background image

6

Start-up

For Your Safety

This  appliance  has  a  hot  surface  igniter(s).  It  is

equipped with an ignition device(s) which automatical-

ly lights the burners. Do not try to light the burners by

hand.

BEFORE  OPERATING,  smell  all  around  the  appli-

ance  area  for  gas.  Be  sure  to  smell  near  the  floor

because some gas is heavier than air and will settle on

the floor.

WHAT TO DO IF YOU SMELL GAS:

• Do not try to light any appliance.

Do not touch any electrical switch; do not use any

telephone in your building.

Immediately call your gas supplier from a neigh-

bor’s  telephone.  Follow  the  gas  supplier’s

instructions.

If you cannot reach your gas supplier, call the fire

department.

Use only your hand to push in or turn the gas con-

trol knob. Never use tools. If the knob will not turn

by hand, do not try to repair it, call a qualified serv-

ice  technician.  Forced  or  attempted  repair  may

result in a fire or explosion.

Do  not  use  this  appliance  if  any  part  has  been

under  water,  immediately  call  a  qualified  service

technician to inspect the appliance and to replace

Initial Start-up

Tools Needed:

(1) 12-0-12, 24” scale U-tube manometer

(4) 6-0-6, 12” scale U-tube manometers (min.)

(1) Screwdriver

(1) Multi-meter

(1) 3/16” Allen wrench

WARNING:

If you do not follow these instructions

exactly, a fire or explosion may result causing prop-

erty damage, personal injury or loss of life.

NOTE:

Digital manometers are not recommended.

any part of the control system and any gas control

which has been under water.

Check around unit for debris and remove combus-

tible products, i.e. gasoline, etc.

Pre Start-up Check

1. Verify heater is filled with water.

2. Check  system  piping  for  leaks.  If  found,  repair

immediately.

3. Vent air from system. Air in system can interfere

with water circulation.

4. Purge air from gas lines up to FlexGas gas train.

Propane Supply Pressure
Test Point

Models: 302CD-902CD

Models: 992CD-

2342CD

Gas Valve

Output Tap

Fig. 4: FlexGas Gas Pressure Measurement Locations

Summary of Contents for Raypak Hi Delta FlexGas 1262CD

Page 1: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the...

Page 2: ...2 Rev 5 reflects the following Changes to updated to C models...

Page 3: ...r to the Hi Delta manual for available firing options The second group of characters identifies the size of the heater four numbers representing the approximate MBTUH input and where applicable a lett...

Page 4: ...gas and 13 0 in WC for propane gas The regulator should be placed a minimum distance of 10 times the pipe diameter upstream of the heater gas controls The heater must be isolated from the gas supply p...

Page 5: ...et taps on propane gas See Fig 5 for gas pressure measure ment locations Bleeds Vents This FlexGas gas train is equipped with an propane gas regulator and low gas pressure switch optional on 302CD 902...

Page 6: ...esult in a fire or explosion Do not use this appliance if any part has been under water immediately call a qualified service technician to inspect the appliance and to replace Initial Start up Tools N...

Page 7: ...ould open in 45 60 seconds 3 If burner does not light on first trial It will retry up to three times 4 Main burner ignition Check manifold gas pres sure at gas valve outlet pressure tap This should re...

Page 8: ...trial It will retry up to three times 9 Main burner ignition Check upper manifold gas pressure 10 If the pressure readings differ by more than 0 1 in WC remove screw cover from the gas pres sure regul...

Page 9: ...9 5 Replace all gas pressure caps 6 Check for gas leaks one more time 7 Restart unit Fig 5 FlexGas Control Panel Fig 6 Wiring Diagram Wiring Diagram...

Page 10: ...10 1 S 2 G 6 G 5 G 4 G 1 S 1 G 1 S 7 G 8 G 1 G 1 C...

Page 11: ...011910F 011910F 011910F 4 G MANUAL GAS VALVE NAT 011945F 011945F 007665F 007665F 5 G MANUAL GAS VALVE PRO 011944F 011945F 011945F 011945F F 8 4 9 1 1 0 F 7 4 9 1 1 0 F 7 4 9 1 1 0 F 6 4 9 1 1 0 E V L...

Page 12: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A www raypak com...

Reviews: