10.0 DIAGNOSTICS & TROUBLESHOOTING
10.7 Service Analyzer Chart (cont.)
Diagnostics
CONTAMINATION
SYMPTOM
POSSIBLE CAUSE
CHECK/REMEDY
Moisture
Poor evacuation on installation or during service
In each case, the cure is the same. Recover re
-
frigerant. Add filter drier, evacuate and recharge
High head pressure
Noncondensibles air
Unusual head and
suction readings
Wrong refrigerant or mixed refrigerants
Foreign matter - copper
filings
Copper tubing cuttings
Copper oxide
Dirty copper piping or nitrogen not used when brazing
Welding scale
Nitrogen not used during brazing
Soldering flux
Adding flux before seating copper partway
Excess soft solder
Wrong solder material
LOSS OF LUBRICATION
SYMPTOM
POSSIBLE CAUSE
CHECK/REMEDY
Compressor failures
Line tubing too large
Reduce pipe size to improve oil return
Low suction pressure
Low charge
Check system charge
Refrigerant leaks
Repair and recharge
Cold, noisy compressor
- Slugging
Dilution of oil with refrigerant
Observe piping guidelines
Noisy compressor
Migration
Check crankcase heater
Cold, sweating com
-
pressor
Flooding
Check system charge
Low load
Reduced airflow
Dirty filter
Dirty coil
Wrong duct size
Restricted duct
Thermostat setting
Advise customer
Short cycling of com
-
pressor
Cycling or faulty high or low-pressure control
Check pressures and address cause of any
abnormal pressure. Replace control if faulty
Loose wiring
Check all control wires
Thermostat
In supply air stream, out of calibration
Customer misuse
SLUGGING
SYMPTOM
POSSIBLE CAUSE
CHECK/REMEDY
On start-up
Incorrect piping
Review pipe size guidelines
TXV hunting when
running
Fault TXV
Replace TXV