background image

51

Dia

gn

ost

ics

FIGURE 33

DIAGNOSTICS FLOWCHART

GO TO

E

NOTE: Always verify gas valve inlet and outlet gas pressure.

KEY TO ABBREVIATIONS

IBM  = Indoor  Blower  Motor

IDM  = Induced  Draft  Motor

IFC = Integrated  Furnace  Control

PS = Pressure  Switch(es)

SE = Spark  Electrode

DSI = Direct-Spark  Ignition

FLAME  (AMBER)  LED CODES

OFF = No Flame Present

RAPID  BLINK  = Unexpected  Flame

SLOW  BLINK  = Marginal  Flame Sense

STEADY ON = Normal  Flame Sense

Does  the  IDM  Energize?

IDM  Runs  for  30  sec. pre-purge ?

Spark Ignitor Sparking? 

Does  Main  Burner  Light  and stay  lit?

Is  the gas valve  energized?

PS dropping  out ?

Check IFC*

Does  IBM  start  on  heat speed  20  seconds

after  burners  light ?

Does  main  burner  remain  lit  until

heat call  ends?

Does  thermostat  maintain  reasonable  room

temperature  near setpoint ?

Set thermostat  to  off  position  (W  to  C = ØV)

Does  gas valve  shut  off  immediately?

Does  IDM  shut  off  after  ten  second  post-purge?

Does  IBM  shut  off  after  a max.  of  3 min?

END

Heat-mode  troubleshootin g

“FAULT DISPLAYED ?” 

24V  on  W to  IFC?

Check IFC*.

Does  IDM  run

indefinately .

Does  IDM  Run  for  60  sec. and then  off  for  Five minutes

- Check thermostat  in  “heat”  mode,

battery, wire,  and connections.

- Check PS contact s

- Check wires  for  short.

- Check IFC*.

- Check switches  and hoses  for

water  or  moistur e

- Check PS, PS Hoses,  and wires.

- Check for  blocked  vent,  excessive  vent  length  or  elbows,  or

blocked  heat exchanger .

- Check IDM  wired  correctly .

- Ensure  against  excessive  wind,  which  can open  pressure  switch.

- Check for  intermittent  P.S. operation.

- Check switches  and hoses  for  water  or  moisture.

- Check gas supply  and manifold  pressure.

- Ensure  L1  and Neutral  not  swapped  on  IFC and junction  box.

- Check igniter  alignment .

- Check orifice  or  other  restrictions  to  gas flo w.

- Check flame  sense  rod  (clean  with  scotch brite pad).

- Check  flame  carry over.

- Check wires,  continuity , and connection  between  IFC and gas valve.

- Ensure  24  V between  appropriate  pins  on  connector  of  IFC.

- Ensure  manual  switch  on  valve  is in  the  “ON”  position.

- 90+  check  aux.  limit  open?  Should  be closed

- 90+  upflow  models  – check  drain  pressure  switch  between  IFC and

gas valve  – should  be closed  – replace  drain  pressure  switch  if  drai n

is not  blocked  or  clear  drain  if  blocked.

- Did  a pressure  switch  open  during  ignition  trial?  If  yes, go  to  F
- Did  a limit  open  during  ignition  trial?  If  yes, go  to  D

- Check line  voltage  between  “HEAT”  and “NEUTRAL”  on  IFC.

- Check wires,  connections,  and continuity  between  IFC and IBM.

- Check IBM  capacitor .

- Check IBM.

CHECK:

- grounding  on  IFC and unit.

- check  for  proper  polarity  between  L1  &  neutral.

- flame  sense  rod  (clean  if  necessar y).

- wire  continually  between  flame  sense  rod  and appropriate  pin  of

connector  on  IFC

- flame  carries  across  all burners,  and all burners  stay  lit.

CHECK:

AIRFLOW - ensure  no  restrictions,  such  as dirty  filte r, dampers,  closed  registers,  etc.

LIMITS - ensure  good  wire  and connections  between  IFC and all limits.  Make  sur e

limits  are not  open  when  circulating  air  temperature  is within  a specified  range.

ROLLOUTS - ensure  rollouts  or  overtemperature  limits  do  not  need to  be reset.  Make

sure  no  flame  rollout  in  burner  compartment  due to  blocked  flu  or  heat exchanger .

OVERFIRE - ensure  furnace  is not  overtemperature  (temp  rise  is above  stated  range) .

Check gas valve,  proper  orifice  size, gas pressure,  etc.

Is  Limit  circuit  open  or opening  and closing?

Note:  IFC Status  LED should  be blinking  a Fault Code. 

Is the IFC sensing a good flame: NOTE:

Flame sense light should be steady-on

when burners are lit. If flame LED blinking,

or off, flame sense is low or absent.

Ensure  thermostat  is properly  placed  and not  improperly  affected  by

registers,  fans,  sunlight,  heat through  walls,  pipes,  or  wires  in  walls .

- Check heat anticipator  setting.  Furnace  may  need an isolation  relay.

- Check installation  instructions  under  section  titled  “Isolation  Relay”  for

details .

- Verify  correct  furnace  sizing.

NOTE: If  IFC goes  into  lockout  (“ST ATUS LED will  blink  code  “1”),  shut

off  main  power  to  unit,  wait  30  seconds  and then  reset  power .

PROBLEM

STILL

PRESENT

Fault Code Present

“FLAME”  LED BLINKING

OR STEADY ON

If  “E”  did  not

resolve  issue

Double  check  - Is  W off  at IFC?

(W  to  C = ØV?)

Voltage  present  at gas valve?

- Check gas valve.

SEE FAULT CODES

- Check IFC*.

Check IFC*.

*Most  failures  are not  due to  the  IFC. Doubl e

check  all other  possibilities,  including  the

ground  connection  or  wire  connections,  before

replacing  the IFC.

Ensure  TSTAT is not  in  “FAN”  position.

Is disply flashing a fault code

Is  “FLAME”  LED blinking  or  steady-on ?

**System  will  attempt  to  light  4 times.  Voltage

is present  at gas valve  for  only  7 seconds  dur -

ing  each trial  for  ignition.  The entire  system  will

go  into  a 1 hour  lockout  after  4 attempts. 

- Check line  voltage  at IDM.

- Check wires  and connections  between  IDM  and IFC.

- Ensure  line  voltage  on  IDM  pins  of  IFC connector .

- Check IDM  capacitor  (90+  only) .

CHECK BLINK  CODES

- Check for  open  limit  or  limit  circuit.

FOR DIRECT SPARK IGNITION 

- Check ignitor  connected .

- Check ignitor  wires.

- Check ignitor  for  fractures  or  cracking

- Check ignitor  placement .

- If  problem  persists,  check  IFC*.

REPEAT THIS PROCEDURE UNTIL  TROUBLE-FREE OPERATION IS OBTAINED.

1) Set FAN switch  to  “AUTO”

2) Set thermostat  to  call  for  low HT ( “W” terminal)  

START

YES

NO

NO

If  “I ”  did  not

resolve  issue.

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

I

D

F

E

G

YES

NO

YES

PREPURGE

IGNITION  TRIAL

IBM  “ON”  DELAY

STEADY STATE LOW HT 

END HEAT CALL

POST-PURGE

IBM  “OFF”  DELAY

STEADY OFF

NO

**

ST-A1227-08-00

GO TO

F

GO TO

I

W

A

R

N

IN

G

H

A

ZA

R

D

O

U

S

 V

O

LT

A

G

E

LI

N

E

 V

O

LT

A

G

E

C

O

N

N

E

C

TI

O

N

S

D

IS

C

O

N

N

E

C

P

O

W

E

R

 B

E

FO

R

E

 S

E

R

V

IC

IN

G

.

S

E

R

V

IC

E

 M

U

S

B

E

 B

Y

 A

 T

R

A

IN

E

D

Q

U

A

LI

FI

E

D

S

E

R

V

IC

E

 T

E

C

H

N

IC

IA

N

.

N

O

TE

:A

lw

ay

ve

rif

ga

va

lv

in

le

an

ou

tle

ga

pr

es

su

re

.

IN

TE

G

R

A

TE

D

 F

U

R

N

A

C

E

 C

O

N

TR

O

(IF

C

)

D

IA

G

N

O

S

TI

C

S

G

U

ID

E

N

O

TE

: M

os

fa

ilu

re

ar

no

du

to

 t

he

 I

FC

D

ou

bl

ch

ec

al

ot

he

r

po

ss

ib

ili

tie

s,

 

in

cl

ud

in

th

gr

ou

nd

 

co

nn

ec

tio

n,

 

be

fo

re

 

re

pl

ac

in

th

IF

C

.

 

 

 

BLOCKED DRAIN - (fault “59” should be present)

Set T-stat to High Heat - Energize W2 + W

Fault

Priority

24
22
21
19
23
13
15
14
16

2

20

4

17

3
6
9
8
7

11
18

CODE

DESCRIPTION

O
C
H

h
F

10
11
12
13
14
20
22
26
33
44
46
45
55
57
61
93

Standby
Compressor on (cooling or heat pump heat)
High Gas heat on
Low gas heat on
Continuous fan on
1 Hour lockout
Failed ignition
Low flame sense
Flame lost
Unexpected flame
Twinning fault
Main limit open
Line and Neutral reversed
MRLC(Man. Reset limit cont.)(aka roll-out) open
Low Pres. Switch Closed
Low Pres. Switch Open, Indcr on low Speed
Low Pres. Switch Open, Indcr on High Speed
High Pres. Switch Closed
High Pres. Switch Open
Blower Fault - blower unable to run
Internal control fault 

“ATTEND TO FAULT” 

- For Twinned  units,  check  that  both  IFCs are set for  “TWIN”  and wire s

are connected  between  “TWIN”  terminals .

- Check IFC*.

- For twinned  units,  ensure  transformers  are in  phase.

(if  out  of  phase,  flame  LED will  be dim) .

- For non-twinned  units,  ensure  “TWIN”  is in  the  single  (OFF) position.

- For Twinned  units  – ensure  both  IFC‘s have same  part  number .

H

Check for high gas valve relay 

on IFC stuck closed. Replace 

IFC, if neccessary

Do IDM, IBM & Gas Valve Shift to High Heat?

STEADY HIGH HEAT 

CHECK:

    -IDM

    -IDM Capacitor

    -Low Pres. Sw. wiring

    -Hoses to Low Pres. Sw. 

CHECK:

    -IBM

    -IBM Capacitor

    -Wiring

    -Flame Sense Rod 

Low Pressure 
Switch Open?

High Gas Valve 

Energized?

24 VAC on

W2?

Check

T- STAT

NO

NO

NO

NO

YES

YES

YES

YES

YES

Restore thermostat to

normal operation.

Summary of Contents for (-)(-)80MDP050A30SA

Page 1: ...IZONTAL SERIES U L and or C S A recognized fuel gas and CO carbon monoxide detectors are rec ommended in all applications and their installation should be in accordance with the manufacturer s recomme...

Page 2: ...30 Humidifier 30 Filter 30 RXGW B01 Chimney Adapter 30 Four Inch Flue Adapter 30 11 TWINNING 32 Furnace Twinning Installations 32 Control Boards 33 35 12 HIGH ALTITUDE 36 Natural Gas at High Altitudes...

Page 3: ...r is correct open the carton and verify that the furnace rating label specifies the same furnace model number that is speci fied on the carton label If the model numbers do not match re turn the furna...

Page 4: ...hese publications are ANSI NFPA No 70 Latest Edition National Electrical Code NFPA90A Installation of Air Conditioning and Ventilating Sys tems NFPA90B Installation of warm air heating and air conditi...

Page 5: ...erature rise in heat record air temperature rise ______ Air temperature rise in cool record air temperature rise VENTING ______ Correct vent pipe diameter and length according to NFGC tables _________...

Page 6: ...IF THE FURNACE IS A MULTI STAGE FURNACE WARNING USE ONLY WITH THE TYPE OF GAS APPROVED FOR THIS FURNACE REFER TO THE FURNACE RATING PLATE WARNING NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE A COMM...

Page 7: ...AS ALL JOINTS SEAMS AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS IN CLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE IF AIR MOVING...

Page 8: ...SITE SELECTION 1 Select a site in the building near the center of the pro posed or existing duct system 2 Give consideration to the vent system piping when se lecting the furnace location Be sure the...

Page 9: ...PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROP ERTY DAMAGE PERSONAL INJURY OR DEATH THE HOMEOWNER SHOULD BE CAUTIONED THAT...

Page 10: ...lbs MAY REQUIRE 3 TO 4 OR 3 TO 5 ADAPTER 4 ADAPTER INCLUDED WITH 801P UNITS MAY BE 0 WITH TYPE B VENT MAY BE 1 WITH TYPE B VENT LEFT SIDE REDUCED CLEARANCE IN SHIP WGTS FIGURE 4 UPFLOW HORIZONTAL DIME...

Page 11: ...Where the maximum airflow is 1800 CFM or more BOTH sides or the bottom must be used for the return air Do not take return air from the back of the unit NOTE DO NOT take return air from furnace rooms g...

Page 12: ...M FLANGES OF CABINET BEFORE THE UNIT IS INSTALLED LIFT UP PULL OUT 1 REMOVE 2 SCREWS LIFT BASE UP SLIDE FORWARD TO REMOVE 2 INSTALLATION IS REVERSE OF REMOVAL VERIFY REAR FLANGE IS SEALED PROPERLY AS...

Page 13: ...ustion gases from an adjacent fuel burning appliance NOTE Do not block furnace access with support rods Main tain clearances recommended in Figure 8 Allow enough space for proper service maintenance o...

Page 14: ...of all appliances in the space If the open space contain ing the appliances is in a building with tight construction contem porary construction outside air may still be required for the appliances to...

Page 15: ...inch of free area for each 1 000 BTUH of total input in the space Table 2 shows some typical examples of openings required for com bustion air openings required for a confined space B USING OUTDOOR AI...

Page 16: ...EACH OPENING WHEN TWO OPENINGS ARE USED WITH A FURNACE 1 LOCATED IN A CONFINED SPACE 2 USING OUTDOOR AIR FOR COMBUSTION 3 COMMUNICATING DIRECTLY TO THE 3 OUTSIDE THROUGH AN OPENING OR 3 THROUGH A VERT...

Page 17: ...S IS NOT A REQUIREMENT SEE PREVIOUS PAGE SINGLE ELBOW IS ALLOWED BUT MAY NOT PREVENT DEBRIS FROM BEING DROPPED INTO THE FURNACE GROUND OR SHELF SURFACE 6 MIN 6 MININUM CLEARANCE PVC DOUBLE ELBOW 8 SCR...

Page 18: ...attic must be ventilated by gable or soffit vents COMBUSTION AIR FROM ATTIC If attic combustion air is used the inlet air opening at the furnace must be protected from accidental blockage Install a 9...

Page 19: ...and or the Natural Gas Installation Code CSA B149 1 2 for proper installation practices NOTE Follow combustion air instructions as outlined in this man ual Single wall vent connectors to B 1 vent or m...

Page 20: ...not be greater than 75 percent of the vertical height of the vent Single appliance venting of a fan assisted furnace into a tile lined masonry chimney is prohibited The chimney must be lined with eith...

Page 21: ...R cont FIGURE 18 DEDICATED VENTING THROUGH CHIMNEY WITH B 1 VENT Combustion Air FIGURE 17 FRESH AIR INLET ST A1220 09 01 1 STANDARD 3 FLUE CONNECTION 2 4 ADAPTER OPTIONAL SEE NATIONAL FUEL GAS CODE FO...

Page 22: ...venting system NOTE Ensure existing venting system complies with latest addi tion of National Fuel Gas Code ANSI Z223 1 and all local codes regulations 1 Visually inspect the venting system for prope...

Page 23: ...N AIR AND TENDS TO COLLECT AT LOWER LEVELS MAKING IT MORE DIFFICULT TO SMELL AT NOSE LEVEL NATURAL GAS IS LIGHTER THAN AIR AND WILL RISE POSSIBLY ACCUMULATING IN HIGHER PORTIONS OF THE STRUCTURE IF A...

Page 24: ...3 feet to easily remove the control valve assembly Install a manual shut off valve in the gas line outside the furnace cas ing The valve should be readily accessible to turn the gas supply on or off I...

Page 25: ...TION TITLED HIGH ALTITUDE INSTALLATIONS OF THIS BOOK FOR INSTRUCTIONS WARNING NEVER PURGE A GAS LINE INTO THE COMBUS TION CHAMBER NEVER USE MATCHES FLAME OR ANY IGNITION SOURCE FOR CHECKING LEAK AGE F...

Page 26: ...With LP gas have the LP supplier adjust the line pressure at the regulator Manifold Gas Pressure Measurement Natural gas manifold pressure should be 3 5 w c for high fire and 1 8 w c for low fire LP g...

Page 27: ...r and the gas supply to the furnace 2 Remove the burner door from the furnace 3 Remove the burner assembly handle with care 4 Remove the two screws attaching the NOx insert retainer bracket to the cen...

Page 28: ...lly connected to line volt age prior to reversing the electrical connection 2 Disconnect the wires from the door switch 3 Remove the junction box from the furnace cabinet wall by re moving the two scr...

Page 29: ...d be sized as shown NOTE Do not use 24 volt control wiring smaller than No 18 AWG Install the room thermostat in accordance with the instruction sheet packed in the box with the thermostat Run the the...

Page 30: ...ach option humidifier or electronic air cleaner RXGW C01 4 INCH FLUE ADAPTER See Figure 26 Refer to Venting section of this manual for more information See National Fuel Gas Code for sizing options FI...

Page 31: ...HE FURNCE AT THE LOCATIONS PROVIDED CUT OUT USING EMBOSSED ANGLES AS A GUIDE FOR PROPER SIZE 23 X 14 ST A1220 07 00 RXGF CB 6625 7 5 5 FIELD SUPPLIED FILTER ST A1220 06 X0 FIGURE 26 FILTER LOCATIONS A...

Page 32: ...be adequate to provide correct airflow to each furnace for supply and return UT ELECTRONIC CONTROLS 1095 300 CONTROL BOARD 62 104059 01 1 Single Stage Operation a Control board ONE is on furnace conn...

Page 33: ...33 TWINNING CONTROL BOARDS Twinning FIGURE 27 UT ELECTRONIC CONTROLS 1095 300 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION ST A1205 05 X0...

Page 34: ...34 TWINNING CONTROL BOARDS cont Twinning FIGURE 28 UT ELECTRONIC CONTROLS 1095 300 CONTROL BOARD TWINNING CONNECTION ONE STAGE THERMOSTAT TIMED STAGING GAS HEAT OPERATION ST A1205 06 X0...

Page 35: ...35 TWINNING CONTROL BOARDS cont Accessories FIGURE 29 UT ELECTRONIC CONTROLS 1095 300 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION ST A1205 07 X0...

Page 36: ...Sea Level Heating Value 1050 Q 23 81 ft3 Natural Gas per hour From Table F 1 of Natural Fuel Gas Code Handbook 2002 3 5 w c column Orifice required at Sea Level 43 From Table F 4 of National Fuel Gas...

Page 37: ...90 FURNACE MODEL NATURAL GAS ORIFICE SELECTION BASED ON HEATING VALUE ELEVATION Table is derived from Appendix of the National Fuel Gas Code To determine the correct orifice for your installation con...

Page 38: ...e LP orifices are based on an 11 of water column pressure at the orifice which dif fers from products that use 10 of water column at the orifice This difference requires a deviation from the NFGC orif...

Page 39: ...spark igniter is energized to light the gas burners and stays energized for the up to 7 seconds after the gas valve opens 5 8 seconds after the gas valve opens the remote flame sen sor must prove fla...

Page 40: ...times in a row the control enters one hour lockout and fault codes 10 and 11 will be displayed alternately as described above 2 When flame is lost five times in a row the control enters one hour lock...

Page 41: ...our period will commence after flame is no longer detected Dead Blower has been detected main limit circuit open for more than 150 seconds When voltage has unexpectedly been detected on the gas valve...

Page 42: ...display orientation is with the control placed in a vertical orientation and the low voltage terminal block T2 is on the left Cool Blower Off Delay SW2 SW3 A means of selecting the cooling speed blowe...

Page 43: ...r amber L E D is provided to indicate flame sta tus When normal flame is sensed the flame L E D is con tinuously on The flame L E D will flash at a rate of one to four flashes per second if a weak fla...

Page 44: ...pressure Then replace the regulator cap securely Any necessary major changes in the gas flow rate should be made by changing the size of the burner orifices To change orifice spuds shut off the manual...

Page 45: ...local gas utility to obtain the yearly average heating value and orifice size required to fire each individual burner at 25 000 BTU HR NOTE Refer to the High Altitude Section of this manual and the Na...

Page 46: ...re needs to be adjusted Use lower speed tap on the multi speed blower IMPORTANT The measured temperature rise should be in the middle of the range IMPORTANT Some high efficiency filters have a greater...

Page 47: ...050314MSA 80MDP050A30SA 1 3 11 x 6 802PA075417MSA 80MDP075B30SA 802PA100521MSA 80MDP100C40SA 802PA125524MSA 80MDP125D50SA 1 2 11 x 7 1 2 11 x 10 3 4 11 x 10 802PA150524MSA 80MDP150D50SA 3 4 11 x 10 Lo...

Page 48: ...led to diagnose and or correct the source of tripping If this unit is mounted in a closet the door must be closed when making this check PRESSURE SWITCH This furnace is equipped with a normally open p...

Page 49: ...nd through it to keep from overheating CAUTION DO NOT OPERATE THE SYSTEM FOR EXTENDED PE RIODS WITHOUT FILTERS A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND...

Page 50: ...replacement marking which can be obtained through the distributor if any are found to be illegible or missing REPLACEMENT PARTS Please visit www myrheem com myruud com for replace ment parts informati...

Page 51: ...ected by registers fans sunlight heat through walls pipes or wires in walls Check heat anticipator setting Furnace may need an isolation relay Check installation instructions under section titled Isol...

Page 52: ...52 Wiring Diagram FIGURE 34 FOR MODELS WITH UT ELECTRONIC CONTROLS 1028 928 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION CM 0814...

Reviews: