Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
Assembly - Remote version / FM Control drawing
Electronic side
Probe side
Assembly instruction:
Probe side:
Connect remote cable.
Obtain right connecting sequence.
The inner conductor and both shield conductors
of the remote cable must not touch other
metal parts. The delivered isolation hoses
must be assembled according to the delivered
instruction.
Electronic side:
1. Feed remote cable though the cable gland at
the tube.
2. Connect remote cable to the plug.
See notes above.
3. Check wiring electrically:
No short circuit must be present between
terminal 10 and 11, 10 and 12, 11 and 12.
4. Connect plug and mating plug.
5. Screw the tube into the threaded bush. While
doing this, move the remote cable downwards.
Take care, that the plug is not getting loose.
While screwing, the cable gland must be open to
avoid, that the wires are beeing twisted.
Note: Inside the threaded bush is a seal ring
which seals the tube to the threaded bush.
6. Tighten the cable gland on the tube.
7. Fasten the two fixing screws.
Tube
Plug
Mating
plug
Mating
plug
Threaded
bush
Threaded
bush
Cable
gland
Fixing
screws
Fixing
screws
All cable glands used for the remote cable
must be closed tightly to reach ingress
protection.
The cable glands must be protected against
mechanical damage.
Original remote cable from the supplier must
be used.
For Hazardous Locations:
Remote cable has intrinsically safe circuit.
Substitution of components may impair
intrinsic safety.
Standard
housing
d- and de-
housing
Versions (for FM, FMc):
Standard housing:
Model RF 3*00 * N .... with option pos.12x
Cl. II, III Div.1 Gr. E,F,G
"d" housing:
Model RF 3*00 * U .... with option pos.12x
XP-IS Cl. I,II,III Div.1 Gr. B-G and
Cl. I Zone 1 Gr. IIB+H2
Remote cable:
Special triaxial cable
Length max. 20m (65ft)
Min. bending radius: 50mm (2")
10 = Probe
11 = Shield
12 = Ground
10 = Probe
11 = Shield
12 = Ground