RFS INSTALLATION GUIDELINES
HYBRIFLEX
®
CABLE|603400210500|September 2020
Visit
for the most current product specifications
Page 36 of 43
System loss measurement (sector jumper connected to main assembly)
Verify that all end-faces are clean and free of any debris.
Connect loopback and test equipment as shown Follow test
equipment instructions to record test result, referring to the
system insertion loss table for pass/fail criteria.
Note
: When using OTDR, the longer the loopback the better
the test result. RFS recommends a loopback of 30m (min) be
used. Lookback modules may be used with power meters but
not recommended for OTDR.
Test diagram using ODM
power meter or similar
device
Breakout
termination
HYBRIFLEX cable
HYBRIFLEX
Jumper
Fiber
breakout
Loopback
recommenm
Loopback
Module
Test diagram
using OTDR
device