16 

INSTALLATION 

 

THIS WATER HEATER IS NOT SUITABLE FOR POOL HEATING. 
Check the water heater is suitable for the gas type available. 
(refer to the rating label on the water heater) 

 

INSTALLATION STANDARDS 

The water heater must be installed: 

 

by a qualified person, and 

 

in accordance the installation instructions, and 

 

in  compliance  with  Standards  AS/NZS 3500.4,  AS 5601  or  AS/NZS 5601.1,  as  applicable  under  local 
regulations, and all local codes and regulatory authority requirements. 

 
In New Zealand the installation must also conform with NZS 5261, as applicable under local regulations, and 
the New Zealand Building Code. 
 
All  packaging  materials  must  be  removed  from  the  water  heater  prior  to  its  installation.  This  includes  the 
removal  of  the  cardboard  base  of  the  carton  from  the  underside  of  the  water  heater  and  the  protective 
packaging from the draught diverter of an indoor model. 
 

WATER HEATER APPLICATION 

This water heater is designed for the purpose of heating potable water. Its use in an application other than 
this may shorten its life. 
 
If this water heater is to be used where an uninterrupted hot water supply is necessary for the application or 
business,  then  there  should  be  redundancy  within  the  hot  water  system  design.  This  should  ensure  the 
continuity of hot water supply in the event that this water heater was to become inoperable for any reason. 
We recommend you provide advice to the system owner about their needs and building backup redundancy 
into the hot water supply system. 
 

Note:

 AS 3498 requires that a water heater provides the means to inhibit the growth of Legionella bacteria in 

potable  water.  This  water  heater  can  satisfy  this  AS 3498  requirement  provided  it  is  operating  and  the 
thermostat setting is 60°C or higher, including when it is used as an in-series booster water heater for a solar 
water heater. 
 

WATER HEATER LOCATION 

An indoor model must be installed indoors and an outdoor model must 
be installed outdoors. 
 
The water heater should be installed close to the most frequently used 
outlets  or  with  a  circulated  flow  and  return  system  and  its  position 
chosen with safety and service in mind. Make sure people (particularly 
children)  will not touch the  flue outlet. The flue terminal must be clear 
of obstructions and shrubbery. 
 
Clearance must be allowed for servicing of the water heater. The water 
heater  must  be  accessible  without  the  use  of  a  ladder  or  scaffold. 
Make  sure  the  temperature  pressure  relief  valve  lever  is  accessible 
and the front cover and burner can be removed for service. 
 
You must be able to read the information on the rating plate. If possible 
leave  headroom  of  one  water  heater  height  so  the  anode  can  be 
inspected or replaced. Remember  you may have to remove the entire 
water heater later for servicing. 
 
The water heater must not be installed in an area with a corrosive atmosphere where chemicals are stored or 
where aerosol propellants are released. Remember the air may be safe to breathe, but when it goes through 
a flame, chemical changes take place which may attack the water heater. 

 

 

Summary of Contents for 260 Litre

Page 1: ...water heater must be installed and serviced by a qualified person Please leave this guide with a responsible officer Owner s Guide and Installation Instructions Gas Heavy Duty Water Heater 260 litre m...

Page 2: ...sure accuracy in preparation of this publication No liability can be accepted for any consequences which may arise as a result of its publication Warning Upon completion of the installation and commis...

Page 3: ...ended for the installer but may be of interest About Your Water Heater 4 Regular Care 8 Water Supplies 11 Save A Service Call 14 Installation 16 Connections Plumbing 25 Multiple Installations 28 Commi...

Page 4: ...rature for your hot water needs Refer to Temperature Adjustment on page 5 To meet the requirements of the National Plumbing Standard the temperature of the stored water must not be below 60 C If this...

Page 5: ...ter heater is supplied with a thermostat an over temperature cut out and a combination temperature pressure relief valve These devices must not be tampered with or removed The water heater must not be...

Page 6: ...on valve fully at the inlet to the water heater Open the gas isolation valve fully at the inlet to the gas control Light the water heater refer to Lighting the Water Heater on page 33 GOING ON HOLIDAY...

Page 7: ...r area or you are not sure of your water chemistry have your water checked against the conditions described on pages 11 to 13 HOW LONG WILL THE WATER HEATER LAST The water heater is supported by a man...

Page 8: ...on the water heater Warning Servicing of a water heater must only be carried out by qualified personnel Phone Rheem Service or their nearest Accredited Service Agent Note The annual service and routi...

Page 9: ...mmercial applications where large volumes of hot water are used sediment may build up on the bottom of the cylinder and reduce the heating efficiency In extreme cases particularly in areas of high wat...

Page 10: ...e once every six months It is very important you raise and lower the lever gently Warning Failure to do this may result in the water heater cylinder failing Warning Exercise care to avoid any splashin...

Page 11: ...the total dissolved solids TDS content in the water is less than 2500 mg L and when the correct colour coded anode is used If an incorrect colour coded anode is used in the water heater any resultant...

Page 12: ...for two or more weeks the following procedure should be carried out before using any electrical appliances automatic washing machines and dishwashers which are connected to the hot water supply The h...

Page 13: ...Y The water heater and its components are not suitable for certain water chemistries Those chemistries are listed below If the water heater is connected at any time to a water supply with the followin...

Page 14: ...discharging too much water Refer to Temperature Pressure Relief Valve Running on page 15 Thermostat setting Ensure the thermostat setting is appropriate You may choose to adjust the thermostat upwards...

Page 15: ...vice Agent to arrange for inspection EXPANSION CONTROL VALVE RUNNING If an expansion control valve is fitted in the cold water line to the water heater refer to page 25 it may discharge a small quanti...

Page 16: ...r needs and building backup redundancy into the hot water supply system Note AS 3498 requires that a water heater provides the means to inhibit the growth of Legionella bacteria in potable water This...

Page 17: ...adequate air supply must be provided For efficient water heater operation allow two permanent openings into the room or enclosure each of at least 30 600 mm 2 for a 51 MJ model The distance between th...

Page 18: ...these horizontal distances cannot be achieved AS NZS 5601 1 states an equivalent horizontal distance measured diagonally from the nearest discharge point of the flue terminal to the opening may be de...

Page 19: ...Where a temperature limiting device is installed adjacent to the water heater the cold water line to the temperature limiting device can be branched off the cold water line either before or after the...

Page 20: ...ed hot water flow and return pipe If circulated tempered water were to be returned back to the water heater depending on the location of the return line connection on the water supply line to the wate...

Page 21: ...cally fitted as standard Total Dissolved Solids Anode colour code 0 40 mg L Green 40 150 mg L Green or Black 150 400 mg L Black 400 600 mg L Black or Blue 600 2500 mg L Blue 2500 mg L Blue no cylinder...

Page 22: ...ressure kPa Test Point Gas Pressure kPa Max Gas Pressure kPa 620 260 630 260 620 260 630 260 620 260 630 260 620 260 630 260 Natural 51 1 13 1 00 3 50 Propane 47 2 75 2 70 3 50 Butane 39 2 75 2 70 3 5...

Page 23: ...INSTALLATION 23 TYPICAL INSTALLATION OUTDOOR LOCATION INSTALLATION HEAVY DUTY GAS OUTDOOR 260L...

Page 24: ...INSTALLATION 24 TYPICAL INSTALLATION INDOOR LOCATION...

Page 25: ...non return valve must be installed on the cold water line to the water heater An acceptable arrangement is shown in the diagram or on page 30 for multiple installations Refer also to Hot Water Delive...

Page 26: ...heater Connect the drain lines to the valves using disconnection unions The drain line from the valve to the point of discharge should be as short as possible have a continuous fall all the way from t...

Page 27: ...pipe size selection must take into account the gas input of this water heater refer to table on page 22 as well as all of the other gas appliances in the premises Warning Always isolate the water hea...

Page 28: ...ts of both AS NZS 3500 4 and the application 5 A non return valve isolation valve and if required a pressure limiting valve and expansion control valve must be installed on the cold water line to the...

Page 29: ...MULTIPLE INSTALLATIONS 29 Back to Back Manifold Single Bank of Water Heaters Multiple Banks of Water Heaters TPR Valve Drain Line Common Discharge Point Angle Manifold In Line Manifold...

Page 30: ...F INSTALLATION LAYOUT MINIMUM DIMENSIONS Notes Installation Layout Minimum Dimensions 1 A minimum of 900 mm E F should be left in front of the water heater for access servicing and water heater remova...

Page 31: ...MULTIPLE INSTALLATIONS 31 MANIFOLD ARRANGEMENT Hot Manifold Assembly Cold Manifold Assembly...

Page 32: ...or ignite when the water heater is turned on Explain to the householder or a responsible officer the functions and operation of the water heater GAS INLET PRESSURE IMPORTANT CHECK the gas supply press...

Page 33: ...series booster water heater for a solar water heater SAFETY INFORMATION A This water heater is equipped with an igniter button which lights the pilot When lighting the pilot follow these instructions...

Page 34: ...knob and check the pilot is still alight The pilot can be checked by looking through the large opening below the gas control 10 If the pilot has failed to light or has not remained alight turn the ga...

Page 35: ...e refer to Rheem Service or their nearest Accredited Service Agent If unable to get the water heater working properly contact Rheem Service or their nearest Accredited Service Agent When satisfied eve...

Page 36: ...32 Close all hot water taps Operate the relief valve release lever do not let the lever snap back or you will damage the valve seat Operating the lever will release the pressure in the water heater A...

Page 37: ...37 This page is intentionally blank...

Page 38: ...38 This page is intentionally blank...

Page 39: ...nstalled site shall be the owner s responsibility 2 5 Where the water heater is installed in a position that does not allow safe or ready access the cost of that access including the cost of additiona...

Page 40: ...efect and in any event within the applicable warranty period 4 2 You are not entitled to make a claim under this warranty if your water heater a Does not have its original serial numbers or rating lab...

Reviews: