Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
Notes for use in Hazardous Locations
Zone classification
usable in zone
ATEX
category
IEC-Ex
Equipement
Protection Level (EPL)
Dust applications 20, 21, 22
1 D
Da
21, 22
2 D
Db
22
3 D *
Dc
Gas applications
0, 1, 2
1 G
Ga
1, 2
2 G
Gb
2
3 G
Gc
General Notes
Marking
Devices with Ex approval are marked on the name plate.
Process pressure
The device construction allows process over-pressure up to 25 bar (363 psi). These pressure is
allowed for test purposes. The definition of the Ex approvals are only valid for a container-over-
pressure between -0.2..+0.1 bar (-2.9..+1.45psi).
For higher or lower pressures the approvals are not valid.
Process and ambient
temperature
The permitted temperature ranges are marked on the name plate.
* in case of conductive dust additional
requirements for the installation may
be necessary
Permitted zones (categories) for mounting in partition wall
EPL (IEC-Ex)
Db
Gb
Db
Category (ATEX)
2D
2G
2D
Zone
21
1
21
EPL (IEC-Ex)
Da
Gb
Da
Category (ATEX)
1D
2G
1D
Zone
20
1
20
Rod
Rope
Rod,
Remote
version
Rope,
Remote
version
Standard
housing
d-housing
de-housing
With
Standard
housing
With
d- and de-
housing
RF 3100
RF 3200
RF 3300
RFnivo
®
1
2
3
4
5
6
7
8
9
10
11
12
RF 3000 d
gi241014