Triple  IR  Flame  Detector

RFD-3000X

Document  No.  Manual

3000X  (Rev.  05)                                                                                              March  2012

-  6  -

2.    Technical  Specifications

 

2.1    Electrical  Specifications

2.1.1    Operating  Voltage  and  Power  Consumption

ㆍ  Recommended  Operating  Voltage  :  24VDC

ㆍ  Rating  Voltage  :  18VDC  ~  30VDC

ㆍ  Max  Input  Voltage  :  30VDC

ㆍ  Max  Consumption  Power  :  4.5W  (at  30VDC  )

ㆍ  Normal  Average  Current  :  approximate  100mA  (at  24VDC)

ㆍ  Max  Operating  Current  :  approximate  150mA 

  (at  18VDC~30VDC,  during  detection  of  fire  or  self-diagnosis  test)

2.1.2    Relay  Output

ㆍ  3A  30VDC,  3A  277VAC

ㆍ  Dry  contact

ㆍ  A(Normal  Open)  or  B(Normal  close)

2.1.3    0-20mA  Current  Output

ㆍ  Non-isolation  output,  Common  GND(-Power)

ㆍ  Max.  Terminating  Resistance    :  400Ω

ㆍ  0mA    (+0.5mA)  :  Connection  Fault,  Low  Power  Fault

ㆍ  2mA    (±0.5mA)  :  Self-diagnosis  test  Fault

ㆍ  4mA    (±0.5mA)  :  Normal

ㆍ  8mA    (±0.5mA)  :  Initialize  Circuit  Fault

ㆍ  12mA  (±0.5mA)  :  Self-diagnosis  Test  Excution

ㆍ  16mA  (±0.5mA)  :  Warning

ㆍ  20mA  (±0.5mA)  :  Fire  Detection

2.1.4    RS485  Communication

ㆍ  Non-isolation  output  (2  wiring)

ㆍ  Communication  Speed  :  4800,  9600,  19200,  38400bps  (dip-switch  selectable,)

                                                      Detector  must  be  reset  after  change  communication  speed.

Summary of Contents for RFD-3000X

Page 1: ...Flame detector Triple IR RFD 3000X User s Manual Rezontech co ltd...

Page 2: ...ons 3 1 2 Components 3 1 2 1 Fundamental components 3 1 2 2 Spare components 3 1 3 Necessary tools 3 2 Selection of Installation Location 3 2 1 Cone of Vision 3 2 1 1 Fuel 3 2 1 2 Cone of Vision 3 2 2...

Page 3: ...Output Setting Fault RELAY Output Setting Current Output 3 3 4 5 Setting Self Diagnosis Function 3 3 4 6 Setting Communication Configuration Setting RS485 Communication Enable Setting Detector Addres...

Page 4: ...g 1Hz or blinking 2Hz with delay 0 5sec repeatedly 5 3 4 When receiver unable to detect various signal 41 41 41 41 41 6 Customer Support 6 1 Contacts Information 42 7 Appendix 7 1 Abbreviation 7 2 Cho...

Page 5: ...ch enables it to be widely used in various applications 1 2 Contents of User Manual This operating manual describes detector and its features Its contents of 7 different sections as per stated on Tabl...

Page 6: ...r representative from which the original shipment was made In all cases this warranty is limited to the cost of the product supplied by Rezontech The customer will assume all liability for the misuse...

Page 7: ...ring detection of fire or self diagnosis test 2 1 2 Relay Output 3A 30VDC 3A 277VAC Dry contact A Normal Open or B Normal close 2 1 3 0 20mA Current Output Non isolation output Common GND Power Max Te...

Page 8: ...Normal Green LED lighting Power supply fault Orange LED blinking 2Hz Self diagnosis test fault Any of LEDs simultaneously blinking 1Hz at where the channels having detection problem Initializing Circ...

Page 9: ...teel Weight Body approximate 3 5 Overall approximate 4 5 Dimension Body W5 3 134 H4 6 117 D4 3 112 inch mm Dimension Overall W5 3 134 H6 41 163 D14 0 356 inch mm Color Metal Electrical connection Exte...

Page 10: ...Ltd Triple IR Flame Detector RFD 3000X Document No Manual 3000X Rev 05 March 2012 9 2 3 Environmental Specifications Operating Temperature 40 75 Storage Temperature 50 80 Humidity Relative humidity 9...

Page 11: ...ompositions RFD 3000X Flame Detector 1 EA BK 02 Bracket 1 EA Spare Bolt 1 set Tools 3 1 2 Components 3 1 2 1 Fundamental components Component standard Q ty pcs Description Hexagon wrench Bolt M6 10 2...

Page 12: ...D 3000X Document No Manual 3000X Rev 05 March 2012 11 3 1 3 Necessary tools Tool name Standard Q ty pcs Description Hexagon wrench driver Metric 5M 1 Join the detector bracket Screw driver 1 Install t...

Page 13: ...minimum necessary to install detectors in proper position for its essential function which is detection of fire According to the purpose for which user want to use please use the information 3 2 1 Co...

Page 14: ...ty of false alarm sources False alarm sources in Table 7 are representative samples of detector response in the presence of false stimuli Radiation Source Immunity Distance ft m reflected sunlight ref...

Page 15: ...internal external etc Selecting place of installation according to detection distance and angle Range of Temperature Min Max of place usage installation Avoid those area which have obstructed object...

Page 16: ...all the conduit including drain holes facing downward to avoid water condensation in the detector Any conduit entry not used during installation shall be plugged with suitably rated and approved condu...

Page 17: ...crew Enclosure Material 316 Stainless Steel Weight Body approximate 3 5 Overall approximate 4 5 Dimension Body W5 3 134 H4 6 117 D4 3 112 inch mm Dimension Overall W5 3 134 H6 4 163 D14 0 356 inch mm...

Page 18: ...anual 3000X Rev 05 March 2012 17 4 Holes on bracket for mounting detector Mount the bracket with M5 30 4pcs bolts Refer to Figure 7 Detector can be installed on the wall or the ceiling with bracket Re...

Page 19: ...e connection of the electrical wiring are connected to each system or product as stated below 3 3 3 1 Terminal blocks The detector has terminal blocks TB1 TB2 as shown in Figure 8 Each of terminals in...

Page 20: ...t loop line normal close FLT_COM Fault loop line common ALM_N O Alarm loop line normal open ALM_COM Alarm loop line common ALM_N C Alarm loop line normal close TB2 SELF TEST Self diagnosis input EXT_R...

Page 21: ...ated according to detector s condition Terminal Block Terminal Label Relay status Normal De Energized Alarm Energized TB1 ALM_N C Normally Closed N C Normally Open N O ALM_N O Normally Open N O Normal...

Page 22: ...ergized TB1 FLT_N C Normally Closed N C Normally Open N O FLT_COM Common Common 3A 30VDC 3A 277VAC FLT_N C is Default If SW1 8 is ON fault output is disabled Table 12 Fault Relay Operating Status Note...

Page 23: ...Flame Detector RFD 3000X Document No Manual 3000X Rev 05 March 2012 22 Interlink wiring of Power Supply Alarm and fault Relay Disconnection error check with EOL Figure 10 Typical wiring for fault and...

Page 24: ...imary stage before the real fire is confirmed This signal only occurs within delay time Warning Relay operated according to detector s condition Terminal Block Terminal Label Relay status Normal De En...

Page 25: ...ble 14 for using current output and its status Terminal Block Terminal Label Detector Status Current Output mA TB2 0 20mA Connection fault 0 Self diagnosis fault 2 Normal standby 4 Initializing Circui...

Page 26: ...use through interlinking remote control machine or other system Terminal Block Terminal Label Connection TB2 485 RS485 A 485 RS485 B Table 15 RS485 Terminals and their Connection description Communic...

Page 27: ...rminal Block Terminal Label Connection TB2 EXT_Rst External recovery signal line Table 16 External recover connection Signal Specification Operating Signal Short circuit 1second to GND and then Open c...

Page 28: ...uit to GND Operating delayed time 1 seconds Operating continuous time operating delayed time 10 secs approx 20 secs The result of signal Result signal Normal Fault Normal output for all signals Fault...

Page 29: ...s See Figure 16 3 3 4 1 Programmable switches and jumper Figure 16 Programmable Dip switches and external reset Jumper Switch Description SW1 Controls and sets Sensitivity Delay time and output relay...

Page 30: ...ot responsible in this case Setting method of sensitivity Turn off the power during switch setting Turn on the power after changing the switch SW1 1 SW1 2 SW1 Setting Sensitivity Range of Sensitivity...

Page 31: ...the detector returns to its standby state The Alarm delay option affects the output relays and the 0 20mA If current output is available SW3 1 is ON The LEDs and outputs indicate warning level during...

Page 32: ...See Figure 14 and 16 and the other is using RS485 communication SW1 Switch Setting Function SW1 5 OFF Automatic Recover ON Alarm Latch Table 22 Switch setting for recovering signal of fire detection S...

Page 33: ...ection or all kinds fault detection not needed by setting the SW1 8 to ON SW1 Switch Setting Function SW1 8 OFF Fault Relay Output N C default ON Fault Relay Output N O Table 24 Switch setting for FAU...

Page 34: ...or sensor itself for radiant energy as well as cleanness of transmission windows If there are some fault on internal circuit or decrease of transmission intensity with obscured glass from oil vapor or...

Page 35: ...ION enabled Table 27 Setting of RS485 Communication Enable Setting Detector Address This is a feature to set the address of detectors to identify each of them when the user use RS485 communication Ava...

Page 36: ...4800 bps OFF ON 19200 bps ON ON 38400 bps Table 29 Setting of BAUD Rate 3 3 5 Ground Connection For proper operation of the detector the RFD 3000X must be grounded through a wire to the chassis Failur...

Page 37: ...alled and operated the product properly there are a few issues to be inspected or taken into account as stated below 4 1 1 Inspection of Installation Conditions If there are any inferior or bad instal...

Page 38: ...lay signal open Energized LED Fault signal output Current output Fault signal When SW3 1 is ON RS485 Communication Fault signal When SW3 2 is ON Table 30 Initial Operation of Product 4 3 Safety Handli...

Page 39: ...equipment before testing Testing Sequences 1 Please wait for about 10seconds after the power is supplied Check if Green LED is turn on 2 Face and Turn On the TL3000 in front of the flame detector 3 Th...

Page 40: ...peration Status Vary According to Testing Conditions Status Operate or Output Status Before connecting power Fault Relay signal open de energized All LED OFF After connecting power connecting power Fa...

Page 41: ...of cleaning operations depends upon the local environmental conditions and specific applications The fire detection system designer will give his recommendations 1 Disconnect power to the detector be...

Page 42: ...it fall below operation range of operation The product may be polluted by foreign substances on the connector during the combination Please check the internal wired connector Please contact the manufa...

Page 43: ...March 2012 42 6 Customer Support 6 1 Contacts Information Rezontech Office Address Phone Fax E Mail South Korea TEL 82 1544 9108 FAX 82 31 420 0800 E Mail yacht rezontech com 805 Megavally Gwanyang d...

Page 44: ...n has been removed LED Light Emitting Diode mA Milli Ampere 0 001 ampere N C Normal Close N O Normal Open Table 34 Various Types of Abbreviation 7 2 Choosing of Wiring Kindly consider the electric wir...

Page 45: ...ngth for installation overall space or partly space The necessary voltage range for product The minimum range of power supply voltage Setting of electrical wiring in order for the product to function...

Reviews: