background image

 

ABOUT YOUR WATER HEATER 

 

WATER HEATER APPLICATION 

This water heater is designed for the purpose of heating potable water. Its use in an application other than 
this may shorten its life. 
 

MODEL TYPE 

The model Rheem

®

 Heavy Duty Gas water heater you have chosen is 

a quick recovery water heater. 
 
Water is stored in a vitreous enamel lined steel cylinder and heated by 
a  gas  burner  located  under  the  cylinder.  The  heat  produced  by  the 
burner is transferred to the water through the base of the cylinder and 
through the wall of a flue pipe which passes through the centre of the 
cylinder.  A  flue  baffle  in  this  flue  ensures  the  efficiency  of  the  water 
heater  is  correct.  The  gas  supply  to  the  burner  is  controlled  by  the 
thermostat so the water is heated to a constant temperature. 
 
Automatic safety controls are fitted to the water heater to provide safe 
and efficient operation. 
 

MAINS PRESSURE 

The water heater is designed to operate at mains pressure by connecting directly to the mains water supply. 
If the mains supply pressure in your area exceeds that 

shown on page 

18, a pressure limiting valve must be 

fitted. The supply pressure should be greater than 350 kPa for true mains pressure operation to be achieved. 
 

HOW HOT SHOULD THE WATER BE? 

The  water  heater  features  a  user  adjustable  thermostat,  which  allows 
you  to  personally  choose  the  most  suitable  temperature  for  your  hot 
water needs. Refer to 

“Temperature Adjustment”

 on page 5. 

 
To  meet  the  requirements  of  the  National  Plumbing  Standard  the 
temperature of the stored water must not be below 60°C. 
 
If this water heater is installed as an in-series booster water heater as 
part  of  a  commercial  solar  water  heating  system,  it  is  recommended 
the thermostat is set at 60°C to maximise solar contribution. 
 

Note:

  AS 3498  requires  that  a  water  heater  provides  the  means  to 

inhibit  the  growth  of  Legionella  bacteria  in  potable  water.  This  water 
heater  can  satisfy  this  AS 3498  requirement  provided  it  is  operating 
and the thermostat setting is 60°C or higher, including when it is used 
as an in-series booster water heater for a solar water heater. 
 

HOTTER WATER INCREASES THE RISK OF SCALD INJURY 

This water heater can deliver water at temperatures which can cause scalding. Check the water temperature 
before  use,  such  as  when  entering  a  shower  or  filling  a  bath  or  basin,  to  ensure  it  is  suitable  for  the 
application and will not cause scald injury. 
 
We recommend and it may also be required by regulations that an approved temperature limiting device be 
fitted into the hot water pipe work to the bathing and public areas when this water heater is installed. This will 
keep the water temperature below 50°C at the bathroom and ensuite. The risk of scald injury will be reduced 
and still allow hotter water to the kitchen and laundry. 
 

 

 

maximum thermostat 

setting 

maximum recommended 

supply temperature to 

bathrooms and ensuites 

minimum recommended 

stored water temperature 

   

 

 

Summary of Contents for 260 Litre

Page 1: ...water heater must be installed and serviced by a qualified person Please leave this guide with a responsible officer Owner s Guide and Installation Instructions Gas Heavy Duty Water Heater 260 litre m...

Page 2: ...sure accuracy in preparation of this publication No liability can be accepted for any consequences which may arise as a result of its publication Warning Upon completion of the installation and commis...

Page 3: ...ended for the installer but may be of interest About Your Water Heater 4 Regular Care 8 Water Supplies 11 Save A Service Call 14 Installation 16 Connections Plumbing 25 Multiple Installations 28 Commi...

Page 4: ...rature for your hot water needs Refer to Temperature Adjustment on page 5 To meet the requirements of the National Plumbing Standard the temperature of the stored water must not be below 60 C If this...

Page 5: ...ter heater is supplied with a thermostat an over temperature cut out and a combination temperature pressure relief valve These devices must not be tampered with or removed The water heater must not be...

Page 6: ...on valve fully at the inlet to the water heater Open the gas isolation valve fully at the inlet to the gas control Light the water heater refer to Lighting the Water Heater on page 33 GOING ON HOLIDAY...

Page 7: ...r area or you are not sure of your water chemistry have your water checked against the conditions described on pages 11 to 13 HOW LONG WILL THE WATER HEATER LAST The water heater is supported by a man...

Page 8: ...on the water heater Warning Servicing of a water heater must only be carried out by qualified personnel Phone Rheem Service or their nearest Accredited Service Agent Note The annual service and routi...

Page 9: ...mmercial applications where large volumes of hot water are used sediment may build up on the bottom of the cylinder and reduce the heating efficiency In extreme cases particularly in areas of high wat...

Page 10: ...e once every six months It is very important you raise and lower the lever gently Warning Failure to do this may result in the water heater cylinder failing Warning Exercise care to avoid any splashin...

Page 11: ...the total dissolved solids TDS content in the water is less than 2500 mg L and when the correct colour coded anode is used If an incorrect colour coded anode is used in the water heater any resultant...

Page 12: ...for two or more weeks the following procedure should be carried out before using any electrical appliances automatic washing machines and dishwashers which are connected to the hot water supply The h...

Page 13: ...Y The water heater and its components are not suitable for certain water chemistries Those chemistries are listed below If the water heater is connected at any time to a water supply with the followin...

Page 14: ...discharging too much water Refer to Temperature Pressure Relief Valve Running on page 15 Thermostat setting Ensure the thermostat setting is appropriate You may choose to adjust the thermostat upwards...

Page 15: ...vice Agent to arrange for inspection EXPANSION CONTROL VALVE RUNNING If an expansion control valve is fitted in the cold water line to the water heater refer to page 25 it may discharge a small quanti...

Page 16: ...r needs and building backup redundancy into the hot water supply system Note AS 3498 requires that a water heater provides the means to inhibit the growth of Legionella bacteria in potable water This...

Page 17: ...adequate air supply must be provided For efficient water heater operation allow two permanent openings into the room or enclosure each of at least 30 600 mm 2 for a 51 MJ model The distance between th...

Page 18: ...these horizontal distances cannot be achieved AS NZS 5601 1 states an equivalent horizontal distance measured diagonally from the nearest discharge point of the flue terminal to the opening may be de...

Page 19: ...Where a temperature limiting device is installed adjacent to the water heater the cold water line to the temperature limiting device can be branched off the cold water line either before or after the...

Page 20: ...ed hot water flow and return pipe If circulated tempered water were to be returned back to the water heater depending on the location of the return line connection on the water supply line to the wate...

Page 21: ...cally fitted as standard Total Dissolved Solids Anode colour code 0 40 mg L Green 40 150 mg L Green or Black 150 400 mg L Black 400 600 mg L Black or Blue 600 2500 mg L Blue 2500 mg L Blue no cylinder...

Page 22: ...ressure kPa Test Point Gas Pressure kPa Max Gas Pressure kPa 620 260 630 260 620 260 630 260 620 260 630 260 620 260 630 260 Natural 51 1 13 1 00 3 50 Propane 47 2 75 2 70 3 50 Butane 39 2 75 2 70 3 5...

Page 23: ...INSTALLATION 23 TYPICAL INSTALLATION OUTDOOR LOCATION INSTALLATION HEAVY DUTY GAS OUTDOOR 260L...

Page 24: ...INSTALLATION 24 TYPICAL INSTALLATION INDOOR LOCATION...

Page 25: ...non return valve must be installed on the cold water line to the water heater An acceptable arrangement is shown in the diagram or on page 30 for multiple installations Refer also to Hot Water Delive...

Page 26: ...heater Connect the drain lines to the valves using disconnection unions The drain line from the valve to the point of discharge should be as short as possible have a continuous fall all the way from t...

Page 27: ...pipe size selection must take into account the gas input of this water heater refer to table on page 22 as well as all of the other gas appliances in the premises Warning Always isolate the water hea...

Page 28: ...ts of both AS NZS 3500 4 and the application 5 A non return valve isolation valve and if required a pressure limiting valve and expansion control valve must be installed on the cold water line to the...

Page 29: ...MULTIPLE INSTALLATIONS 29 Back to Back Manifold Single Bank of Water Heaters Multiple Banks of Water Heaters TPR Valve Drain Line Common Discharge Point Angle Manifold In Line Manifold...

Page 30: ...F INSTALLATION LAYOUT MINIMUM DIMENSIONS Notes Installation Layout Minimum Dimensions 1 A minimum of 900 mm E F should be left in front of the water heater for access servicing and water heater remova...

Page 31: ...MULTIPLE INSTALLATIONS 31 MANIFOLD ARRANGEMENT Hot Manifold Assembly Cold Manifold Assembly...

Page 32: ...or ignite when the water heater is turned on Explain to the householder or a responsible officer the functions and operation of the water heater GAS INLET PRESSURE IMPORTANT CHECK the gas supply press...

Page 33: ...series booster water heater for a solar water heater SAFETY INFORMATION A This water heater is equipped with an igniter button which lights the pilot When lighting the pilot follow these instructions...

Page 34: ...knob and check the pilot is still alight The pilot can be checked by looking through the large opening below the gas control 10 If the pilot has failed to light or has not remained alight turn the ga...

Page 35: ...e refer to Rheem Service or their nearest Accredited Service Agent If unable to get the water heater working properly contact Rheem Service or their nearest Accredited Service Agent When satisfied eve...

Page 36: ...32 Close all hot water taps Operate the relief valve release lever do not let the lever snap back or you will damage the valve seat Operating the lever will release the pressure in the water heater A...

Page 37: ...37 This page is intentionally blank...

Page 38: ...38 This page is intentionally blank...

Page 39: ...nstalled site shall be the owner s responsibility 2 5 Where the water heater is installed in a position that does not allow safe or ready access the cost of that access including the cost of additiona...

Page 40: ...efect and in any event within the applicable warranty period 4 2 You are not entitled to make a claim under this warranty if your water heater a Does not have its original serial numbers or rating lab...

Reviews: