4.9 Control Wiring (cont.)
4.10 Power Wiring
TYPICAL 2-STAGE THERMOSTAT: AIR CONDITIONER
WITH ELECTRIC HEAT
W1
W2
Y1
Y2
R
C
G
ODD
Y1 Y2 G
W2 C
R DHM
Y1
Y2
R
C
W/BK
W/BL
Y
Y/BL
R
BR
Y
Y/BL
R
BR
G
W1
Typical Two-Stage Thermostat with Dehumidification
Outdoor Unit
Air Handler
Field-Installed
Factory Standard
TYPICAL 2-STAGE THERMOSTAT: AIR CONDITIONER
WITH ELECTRIC HEAT USING A HUMIDISTAT FOR
DEHUMIDIFICATION
W1
W2
Y1
Y2
R
C
G
ODD
Y1 Y2 G W1 W2 C
R
Y1
Y2
R
C
W/BK
W/BL
Y
Y/BL
R
BR
Y
Y/BL
R
BR
G
Typical Two-Stage Thermostat
Outdoor Unit
Air Handler
Field-Installed
Factory Standard
Humidistat
TYPICAL 2-STAGE THERMOSTAT: AIR CONDITIONER
AND FURNACE
R
C
W1
W/E
Y1
Y2
G
R
C
Y1
Y2
R
C
W1
Y1
Y2
G
W2
W2
R
BR
Y
Y/BL
Typical
Two-Stage
Thermostat
Furnace
Control
Field wiring must comply with the National Electric
Code (C.E.C. in Canada) and any applicable local
code.
Wiring
** ODD non-functional on (-)H2T air-handlers
** ODD non-functional on (-)H2T air-handlers
4.10 Power Wiring
It is important that proper electrical power from a
commercial utility is available at the outdoor unit
contactor. Voltage ranges for operation are shown below.
VOLTAGE RANGES (60 HZ)
Install a branch circuit disconnect within sight of the
unit and of adequate size to handle the minimum circuit
capacity (see Section 3.2).
Power wiring must be run in a rain-tight conduit. Conduit
must be attached to the hole in the bottom of the control
box as shown below.
Connect power wiring to line-voltage lugs on the
contactor located in the outdoor unit electrical box. (See
wiring diagram attached to unit access panel and above
illustration.)
Check all electrical connections, including factory wiring
within the unit and make sure all connections are tight.
DO NOT
connect aluminum field wire to the contactor
terminals.
Operating Voltage Range at Maximum
Nameplate Voltage
Load Design Conditions for Compressors
Copeland
208/230 (1 Phase)
187 - 253
208/230 (3 Phase)
187 - 253
460
414 - 506
575
517 633
Outdoor
Unit
4.0 INSTALLATION
Contactor
ST-A1226-09