41
Field Selections
FIELD SELECTIONS & ADJUSTMENTS
FIELD SELECTIONS –– DIPSWITCHES
A dipswitch bank; SW1 is provided for some field adjustments .
Heating blower off delay, cooling (and heat-pump) blower off
delay, display (7-Segment) orientation and fault clear are the
adjustments and functions that can be handled using the dip-
switches .
Seven-Segment Display Orientation; SW1
As the control will be applied in a multi-position furnace a means
of changing the orientation of the seven segment display is re-
quired . This dipswitch is to be labeled SW1 . Factory setting of
the SW1 dipswitch is OFF . The factory setting display orienta-
tion is with the control placed in a vertical orientation and the low
voltage terminal block T2 is in the bottom position .
Heat Blower-Off Delay; SW2 & SW3
A means of controlling the HEAT speed blower “off” delay time
is provided . The dipswitches are labeled SW2 and SW3 . The
following table defines the settings:
SW2
SW3
OFF
OFF
90 seconds
(Factory Setting)
ON
OFF
120 seconds
OFF
ON
160 seconds
ON
ON
180 seconds
Cooling & Heat-Pump Heat Blower Off Delay; SW4
A means of controlling the COOL speed blower “off” delay time
is required . The dipswitch is labeled SW4 . The following table
defines the settings:
SW4
OFF
30 seconds (Factory Setting)
ON
45 seconds
FIGURE 30
DIPSWITCH MAP
ST-A1194-110-00
O
N
1
2
3
4
Switch Setting Orientation
Upflow
Downflow
Switch 1
Seven Segment
Display Orientation
ON
OFF
Switch Setting
Airflow Adjustments
A
B
C
D
OFF
ON
OFF OFF
OFF
ON
ON
ON
Switch Pair 4 & 5
Heat Blower Off Delay
90 Seconds (Factory)
120 Seconds
160 Seconds
180 Seconds
Manual Fault Clear
On/Off 3 TImes for Fault Clear
or
Off/On 3 times for Fault Clear
Switch Setting
Airflow Adjustments
30 Seconds (Factory)
45 Seconds
Switch 4
Cool Off Delay
ON
OFF