 3.5
(
W.C.
45,000
43
45
50,000
42
43
67,500
43
45
75,000
42
43
100,000
42
43
125,000
42
43
150,000
42
43
L.P. GAS
HEATING VALUE @ 2,475 BTU/FT
3
, SPECIFIC GRAVITY 1.52/
MANIFOLD PRESSURE @ 10
(
W.C.
45,000
54
55
50,000
54
55
67,500
54
55
75,000
54
55
100,000
54
55
125,000
54
55
150,000
54
55
ORIFICE SIZING CHART (CANADA)
Summary of Contents for RGDG
Page 35: ...35 FIGURE 31 FILTER RETAINING RODS SIDE RETURN FIGURE 32 DOWNFLOW FILTER INSTALLATION...
Page 43: ...FIGURE 36 FOR MODELS WITH UTEC 1012 920 OR HONEYWELL S9201E2001 INTEGRATED FURNACE CONTROL 43...
Page 44: ...44 FIGURE 37 FOR MODELS WITH WHITE RODGERS 50A62 101 INTEGRATED FURNACE CONTROL...
Page 45: ...45 FIGURE 38 FOR MODELS WITH UTEC 1012 925 INTEGRATED FURNACE CONTROL...
Page 46: ...46...
Page 47: ...47...
Page 48: ...48 CM 398 Rheem Manufacturing Company Air Conditioning Division Fort Smith Arkansas...