background image

Page 12 

SECTION V: MAINTENANCE

WaTer pIpIng

On an annual basis, all piping should be checked for leakage at joints, shut-off valves, and 
unions.

T&p relIef valve

On an annual basis, the temperature and pressure relief valve should be checked for proper 
operation.  First, attach a drain line to the valve to direct the water discharge to an open drain.  
This is very important because the temperature of the discharge could be very hot.  Second, lift 
the lever at the end of the valve several times.  The valve should operate freely and return to its 
original position properly.  If water does not flow out of the valve, remove and inspect for 
corrosion or obstructions.  Replace with a new valve if necessary.  Do not repair the faulty valve 
as this may cause improper operation.

anode rods

Anode rods should be inspected twice in the first year and at least yearly once a time interval for 
inspection has been developed.  It is recommended to check the rod(s) six months after the 
heater is installed.  If the anode rod had reduced in size by two-thirds of its original diameter of 
3/4” or shows signs of pitting, it is time for replacement.  Take the following steps when changing 
the anode rod(s):

1. Shut off water supply.

2. Open any faucet to relieve tank pressure.

3. Remove caps on indirect water heater top; push insulation aside.

4. Use a 1 1/16” six-sided socket wrench and a breaker bar.  Snap hard to break the anode  
rod seal.

5. Remove rod(s) and replace with new rod(s). 

6. Turn water supply back on and leave faucet open until air is out of line.

7. Turn faucet off and check that new rod(s) doesn’t leak.

8. Snap caps back into place.

flusH THe Tank

The indirect water heater is glass lined.  Elements in the water such as lime, iron and other 
minerals may accumulate in the heater.  It is recommended that the tank be drained and flushed 
thoroughly once a year to prevent buildup in the tank.

Summary of Contents for Indirect Water Heater

Page 1: ...g the indirect water heater into service This unit must be installed by licensed or authorized installers or technical personnel that service water heating equipment The indirect water heater must be...

Page 2: ...Section I Specifications 3 Section II General Informations 5 Section III Pre Installation 7 Section IV Installation 9 Section V Maintenance 12 Section VI Troubleshooting 13 Section VII Parts List 14...

Page 3: ...erature setting for normal residential use is 120 F Rheem recommends a tempering valve or anti scald valve be installed and used according to the manufacturer s directions to prevent scalding STID30 2...

Page 4: ...000 202 104 000 214 111 000 STID80 188 76 000 212 91 000 224 98 000 221 97 000 233 104 000 245 112 000 257 119 000 STID120 220 76 000 244 91 000 256 98 000 253 97 000 265 104 000 277 112 000 289 119 0...

Page 5: ...ited control for domestic hot water temperature The proper temperature setting for domestic hot water use is 120 F 49 C If hotter water is required a tempering device or anti scald device must be inst...

Page 6: ...ter system When hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet a...

Page 7: ...F and 200 F boiler water To determine the appropriate circulator for your system follow these three steps 1 Calculate the pressure drop of all straight pipe and fittings on the supply and return at th...

Page 8: ...imum coil output assume coil output boiler output listed in Tables 2 and 3 is not met the output first hour rating of the indirect water heater will not be met at the selected flow rate To approximate...

Page 9: ...minimized A flow check valve must be installed on the return line All piping to the inlet cold and outlet hot domestic water connections should be new copper with a minimum size of 1 2 ID for models S...

Page 10: ...tion cont CHECK VALVES ZONE CIRCULATORS ISOLATION VALVES ADDITIONAL ZONES INDIRECT CIRCULATOR INDIRECT WATER HEATER TO HEATING ZONE AIR SEPARATOR AIR VENT EXPANSION TANK COLD WATER INLET BOILER CIRCUL...

Page 11: ...m circulator stays off and the boiler must light to reach high limit WIRING NOTES 1 Dashed lines indicate low voltage 24 VAC 2 Use jumper wire between terminals 1 and 3 on R845 relay THERMOSTAT SPECIF...

Page 12: ...nd at least yearly once a time interval for inspection has been developed It is recommended to check the rod s six months after the heater is installed If the anode rod had reduced in size by two thir...

Page 13: ...HFN SRZHU VXSSO 5HSODFH DV QHFHVVDU DXOW WDQN DTXDVWDW 5HSODFH DTXDVWDW RLOHU F FOHV PRUH WKDQ WLPHV SHU GD GXULQJ KRWHVW PRQWKV FHVVLYH GHPDQG 5HGXFH GHPDQG RU FRQVLGHU ODUJHU WDQN DXOW DTXDVWDW 5HSO...

Page 14: ...n VIi parts list No Description Applicable Models 1 Anode All models 2 Anode Outlet STID 30 STID 40 STID 50 3 T P Relief Valve All models 4 Drain Valve All models 5 Aquastat All models Page 14 14 2 1...

Page 15: ...nt component part s to a convenient delivery point selected by Rheem near the place the original water heater or original component part s is located such as a local Rheem water heater retailer You mu...

Page 16: ...rranty in the event warranty service is needed Reasonable proof of the date of original installation or date of original purchase of your water heater whichever came first may be required to establish...

Reviews: