background image

Raypak  strongly  recommends  that  this  manual  be

reviewed  thoroughly  before  installing  your  Hi  Delta

heater  equipped  with  FlexGas.  Raypak  also  recom-

mends  that  the  appropriate  Hi  Delta  Installation  and

Operating  Instruction  manual  (1000.502  for  302C-

902C or 1000.512 for 992C – 2342C) be thoroughly

read before attempting to install these heaters.  Fac-

tory warranty does not apply to heaters that have been

improperly installed or operated. (Refer to the warranty

at  the  back  of  the  standard  Hi  Delta  manuals.)

Installation and service must be performed by a quali-

fied installer, service agency or gas supplier. If, after

reviewing  these  manuals,  you  still  have  questions

which  these  manuals  do  not  answer,  please  contact

the manufacturer or your local Raypak representative.

Thank you for purchasing a Raypak product. We hope

you will be satisfied with the high quality and durability

of our equipment.

Model Identification

The  model  identification  number  and  heater  serial

number are found on the heater rating plate located on

the lower right outside jacket of the heater. The model

number  will  have  the  form  H9  1262CD  or  similar

depending on the heater size and configuration. The

letter(s)  in  the  first  group  of  characters  identifies  the

application  (H  =  Hydronic  Heating,  WH  =  Domestic

Hot Water (DHW), P = Pool). The number which fol-

lows  identifies  the  firing  mode  (1  or  4  =  on-off,  3  =

2-stage, 8 = 3-stage and 9 = 4-stage). 

NOTE: Not all 

these  firing  options  are  available  on  all  heaters.

Refer  to  the  Hi  Delta  manual  for  available  firing

options.  The second group of characters identifies the

size  of  the  heater  (four  numbers  representing  the

approximate MBTUH input), and, where applicable, a

letter,  indicating  the  manufacturing  series.  The  final

character is the letter “D” which designates the heater

as a FlexGas equipped heater.

Ratings and Certifications

Standards:

ANSI Z21.13 · CSA 4.9 - latest edition, Gas-Fired

Hot Water Boilers

CAN 3.1 - latest edition, Industrial and Commer-

cial Gas-Fired Package Boilers

ANSI Z21.56 · CSA 4.7 - latest edition, Gas-Fired

Pool Heaters

ANSI  Z21.10.3  ·  CSA  4.3  -  latest  edition,  Gas

Water Heaters

3

WARNING:

Do not use this heater if any part has

been under water. Immediately call a qualified serv-

ice technician to inspect the heater and to replace

any part of the control system and any gas control

which has been under water.

WARNING:

Should  overheating  occur  or  the  gas

supply valve fail to shut off, do not turn off or discon-

nect the electrical supply to the heater. Instead, shut

off the gas supply at a location external to the heater.

WARNING:

Risk of electrical shock. More than one

disconnect  switch  may  be  required  to  de-energize

the equipment before servicing.

WARNING:

This  FlexGas  heater  is  intended  for

operation  on  Natural  Gas  as  the  primary  fuel.  DO

NOT use this heater on Propane Gas as the primary

fuel.

Model 

Input

(MBTUH)

Pipe Size

(Nat)

Pipe Size

(LP)

302CD

300

1-

1

4

3

4

402CD

399

1-

1

4

3

4

502CD

500

1-

1

4

3

4

652CD

650

1-

1

4

3

4

752CD

750

1-

1

4

1-

1

4

902CD

900

1-

1

4

1-

1

4

992CD

990

2”

1-

1

4

1262CD

1260

2”

1-

1

4

1532CD

1530

2”

1-

1

4

1802CD

1800

2”

1-

1

4

2072CD

2070

2”

1-

1

4

2342CD

2340

2”

1-

1

4

Table 1: FlexGas Specifications

Summary of Contents for Raypak Hi Delta FlexGas 1262CD

Page 1: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the...

Page 2: ...2 Rev 5 reflects the following Changes to updated to C models...

Page 3: ...r to the Hi Delta manual for available firing options The second group of characters identifies the size of the heater four numbers representing the approximate MBTUH input and where applicable a lett...

Page 4: ...gas and 13 0 in WC for propane gas The regulator should be placed a minimum distance of 10 times the pipe diameter upstream of the heater gas controls The heater must be isolated from the gas supply p...

Page 5: ...et taps on propane gas See Fig 5 for gas pressure measure ment locations Bleeds Vents This FlexGas gas train is equipped with an propane gas regulator and low gas pressure switch optional on 302CD 902...

Page 6: ...esult in a fire or explosion Do not use this appliance if any part has been under water immediately call a qualified service technician to inspect the appliance and to replace Initial Start up Tools N...

Page 7: ...ould open in 45 60 seconds 3 If burner does not light on first trial It will retry up to three times 4 Main burner ignition Check manifold gas pres sure at gas valve outlet pressure tap This should re...

Page 8: ...trial It will retry up to three times 9 Main burner ignition Check upper manifold gas pressure 10 If the pressure readings differ by more than 0 1 in WC remove screw cover from the gas pres sure regul...

Page 9: ...9 5 Replace all gas pressure caps 6 Check for gas leaks one more time 7 Restart unit Fig 5 FlexGas Control Panel Fig 6 Wiring Diagram Wiring Diagram...

Page 10: ...10 1 S 2 G 6 G 5 G 4 G 1 S 1 G 1 S 7 G 8 G 1 G 1 C...

Page 11: ...011910F 011910F 011910F 4 G MANUAL GAS VALVE NAT 011945F 011945F 007665F 007665F 5 G MANUAL GAS VALVE PRO 011944F 011945F 011945F 011945F F 8 4 9 1 1 0 F 7 4 9 1 1 0 F 7 4 9 1 1 0 F 6 4 9 1 1 0 E V L...

Page 12: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A www raypak com...