10.0 DIAGNOSTICS AND TROUBLESHOOTING
10.7 Service Analyzer Chart (cont.)
Diagnostics
COMPRESSOR OVERHEATING (Cont.)
SYMPTOM
POSSIBLE CAUSE
CHECK OR REMEDIES
Short cycling of
compressor (cont.)
Distributor tube
Restricted with foreign matter
Kinked
I.D. reduced from previous compressor failure
Low charge
Check system charge
Low evaporator airflow
Dirty coil
Dirty filter
Duct too small or restricted
Faulty run capacitor
Replace capacitor
Faulty internal overload
Replace compressor
Faulty compressor
Fast equalization/Low pressure difference
Replace compressor and examine system to locate
reason
ELECTRICAL
SYMPTOM
POSSIBLE CAUSE
CHECK OR REMEDIES
Voltage present on
load side of com
-
pressor contactor
and compressor
won’t run
Compressor starts components
Check start capacitor
Check potential relay
Run capacitor
Check with ohmmeter
Internal overload
Allow time to rest
Compressor windings
Check for correct ohms
Voltage present on
line side of com
-
pressor contactor
only
Thermostat
Check for control voltage to contactor coil
Compressor control circuit
High-pressure switch
Low-pressure switch
Ambient thermostat
Solid-state protection control or internal thermal sensor
Compressor timed off/on control or interlock
No voltage on line
side of compressor
contactor
Blown fuses or tripped circuit breaker
Check for short in wiring or unit
Improper wiring
Recheck wiring diagram
Improper voltage
High voltage
Wrong unit
Power supply problem
Low voltage
Wrong unit
Power supply problem
Wiring undersized
Loose connections
FLOODED STARTS
SYMPTOM
POSSIBLE CAUSE
CHECK OR REMEDIES
Liquid in the com
-
pressor shell
Faulty or missing crankcase heater
Replace crankcase heater
Too much liquid in
system
Incorrect piping
Check piping guidelines
Overcharge
Check and adjust charge